INTERRUPTOR MONOPOLAR SIMPLES
S INTERRUPTOR MONOPOLAR 2 SEÇÕES
S 3W INTERRUPTOR THREE WAY
L04b L04b L04b L04b L04b L04b QUADRO DE DISTRIBUIÇÃO DE FORÇA E LUZ
L05 L05 DE CONDUTORES COM BITOLA IGUAL OU SUPERIOR A 16mm2 DEVERÃO SER EXECUTADAS COM CONECTORES DE PRESSÃO MONTADOS
L01b
L12a L12a L12a SALÃO DE VENDAS COM FERRAMENTAS ADEQUADAS.
6- PARA A PASSAGEM DOS FIOS E CABOS VERIFICAR A LIMPEZA DAS CAIXAS DE PASSAGEM E ELETRODUTOS.
CPD 7- O FIO NEUTRO NÃO PODERÁ SER LIGADO AO FIO TERRA.
8-PARA CADA LUMINÁRIA DE EMERGÊNCIA AUTÔNOMA, CONSIDERAR UMA TOMADA 2P+T 220V PADRÃO BRASILEIRO INSTALADA NO
L11a L11a L11a L11a PERFILADO. A LUMINÁRIA DE EMERGÊNCIA DEVERÁ TER AUTONOMIA DE 2HS DE FUNCIONAMENTO ININTERRUPTO.
9- TODOS OS ELEMENTOS METÁLICOS DEVERÃO SER ATERRADOS COM TERMINAL AO CONDUTOR DE PROTEÇÃO.
SALA REUNIÃO L06 10- TODOS ELETRODUTOS DEVERÃO SER DE AÇO GALVANIZADO, DIÂMETRO 3/4", QUANDO NÃO BITOLADOS. QUANDO EMBUTIDOS NO
L01b
PISO, DEVERÃO SER DO TIPO CORRUGADO REFORÇADO, DIÂMETRO 3/4", TAMBÉM QUANDO NÃO BITOLADOS.
3w
L1b
11- TODOS OS ELETRODUTOS DEVERÃO CONTER O CONDUTOR DE PROTEÇÃO.
L06
12- AS CAIXAS DE PASSAGEM APARENTES SERÃO DO TIPO CONDULETE DE ALUMÍNIO FUNDIDO COM TAMPA E GUARNIÇÕES DE
L06 L06 NEOPRENE, QUANDO EMBUTIDAS EMBUTIDAS DEVERÃO SER DE FERRO GALVANIZADO;
L11a L11a L11a L11a 13- OS PERFILADOS DEVERÃO SER EM CHAPA DE AÇO GALVANIZADO LISO E SEM TAMPA.
14- TODAS AS DERIVAÇÕES E TERMINAÇÕES DEVERÃO FICAR EM CAIXAS METÁLICAS DE FERRO GALVANIZADO COM TAMPA FIXADA COM
PARAFUSOS DO TIPO IMPERDÍVEIS.
16- NAS EXTREMIDADES DOS ELETRODUTOS DEVERÃO SER UTILIZADAS BUCHAS E ARRUELAS DE ARREMATE.
L12a
L12a L12a L12a 17- OS CONDUTORES DEVERÃO SER DO TIPO ANTI-CHAMA, TÊMPERA MOLE, ISOLAÇÃO EM PVC 750V/70ºC EM SERVIÇO, 100ºC EM
E10
SOBRECARGA, 160ºC EM CURTO, COM SEÇÃO MÍNIMA DE 2,5mm² PARA FORÇA E LUZ. SEGUIR ORIENTAÇÕES DO MEMORIAL
L12a
APARENTES.
L12a
L06 L06
L11a,b
22 - OS CABOS ALIMENTADORES DE PAINEIS DEVEM TER ISOLAÇÃO 0,6/1 KV E OS CABOS DAS TOMADAS E LUMINÁRIAS ISOLAÇÃO 750V,
L012a,b L11a L11a L11a L11a TODOS COM CARACTERÍSTICAS DE NÃO PROPAGAÇÃO DE FOGO, LIVRES DE HALOGÊNIOS E SEM LIBERAÇÃO DE GASES TÓXICOS;
L12a,b
L12b L12b
RECEPÇÃO L12b
L06 L06
L06 L06
QGBT
FILIAL
L12b L12b L12b QDLT ENTRADA DE
ENERGIA
L06
L06 3w
L11a L11a L11a L11a
DEPÓSITO
L13
L16
L07 L07
L07 BANHEIRO FEMININO BANHEIRO MASCULINO COPA
L07
L16
L14 L14 L15 L15
L12b L12b L12b L12b L12b L12b L12b
SECRETÁRIA DIRETOR L13 L11a L11a L11a L11a
L08 L13 L15 L16
L14 L15 L16
L14
L11b L11b L11b L11b L11b L11b L11b L11b L11a L11a L11a L11a
L09
DEPÓSITO
L09
DIRETORIA/REMOTO
DIRETOR
L11b L11b L11b L11b L11b L11b L11b L11b L11a L11a L11a L11a
L08 L08
L09
L10
L10
L10
L11b L11b L11b L11b L11b L11b L11b L11b L11a L11a L11a L11a
L08 L08 L10
00 20/10/2017 JP PROJETOS EMISSÃO DE PROJETO EXECUTIVO. LIBERADO PARA COTAÇÃO
BANHEIRO
L10
DIRETORIA JPPROJETOS ARQUITETURA E GERENCIAMENTO
Rua Doutor Ladyr Ribeiro, Nº:36 - Camboinhas - Niterói - RJ
Rua do Rócio, 423, Vila Olimpia - São Paulo - SP
Tel.: (21) 2609-3138 / fax: (21) 2608-2761 / Tel.: (11) 3045-3386
email: adm@jpprojetos.com
PROJETO:
SULAMÉRICA
AVENIDA ANGÉLICA, 2330 - ED. NEW ENGLAND, 9° ANDAR - HIGIENÓPOLIS - SÃO PAULO - SP
TÍTULO: PRANCHA:
PLANTA BAIXA - 9º ANDAR
01
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
PLANTA DE ILUMINAÇÃO
002
ARQUIVO: EMISSÃO INICIAL: ESCALA: REVISÃO: