1200 SIMBOLOGIA - ILUMINAÇÃO E TOMADAS: SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:

SÍMBOLO DESCRIÇÃO SÍMBOLO

LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C", COM TAMPA. (DIMENSÕES: 150x100mm).
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM
PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO ELETRODUTO LEVE EM AÇO GALVANIZADO ELETROLITICAMENTE, DO TIPO LEVE, INSTALAÇÃO APARENTE NO
ENTREFORRO, Ø3/4" OU CONFORME INDICAÇÃO EM PLANTA.

250
ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA
DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-32W, DA ITAIM ELETRODUTO EM PVC RÍGIDO EMBUTIDO NO TETO, PAREDE OU NO PISO, Ø3/4" OU CONFORME INDICAÇÃO EM
(FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE PLANTA.
DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
BOTOEIRA SIMPLES PARA ACIONAMENTO DE SISTEMA DE ALARME PPNE, FORNECIDO COM TAMPA, A 30cm DO PISO
ACABADO, 10A/250V.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM QUADRO ELÉTRICO PARA DISTRIBUIÇÃO DE CIRCUITOS (QDC).
PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO
MONTANTE ESTRUTURAL DA ELETROCALHA METÁLICA ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE (OU CONFORME INDICAÇÃO) INSTALADA
LAJE SECA (PERFIL C)
A
PERFURADA COM VIROLA DO DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-16W, DA ITAIM A 30cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS. PARÂMETROS GERAIS DE PROJETO:
TIPO "C" COM TAMPA (VER AS (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE
GRAMPO "C" PARA CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE (OU CONFORME INDICAÇÃO) INSTALADA
DIMENSÕES EM PROJETO) DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
SUSTENTAÇÃO DA A 220cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
ELETROCALHA PERFILADO PERFURADO 1 - SISTEMA EM BAIXA TENSÃO TRIFÁSICO 220/127V - 60Hz - Icc MÍNIMO DE 5,0kA.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE - TIPOS C, E, T, TB, L, X e ED, RESPECTIVAMENTE.
TIRANTE ROSCA TOTAL Ø1/4" 38x19mm PARA SUSTENTAÇÃO
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM 2 - A ILUMINÂNCIA MÉDIA DOS AMBIENTES DA EDIFICAÇÃO FORAM DETERMINADAS CONFORME RECOMENDADO
DA ELETROCALHA
ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PELA NBR-5413:1992.
VISTA LATERAL EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO PAREDE, INSTALADA A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-32W, DA ITAIM (FORNECIDA COMPLETA, COM 2 3 - ESQUEMA DE ATERRAMENTO ADOTADO: TN-S.
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À
QUE 10%). PAREDE, INSTALADA A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO. 4 - EM RELAÇÃO AS PRESCRIÇÕES DE PROTEÇÃO CONTRA INCÊNDIO, A EDIFICAÇÃO FOI CLASSIFICADA COMO
BD-3 (TUMULTUADA).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM PAREDE, INSTALADA A 220,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO. 5 - TEMPERATURAS CONSIDERADAS EM PROJETO:
ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. - TEMPERATURA AMBIENTE: 30°C;
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
250

EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO - TEMPERATURA NO SOLO: 20°C.
SOBREPOSTO À PAREDE, INSTALADAS A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU
CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-16W, DA ITAIM (FORNECIDA COMPLETA, COM 2
COMO INDICADO.
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR 6 - LIMITE MÁXIMO DE QUEDA DE TENSÃO ADMITIDA:
50

