DRYING TECHNOLOGIES
9000 aprox.
MAHILD MAHILD MAHILD MAHILD
7400
DRYING TECHNOLOGIES DRYING TECHNOLOGIES DRYING TECHNOLOGIES DRYING TECHNOLOGIES
5160
7940
8200
2100 8965
10000 ca 9020 11065
8965 800
9765
Sala de control por o cliente
vapor e maxima distancia 3 metros da estufa
condensado
agua frio HPS
700
5160
5200
1
** 8620
* max 3 metros distancia hacia camara de secado
Section B-B:
8965
60
100 + 500
290 600
tina 1% Bodengefälle
determinar por el arquitecto
150
Profundidad fundacion a
Conectrar al sistema
de dreinaje
via siphon
500
+/- 0 Punkt Y
1050
*
*
+500
1390 *
2100
"Z"
750 * 750
+500
2100
8965
8565
200
+500
2100
1% Bodengefälle
A 1% Pendiente
A
1%Slope to drain
-150
300
400
100
100 8820
100
B 8820
* distancia a ser definido por el cliente
60 Side and
rear wall.
60
Punkt " Y "
Detail " Y "
Pressure: 10 bar
Temperature: 180 C
DN 125 DN 65 max. Pressure: 10 bar
DN 100 DN 40 R13S Vertical
max. delta P 13 bar Peak consumption: heating 4,4 to/h
DN 100
M V
DN 125 NB:
Ari incorpora
DN 100 anti-retorno
Water conditions:
en trampa
Pressure: 3-5 bar
Peak consumption spray: 860 ltr/h
DN 50 DN 40 R13 Vertical
max. delta p 13 bar
DN 50
M Reco Bath
DN 65 DN 40
V
Cold water flow schematics, kiln type Mh2000, water supply reco:
exterior
3/8“
Reco1
3/4“
3/4“
3/4“
MAHILD DRYING TECHNOLOGIES GMBH
Schematic demonstration of piping and control valve installation. Final design and engineering by customers heating company in Meisenweg 1 Projekt: LM Madeiras , Formas Fundamento, Maßstab
function of loacal situation of the boiler installation and considering local rules and regulations. Piping will terminate about 10 cm 72622 Nürtingen Electricidade, Tubulacao Scale
outside the kiln walls. Configuration and delivery of piping and cold water distribution system outside the kiln by others. Scope of Germany
delivery includes manual valves and motor valves as indicated in drawing excluding counter flanges towards piping. Piping Tel. +49-7022-66926 Zeichn.Nr./Drawing no.: 236122-001-001 pagina 6/12
reductions and manifolds and all other technical necessary devices by others. FAX+49-7022-62121 Gez.: none
gez. kd-cad gepr. la 23.10.2023
DRYING TECHNOLOGIES
Circuito agua fria de humidificacao, secador tipo MH2000ACT, humidificacao : Condiciones de agua:
WLHPS
Wassertank
durch
MAHILD
kiln wall
Camara 2 B2
MC1..4
MC5..8
22 kW 11kW 4 kW 50 W 50 W 15 W
..
2x
VA
DB/WB
HV HV WLHPS WV
VA
F F
HPS KDM1
T
Pos. 3
Pos. 4 Pos. 13
3x1,5 mm2
Ethernet
Ethernet
380/3/60
230/1/60 Mahild recommends to supply separate 230/1/60
Opt. USV voltage for control network 230 V possible Opt. USV
with USV unit for PLC or PC or both.
Side View:
DB2
MC...... Moisture Content sensor
DB...... Dry Bulb
WB..... Web Bulb
DAM... Data Aquisition module
MC1..
MC8....Moisture measuring points
Top VIew:
MC4 MC8
MC2
MC6
DAM
MC1 MAHILD DRYING TECHNOLOGIES GMBH
Meisenweg 1 Projekt: LMMadeiras , Formas Fundamento, Maßstab
MC5 72622 Nürtingen Electricidade, Tubulacao Scale
Germany
Zeichn.Nr./Drawing no.: 236122-001-001 pagina 9/12
Tel. +49-7022-66926 none
FAX+49-7022-62121 Gez.:
gez. kd-cad gepr. la 23.10.2023
DRYING TECHNOLOGIES
13 PLC PC Ethernet x
FMWB
WST
HPS
WST
Top VIew: HSP
M F
FMWB
F
F
VA
Feco
1 Fan Motor ( external ) 3 VEM, Weg o smiliar 380 60 22 6 pole, 1100 RPM
4 Heat valve actuator ( external ) 1 ARI Premio 230 60 50W PN16 Heat Valve