QUE 10%). UMA TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA METÁLICA - 7% CALCULADO A PARTIR DOS TERMINAIS SECUNDÁRIOS DO TRANSFORMADOR MT/BT ATÉ O PONTO DE
DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE A 15cm ACIMA DA PORTA DOS BANHEIROS PPNE (REF.: UTILIZAÇÃO.
LUMINÁRIA RETANGULAR DE SOBREPOR TIPO ARANDELA PARA 1 LÂMPADA FLUORESCENTE COMPACTA DE 23W. SILENTOQUE DA LEGRAND), POTÊNCIA 50W, PARA O SISTEMA DE SINALIZAÇÃO DE EMERGÊNCIA PPNE.
MONTANTE ESTRUTURAL DA INSTALADA A 220cm DO PISO ACABADO OU CONFORME INDICAÇÃO EM PLANTA. CORPO EM CHAPA DE AÇO 7 - NORMAS APLICÁVEIS:
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
LAJE SECA (PERFIL C) TRATADA COM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM VIDRO PLANO TEMPERADO - ELETRODUTOS DE AÇO GALVANIZADO ELETROLÍTICO: ABNT NBR 13.057;
MONTANTE ESTRUTURAL DA SOBREPOSTO À PAREDE, INSTALADAS A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU
JATEADO. REF.: MOD.: OLIVINO 1xTC-TSE-23W DA ITAIM, FORNECIDA COM 1 LÂMPADA FLUORESCENTE COMPACTA - ELETRODUTOS DE PVC RÍGIDO: ABNT NBR 15.465;
LAJE SECA (PERFIL C) GRAMPO "C" PARA COMO INDICADO.
DE 23W-220V. - CONDUTORES DE COBRE 70°C 750V OU 0,6/1kV, NÃO-PROPAGANTES DE CHAMA, LIVRES DE HALOGÊNIO E
GRAMPO "C" PARA SUSTENTAÇÃO DA
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" INSTALADA DIRETAMENTE NO FORRO DO COM BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS: ABNT NBR 13.248;
ELETROCALHA
SUSTENTAÇÃO DA MÍNIMO 30cm CAIXA DE LIGAÇÃO OU PASSAGEM REDONDA PARA UTILIZAÇÃO EM ÁREA COBERTA APARENTE. REF.: DAILET TETO ACABADO (REF.: PIALPLUS, DA LEGRAND), TENSÃO DE 127V - POTÊNCIA 1 00VA OU CONFORME INDICAÇÃO. - INTERRUPTORES PARA INSTALAÇÕES ELÉTRICAS FIXAS DOMÉSTICAS E ANÁLOGAS: ABNT NBR NM 60.669-1;
ELETROCALHA PERFILADO PERFURADO
TIRANTE ROSCA TOTAL Ø1/4" MÚLTIPLO REDONDA DA DAISA. - PLUGUES E TOMADAS PARA USO DOMÉSTICO E ANÁLOGO ATÉ 20A/250V EM CORRENTE ALTERNADA: ABNT
38x19mm PARA SUSTENTAÇÃO
TIRANTE ROSCA TOTAL Ø1/4" CAIXA DE DERIVAÇÃO PARA ELETRODUTOS COM LUVA ROSQUEADA EM PVC 2". (DIM.: 100X100X50mm) REF.: MEGA NBR 14.136;
DA ELETROCALHA
ABRAÇADEIRA DO TIPO "D" UM INTERRUPTOR BIPOLAR SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À - DISJUNTORES TERMINAIS ATÉ 125A (MINI-DISJUNTORES): ABNT NBR IEC 60.947-2;
ELETROCALHA METÁLICA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. - DISJUNTORES ACIMA DE 125A (CAIXA MOLDADA): ABNT NBR IEC 60.947-2;
ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EMCAIXA METÁLICA DO TIPO - DISJUNTORES PADRÃO CEMIG: NEMA (CONFORME HOMOLOGAÇÃO);
ELETRODUTO DE AÇO
PERFURADA COM VIROLA DO TIPO "C" COM TAMPA (VER AS CONDULETE SIMPLES SOBREPOSTO À PAREDE, INSTALADA A 250,0cm DO PISO ACABADO OU CONFORME - DISPOSITIVOS DIFERENCIAL RESIDUAL (DR): ABNT NBR NM 61.008;
GALVANIZADO
TIPO "C" COM TAMPA (VER AS DIMENSÕES EM PROJETO) DOIS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO INDICAÇÃO (REF.: SILENTOQUE DA LEGRAND ). POTÊNCIA 25VA, PARA ATENDIMENTO AO BLOCO AUTÔNOMO. - DISPOSITIVOS PROTETORES DE SURTOS (DPS): NBR IEC 61.643-1;
DIMENSÕES EM PROJETO) PASSAGEM DOS CABOS DE SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. - DUTOS CORRUGADOS DE POLIETILENO (PE) PARA INFRAESTRUTURAS DE ENERGIA E TELECOMUNICAÇÕES
PASSAGEM DOS CABOS DE ILUMINAÇÃO E TOMADAS FIXAÇÃO DO ELETRODUTO NO TETO TRÊS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
(PEAD): ABNT NBR 15.715;
TELECOMUNICAÇÕES PERCURSO DE CABOS QUE SOBE, QUE PASSA E QUE DESCE EM NÍVEL. INDICAÇÃO EM PLANTA. - CONTATORES MODULARES PARA ILUMINAÇÃO: IEC 61.095;
SUPORTAR A CADA 1,20m SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
- BLOCOS AUTÔNOMOS PARA ILUMINAÇÃO DE EMERGÊNCIA: ABNT NBR 10.898;
SEM ESCALA
CORTE A-A - QUADROS ELÉTRICOS: ABNT NBR IEC 60.439-1.
UM INTERRUPTOR BIPOLAR PARALELO, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO CAIXA DE PASSAGEM 15x15cm (OU CONFORME INDICAÇÃO) COM TAMPA REVERSÍVEL. CONSTRUÍDA EM LIGA DE
À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. ALUMÍNIO SILÍCIO, FUNDIDA EM MOLDE PERMANENTE, DE BOM ACABAMENTO, ALTA RESISTÊNCIA MECÂNICA E À
FIXAÇÃO DE ELETROCALHA PROVA CORROSÃO. TAMPA LISA FIXADA POR PARAFUSOS DE AÇO GALVANIZADO, DOTADAS DE JUNTA DE
FIXAR A CADA 1,20m DOIS INTERRUPTORES BIPOLARES PARALELOS, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO VEDAÇÃO. INSTALADA A 30cm DO PISO ACABADO OU CONFORME INDICAÇÃO. REF.: CP-1515-10 DA WETZEL.
SEM ESCALA SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70°C NOTAS:
750V OU CONFORME INDICAÇÃO EM PLANTA. CLASSE 5 DE ENCORDOAMENTO - NEUTRO, FASE, RETORNO SIMPLES, 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
UM INTERRUPTOR INTERMEDIÁRIO SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES
MONTANTE ESTRUTURAL DA GRAMPO "C" FIXADO NO MONTANTE RETORNO PARALELO E TERRA, RESPECTIVAMENTE - #2,5mm² OU CONFORME INDICAÇÃO EM PLANTA. DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
LAJE SECA (PERFIL C) ESTRUTURAL DA LAJE SECA PARA
PASSAGEM DO CABO DE AÇO QUE 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
SUSTENTA A LUMINÁRIA
3-CONFERIR MEDIDAS NO LOCAL.

4-COTAS EM CENTÍMETROS.
NOTAS GERAIS: 5-OS COMPONENTES E MATERIAIS ESPECIFICADOS NESTE PROJETO SÃO REFERÊNCIAS E PODERÃO SER SUBSTITUÍDOS
POR EQUIVELENTES TÉCNICOS (APRESENTAR PROTÓTIPO PARA APROVAÇÃO POR PARTE DA FISCALIZAÇÃO DAS OBRAS).
UNIDUT METÁLICO 1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO.

ELETRODUTO DE AÇO 2 - CONSIDERAR AS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.


GALVANIZADO - PASSAGEM
ELETRODUTO DE SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
AÇO GALVANIZADO
DOS CIRCUITOS DE FORRO 3 - AS ELEVAÇÕES INDICADAS TÊM COMO REFERÊNCIA O PISO ACABADO. SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
ILUMINAÇÃO E TOMADAS ABRAÇADEIRA DO
ELETRODUTO DE
ELETROCALHA DE TIPO "D" 4 - AS TOMADAS INDICADAS EM 220V DEVERÃO SER VERMELHAS DE FÁBRICA, DIFERENTEMENTE DAS TOMADAS DIRETORIA DE INFRAESTRUTURA FÍSICA
INFRAESTRUTURA P/ AÇO GALVANIZADO
CONVENCIONAIS 127V, E ALÉM DISSO DEVERÃO RECEBER MARCAÇÃO INDELÉVEL COM OS DIZERES "220V", CONFORME
ELÉTRICA OU CURVA 90° DE CONDULETE DO
DETALHE APRESENTADO NESTE PROJETO.
TELECOMUNICAÇÕES AÇO GALVANIZADO TIPO "C" OU "E" PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
GRAMPO "C" FIXADO NO MONTANTE PARA TOMADAS PROJETO DE ACORDO COM RDC-50/2002 E
PLUGUE PADRÃO BRASILEIRO 5 - TODOS OS CABOS TERMINAIS SERÃO DO TIPO CLASSE 5 DE ENCORDOAMENTO E TERÃO ISOLAMENTO EM DUPLA CAMADA
ESTRUTURAL DA LAJE SECA PARA SUPORTE DO ALTAS RESOLUÇÃO 1797/09 DA SES-MG
POLIOLEFÍNICO NÃO HALOGENADO 70°C 750V EXCETO EM LOCAIS SUJEITO À UMIDADE, COMO TUBULAÇÕES ENTERRADAS
ELETRODUTO (VER DETALHE) ELETRODUTO DE
AÇO GALVANIZADO
NO SOLO, QUE DEVERÃO SER DO TIPO 0,6/1kV. É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
CABO DE AÇO GALVANIZADO Ø1/8" PARA CABO TRIPOLAR 0,6/1,0kV 3#1,5mm² EM HEPR
SUPORTE DA LUMINÁRIA 90°C (LIVRE DE HALÓGENOS) PARA A LIGAÇÃO
6 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CIRCUITOS) EM TODAS AS CAIXAS, CAIXAS DE COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
PASSAGEM E/OU CONDULETES.
DA LUMINÁRIA
ABRAÇADEIRA DO
7 - TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA INSTALAÇÃO, DEVEM GARANTIR
TIPO "D"
CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE E PROTEÇÃO MECÂNICA.
FORRO (TETO) LUMINÁRIA EMBUTIDA EM BASE CONECTORA CONDULETE DO 05 REVISÃO CONFORME COMENTÁRIOS 30/09/2013 VIABILE
FORRO TIPO "C" OU "E" 8 - EM TODAS AS DERIVAÇÕES UTILIZAR CAIXA DE PASSAGEM DO TIPO CONDULETE METÁLICO MÚLTIPLO.

2200
REATOR ELETRÔNICO DE ALTO PARA TOMADAS
CONDULETE EQUIPADO COM 9 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, EVITANDO-SE 04 REVISÃO DO DETALHAMENTO 24/09/2013 VIABILE
FATOR DE POTÊNCIA MÉDIAS E
TOMADA PADRÃO BRASILEIRO TOMADAS 2P+T 20A 250V TOMADAS 2P+T 20A 250V TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
INTERRUPTORES
PARA LIGAÇÃO DA LUMINÁRIA CONFORME NBR 14.136/2002 CONFORME NBR 14.136/2002
EM CONDULETE DUPLO EM CONDULETE SIMPLES ELETRODUTO DE 10 - NAS INTERLIGAÇÕES DOS ELETRODUTOS METÁLICOS COM AS ELETROCALHAS, UTILIZAR BUCHA E ARRUELA. 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
AÇO GALVANIZADO
FIXAÇÃO DAS LUMINÁRIAS DE EMBUTIR 11 - SONDAR OS ELETRODUTOS COM CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA CAIXA PARA A PASSAGEM

1100
ABRAÇADEIRA DO 02 EMISSÃO FINAL 08/11/2012 VIABILE
DE CABOS.
SEM ESCALA PAREDE SECA "DRY WALL" TIPO "D"

BUCHA S6 PARA PAREDE SECA


TOMADAS PARA USO GERAL CONDULETE DO
12 - TODOS OS ELETRODUTOS EM PVC DEVERÃO OBEDECER À NBR 15.465. NÃO SERÃO ACEITOS PRODUTOS IDENTIFICADOS
COMO "MANGUEIRAS".
01 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE

SEM ESCALA TIPO "E" PARA

300
"DRY WALL"
TOMADAS BAIXAS 13 - NOS TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO, 00 EMISSÃO INICIAL 27/09/2012 VIABILE
PAREDE DA ELETROCALHA ELETRODUTO PARAFUSO CABEÇA REDONDA ENTREFORRO OU ENTREPISO) DEVERÃO SER UTILIZADOS ELETRODUTOS LEVES DE AÇO GALVANIZADO ELETROLITICAMENTE
ROSCA SOBERBA S6 CONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO. PARA INSTALAÇÕES REVISÃO OBJETO DATA VERIFICAÇÃO
BUCHA ARRUELA EXTERNAS, UTILIZAR ELETRODUTOS DE AÇO GALVANIZADO A FOGO DO TIPO PESADO CONFORME NBR 5.624. GERENCIAMENTO E PROJETO:
ABRAÇADEIRA DO TIPO "D" CORTE ESQUEMÁTICO - INSTALAÇÃO APARENTE 14 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO (INCLUSIVE LUMINÁRIAS) ATRAVÉS DO Av. Augusto de Lima, nº655
APARAFUSÁVEL
ELETRODUTO DE AÇO ELETRODUTO DE AÇO
ELETROCALHA GALVANIZADO SOBRE GALVANIZADO SOBRE A DOS COMPONENTES CABO DE PROTEÇÃO Pe (CABO VERDE DOS CIRCUITOS, TERRA) MAIS PRÓXIMO. conj. 418 - Centro - BH
Telefax: (31) 3324-2702
A PAREDE PAREDE 15 - UM MESMO CABO DE PROTEÇÃO (TERRA) PODERÁ SER COMUM A VÁRIOS CIRCUITOS, DESDE QUE SUA BITOLA SEJA http://www.viabile.com.br
METÁLICA MÍNIMO SEM ESCALA
PERFURADA COM viabile@viabile.com.br
15 cm IDÊNTICA AO CABO FASE DE MAIOR SEÇÃO CONTIDO EM UM CONDUTO/NICHO DE ELETROCALHA.
VIROLA DO TIPO "C" BUCHA E ARRUELA
COM TAMPA 16 - ONDE EXISTIR FORRO E/OU PISO ELEVADO, AS ELETROCALHAS DE PASSAGEM DOS CABOS ELÉTRICOS DEVERÃO SER DESENVOLVIMENTO: DATA:
INSTALADAS SOBRE O FORRO OU ABAIXO DO PISO ELEVADO. ESTAS DEVERÃO SER DE USO EXCLUSIVO PARA OS SISTEMA
ELETRODUTO DE BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
ELÉTRICO E DEVERÃO ESTAR DISTANTES PELO MENOS 30cm DAS ELETROCALHAS QUE CONTENHAM CABOS DE
AÇO GALVANIZADO PROJEÇÃO DO CONDULETE EM
CONDULETE CONDULETE METÁLICO TELECOMUNICAÇÕES. NOME DO ARQUIVO CAD: ESCALA: UNIDADE:
ELETROLITICAMENTE RELAÇÃO À PAREDE
ELETRODUTO DE METÁLICO DUPLO DUPLO PARA TOMADAS INDICADA
AÇO GALVANIZADO (OBSERVAÇÃO: INSTALAR 460-UBSSS-R05-ELE-01-PE-T2T.DWG MILÍMETROS
PARA TOMADAS DE ELÉTRICAS 17 - UTILIZAR O SEGUINTE CÓDIGO DE CORES PARA CABOS:
ELETROLITICAMENTE ABRAÇADEIRA SOBRE O
CABEAMENTO F FASE: PRETO - NEUTRO: AZUL CLARO - TERRA: VERDE - RETORNO: BRANCO - RETORNO PARALELO: CINZA. RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
CONDULETE METÁLICO CONDULETE - DISTÂNCIA DE
ESTRUTURADO
DO TIPO MÚLTIPLO 3cm)
F CAIXA DE SOBREPOR 18 - EM SITUAÇÕES ONDE A VIGA ESTRUTURAL TORNAR INVIÁVEL A PASSAGEM DOS CONDUTOS ELÉTRICOS, A INSTALAÇÃO
(MÍNIMO DE 105mmX105mm) DEVERÁ SER FEITA ABAIXO DA VIGA PARA TRANSPOSIÇÃO DESTES OBSTÁCULOS UTILIZANDO-SE TIRANTES PARA EXTENSÃO
DETALHE TÍPICO DE CONEXÃO DO T COM SIRENE DE DOS SUPORTES (VER DETALHES), PODENDO TAMBÉM UTILIZAR ELETRODUTOS METÁLICOS FLEXÍVEIS (SEALTUBE). BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
FIXAÇÃO DO ELETRODUTO EM PAREDE INSTALAÇÃO DOS ELETRODUTOS DE ELÉTRICA/LÓGICA TOMADA 2P+T -10A (REF.:
PIALPLUS DA LEGRAND),
SINALIZAÇÃO INTERMITENTE
ELETRODUTO NA ELETROCALHA FIXAR NO MÁXIMO A CADA 1,50m DISTÂNCIA MÍNIMA ENTRE CAIXAS - 15cm PARA ALIMENTAÇÃO DO ALARME
E STROBE LIGHT, FONTE
INTERNA DE 220Vca-12Vcc.
19 - TODO E QUALQUER PONTO DE CABEAMENTO ESTRUTURADO DEVERÁ SER ACOMPANHADO DE SEU RESPECTIVO PONTO
ELÉTRICO, CONFORME INSTALAÇÕES DE CABEAMENTO (VER PROJETO ESPECÍFICO). PARA INSTALAÇÕES EMBUTIDAS, Secretaria de Estado de Saúde de Minas Gerais
SEM ESCALA r r PNE
SEM ESCALA SEM ESCALA PAINEL AUDIOVISUAL PARA FORNECIMENTO COMPLETO PREVER DISTÂNCIA MÍNIMA DE 15cm ENTRE AS CAIXAS DE ELÉTRICA E DE CABEAMENTO PARA ATENDER A UM MESMO Cidade Administrativa Presidente Tancredo Neves
SINALIZAÇÃO DE T EQUIPAMENTO. Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
EMERGÊNCIA. REF.: ALARME Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
HB, EATON OU EQUIVALENTE. 20 - TODAS AS LUMINÁRIAS, POR SEGURANÇA, DEVERÃO SER FIXADAS ATRAVÉS DE CABO DE AÇO AOS MONTANTES
ESTRUTURAIS DA LAJE (VER DETALHE).. SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
ELETRODUTOS PVC/AÇO F 21 - OS ALIMENTADORES DO QDC A PARTIR DO PADRÃO DE ENTRADA (INCLUINDO O PADRÃO DE ENTRADA DE ENERGIA
SUPERINTENDENCIA DE GESTÃO
r INTERRUPTOR BIPOLAR SIMPLES, 10A/250V
ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150 ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 13057 r REF.: PIALPLUS DA LEGRAND.
JUNTO À CONCESSIONÁRIA) DEVERÃO SER OBJETO DE PROJETO ESPECÍFICO. DIRETORIA DE GESTÃO DA REDE FÍSICA
DIÂMETRO ESPESSURA NOMINAL DA PAREDE DIÂMETRO ESPESSURA NOMINAL DA PAREDE F PARA ACIONAMENTO DA SINALIZAÇÃO DE DISCIPLINA:
22 - OS CHUVEIROS ELÉTRICOS DEVERÃO TER RESISTÊNCIA DO TIPO BLINDADA OU SER APROPRIADOS PARA INSTALAÇÕES
NOMINAL-DN EXTERNO-DE e NOMINAL-DN EXTERNO-DE e EMERGÊNCIA DOS BANHEIROS DO TIPO
ACESSÍVEIS (PNE)
EM CIRCUITOS PROTEGIDOS ATRAVÉS DE IDR (INTERRUPTOR DIFERENCIAL RESIDUAL) PARA EVITAR DESLIGAMENTOS INSTALAÇÕES ELÉTRICAS
mm POL mm mm mm POL mm mm INDEVIDOS. PROJETO:
25 3/4 25,9 2,3 20 3/4 25,2 1,5
32 1 33,0 2,7 25 1 31,5 1,5 23 - TODOS OS BANHEIROS DO TIPO ACESSÍVEIS (PNE) DEVERÃO POSSUIR SINALIZAÇÃO DE EMERGÊNCIA DE ACORDO COM A UBS MINAS - PROJETO MODELO
40 1.1/4 42,0 2,9 32 1.1/4 40,5 2,0 DETALHE ESQUEMÁTICO DE SINALIZAÇÃO PARA NBR-9050. PARA ESQUEMÁTICO DE FUNCIONAMENTO DO SISTEMA, VER DETALHE ESPECÍFICO NESTE PROJETO.
TIPO T2T - TÉRREA
50 1.1/2 47,4 3,0 40 1.1/2 46,6 2,25 24 - PROJETO ELABORADO DE ACORDO COM AS ESPECIFICAÇÕES DA NBR-5410:2004, SEGUINDO AS NECESSIDADES
60 2 59,0 3,1 50 2 58,4 2,25 BANHEIROS DO TIPO ACESSÍVEIS (PNE) APONTADAS PELO LAYOUT SUGERIDO PELO CLIENTE. QUALQUER ALTERAÇÃO DEVERÁ SER COMUNICADA AO PROJETISTA ENDEREÇO:
75 2.1/2 74,7 3,8 65 2.1/2 74,1 2,85 SEM ESCALA PARA VERIFICAÇÃO.
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
85 3 87,6 4,0 80 3 86,8 2,65
CONTEÚDO: ETAPA: FOLHA:
25 - O MEMORIAL DESCRITIVO E QUANTITATIVO FAZEM PARTES INTEGRANTES DESTE PROJETO, E DEVERÃO SER
110 4 113,1 5,0 100 4 111,6 2,65
abrasip-mg PROJETO EXECUTIVO
CONSULTADOS ANTES DE QUAISQUER ORÇAMENTOS OU INSTALAÇÕES. DETALHES CONSTRUTIVOS, NOTAS
GERAIS E SIMBOLOGIA
01
05
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm)
L1ai L1ah L4al
2x32W 2x32W I.S.
L5cb
L4ak #4,0 L5cc L5cc L5cc
1x23W
2x16W 1x23W 1x23W 1x23W
#4,0
L4al
compressor VER NOTA 5 VER NOTA 5
#4,0 2x16W
L4ak

CUIDADOS #4,0 DEPOSITO


BASICOS CONSULTÓRIO

GINECOLOGIA
L2aj
2x32W ODONTOLÓGICO L2bv
#4,0 2x32W
L2aj L2bv
2x32W
L2am #4,0 L2an #4,0 L2ao L2ap
VER NOTA 5 L1ai L1ah 2x32W 2x32W 2x32W 2x32W #4,0
L2aq
2x32W 2x32W 2x32W
#4,0
L2aj #4,0 L2ao,ap L4bt SALA DE APOIO
2x32W L2am,an #4,0 L2aq
L2aj #4,0
#4,0
AGENTES
L4bt L4bu #4,0 #4,0
#4,0 #4,0 ENDEMIAS
L5cc
#4,0 1x23W
#4,0
L1ai L1ah #4,0
2x32W 2x32WL1ah,ai L2ar
#4,0 #4,0 #4,0 #4,0
L5cb L4bt #4,0 #4,0 2x32W

MULTIPROFISSIONAL
1x23W
L4ar COPA
#4,0

ATENDIMENTO
#4,0 #4,0
#4,0 L4bt CIRC. #4,0
L1ag L3bg
2x32W ATENDIMENTO
L4bs
MULTIPROFISSIONAL L5cd
ESCOVÁRIO #4,0
#4,0
1x23W #4,0
#4,0
#4,0
L1ag
L4as #4,0 DML VER NOTA 5
#4,0 L3bg #4,0
L1ag #4,0 2x32W
2x32W #4,0
L4as
L4bs L2bh,bi #4,0
#4,0 2x32W
L2bi
2x16W L2bh GUARDA
MULTIPROFISSIONAL
2x32W 2x32W
MEDICAMENTOS
ATENDIMENTO
CIRC. #4,0 L3bf #4,0 VESTIÁRIO
L1af FEMININO PNE L5cc
VER NOTA 5
2x32W
SALA DE CURATIVOS L3bf 1x23W
L1af 2x32W #4,0 #4,0
#4,0 #4,0
CIRC. L4bz
2x32W
#4,0 #4,0
L2bj

L1af
SALA LAVAGEM
#4,0
2x32W E DESINF. MATER.
#4,0
L5cb #4,0
L4bs L2bj L2bj L2bj L4at
1x23W 2x32W 2x32W 2x32W
2x16W
L3be #4,0
L3be L3be
COLETA L5cd 2x32W 2x32W #4,0
L4at
2x32W
L1ad,ae #4,0 1x23W #4,0 VESTIÁRIO
#4,0 #4,0
#4,0 #4,0
L3bd L3bd FEMININO
TRIAGEM 2x32W 2x32W L3bd
L1ae L1ad #4,0 #4,0 #4,0
L2bk,bl VER NOTA 5
2x32W 2x32W L4au
#4,0 2x32W
#4,0
L4bs
ESTERIL #4,0 #4,0
#4,0 2x16W L2bk L2bl L4au
2x32W 2x32W ALMOXARIFADO #4,0
L4bs
#4,0 L5cc
L4bs
#4,0 L3bc 1x23W NOTAS:
#4,0
SALA DE GERENTE 2x32W

ÁREA PERMEÁVEL
#4,0 L4bw
L3bc 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
#4,0 L4bw2x32W
L1ac L1ac DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
2x32W 2x32W
L2bm,bn
L3bb L3bb VESTIÁRIO
#4,0 2x32W 2x32W 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
L2bm #4,0
MASC. PNE
SALA DE REUNIÃO 2x32W L2bn 3-CONFERIR MEDIDAS NO LOCAL.
#4,0
2x32W L5cd L3ba,bb escaninhos
E EDUCAÇÃO #4,0 L5ca,cb,cc L2br, L5cd 1x23W
#4,0 L4br RECEPÇÃO #4,0 ACESSO FUNCIONÁRIOS 4-COTAS EM CENTÍMETROS.
2x16W L4av
AGENTES 2x16W 5-OS ELETRODUTOS PARA ALIMENTAÇÃO DAS ARANDELAS EXTERNAS DEVERÃO SER INSTALADOS SOBRE AS JANELAS,
#4,0
#4,0
A 2,70m DO PISO ACABADO.
#4,0
DE SAÚDE #4,0 #4,0
#4,0 L2br L2br #4,0 VER NOTA 5
#4,0 2x32W 2x32W #4,0 L4av
#4,0
L1ac
2x32W
ROUPARIA SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
L1ac
2x32W
RESIDUOS RESIDUOS L5cc
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
#4,0 #4,0
ESPERA L3ba L3ba L3aw 1x23W
DIRETORIA DE INFRAESTRUTURA FÍSICA
#4,0 L1ac
2x32W 2x32W 2x16W
I.S. L3ax
MASC. #4,0 #4,0 #4,0 #4,0
2x16W
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
#4,0 L1bo L1bo L1bp L1bp
L5ca L4ab
2x32W 2x32W 2x32W 2x32W RESOLUÇÃO 1797/09 DA SES-MG
#4,0 #4,0
1x23W #4,0
#4,0 L4bq
L4bq #4,0
#4,0 L3aw L3ax
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
L3ba L3ba
I.S. 2x16W
#4,0
#4,0
2x32W 2x32W L4bu
#4,0
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
FEM. #4,0 L5ca
L2ay,az 1x23W
VER NOTA 5
#4,0 #4,0
L4aa
#4,0 L1bo L1bo L1bp L1bp
2x32W #4,0 2x32W 2x32W 2x32W L2ay L2ay
L1bo,bp
04 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 16/09/2013 VIABILE
2x32W 2x32W
L5ca VACINAÇÃO
L5ca
1x23W
1x23W
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 14/02/2013 VIABILE
L5ca
1x23W ACESSO PRINCIPAL
VARANDA COBERTA L2az L2az L5ca
2x32W 2x32W 1x23W CARGA 02 EMISSÃO FINAL 12/11/2012 VIABILE
DESCARGA
01 ALIMENTAÇÃO DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
VAGA PARA
L5ca
ACESSO VACINAÇÃO 1x23W AMBULÂNCIA
00 EMISSÃO INICIAL 27/09/2012 VIABILE

REVISÃO OBJETO DATA VERIFICAÇÃO

GERENCIAMENTO E PROJETO:

ÁREA PERMEÁVEL
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
ÁREA PERMEÁVEL http://www.viabile.com.br
viabile@viabile.com.br

DESENVOLVIMENTO: DATA:

BRENO ASSIS DE OLIVEIRA SETEMBRO/2013


NOME DO ARQUIVO CAD: ESCALA: UNIDADE:

460-UBSSS-R04-ELE-02-PE-T2T.DWG INDICADA MILÍMETROS


RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
ACESSO
PEDESTRES ACESSO VEÍCULOS
PASSEIO EM CONCRETO ÁSPERO BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS

REBAIXO NA CALÇADA P/ REBAIXO NA CALÇADA P/


ACESSIBILIDADE ACESSO DE VEÍCULOS Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

SUBSECRETARIA DE INOVAÇÃO E LOGISTICA


SUPERINTENDENCIA DE GESTÃO
PLANTA DE ILUMINAÇÃO DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:
ESCALA: ...................................................... 1/75
INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T2T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


PLANTA DE ILUMINAÇÃO DO TÉRREO 02
05
FORMATO INTERNACIONAL A1 (841 x 594mm)
LEGENDA PARA PERCURSO DE CABOS (QDC-QDC-T2/T):

T52 T54 T1 T2 T5 T6 T10 T11 T12 T13 T16 T31 T32 T38 T49 T53 T55
A
#4,0
T52 T54 T1 T2 T5 T6 T8 T10 T11 T12 T13 T16 T31 T32 T38 T49 T53 T55
B
#4,0
T52 T54 T1 T2 T5 T6 T7 T8 T10 T11 T12 T13 T16 T31 T32 T38 T49 T53 T55
C
#4,0
T52 T54 T1 T2 T5 T6 T7 T8 T10 T11 T12 T13 T16 T31 T32 T33 T34 T38 T49 T53 T55
T16 D
#4,0

compressor
T29-1kVA-220V T52 T54 T1 T2 T5 T6 T7 T8 T10 T11 T12 T13 T16 T31 T32 T33 T34 T38 T41 T42 T49 T50 T51 T53 T55
T16 T16
T36-1,11kW-220V
E
#4,0 T16 #4,0
T39-1,11kW-220V #4,0
I.S. T44-1,11kW-220V
T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T16 T31 T32 T33 T34 T36 T37 T38 T41 T42 T49 T50 T51 T53 T55
T16 T43-1,11kW-220V F
#4,0
DEPOSITO
T25 T45-1,11kW-220V T27 T27 T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T25 T29 T31 T32 T33 T34 T36 T37 T38 T41 T42 T49 T50 T51 T53 T55
T25 G
T25 T25 T27
T27 T16 #4,0
T14T14 T27 SALA DE
T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T25
GINECOLOGIA #4,0 T25 #4,0 T25 T45
T27 #4,0
#4,0 #4,0 APOIO H
CUIDADOS T25 T27
T16 #4,0
BASICOS #4,0 AGENTES
T43 T16 T29 T31 T32 T33 T34 T36 T37 T38 T39 T41 T42 T44 T49 T50 T51 T53 T55
T36 T16 T29 T14 T25
T25
CONSULTÓRIO T27 ENDEMIAS
#4,0 T16 T27 #4,0
#4,0 #4,0
#4,0 #4,0 #4,0 #4,0 ODONTOLÓGICO
#4,0 T20 T20 T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T25 T26
T14-200VA
T39 T44
T26-2x600VA T26 T28-2x600VA I
T37 T16 T7 T9 #4,0
T14 T14 T25 T16 T27 T27 T28 #4,0 #4,0
T14-200VA #4,0 T16 T8 T20-600VA
#4,0 #4,0 T29 T31 T32 T33 T34 T35 T36 T37 T38 T39 T41 T42 T44 T49 T50 T51 T53 T55
#4,0 T54 #4,0 #4,0 #4,0 T54 T20 T20
T9-2X200VA T16 #4,0 #4,0 T27
T36 T37 T20 #4,0
T14 T14 #4,0 T21-1,8kVA T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T25 T26
#4,0
T37-1,11kW-220V T9
F T14 G H I J K L T20 T21
J
T16
T9 #4,0 #4,0
#4,0 T52 T20 #4,0
#4,0
T41 T42 T50 T51
E T8 T35 #4,0 M COPA T29 T31 T32 T33 T34 T35 T36 T37 T38 T39 T41 T42 T44 T45 T49 T50 T51 T53 T55
T7 T9
T7 #4,0 T22 T23
T7 #4,0 #4,0 D
#4,0 #4,0 N #4,0
T41-1,11kW-220V T54 T20 #6,0
T20
#4,0
T52 T16
T52 CIRC. T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T25 T26 T27
T42 T50 T51 ATENDIMENTO D T54 T8
#4,0
K
#4,0
MULTIPROFISSIONAL T20
T7 ESCOVÁRIO
T42-1,11kW-220V
#4,0
T33-1,11kW-220V D ATENDIMENTO T22 T23
T29 T31 T32 T33 T34 T35 T36 T37 T38 T39 T41 T42 T44 T45 T49 T50 T51 T53 T55

T34-1,11kW-220V #4,0 T20


T33 T34 MULTIPROFISSIONAL T52 T3 T4 T15 T16 T17 T18 T19 T20 T24 T30 T40 T46 T47 T48 T22 T23 DML #4,0
T50 T51 T20 #6,0
T8 #4,0 T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T20 T25 T26 T27 T28
#4,0 #4,0 #6,0
L
T50-1,11kW-220V
#4,0 CIRC. #4,0 T8 T52 T3 T4 T15 T16 T17 T18 T19 T24 T30 T40 T46 T47 T48 #4,0
C T8 T15-200VA #4,0
T29 T31 T32 T33 T34 T35 T36 T37 T38 T39 T41 T42 T43 T44 T45 T49 T50 T51 T53 T55
T51 T35-1,11kW-220V T15-200VA
#4,0 T22
T6 T7 T15 #4,0
B T8 T15 T8 GUARDA
T15
#4,0
T17 #6,0 T52 T54 T1 T2 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T16 T20 T21 T25 T26 T27
T51-1,11kW-220V #4,0 T6 T15 T15 T8-2X200VA
T6-2X200VA
#4,0 T8 T15 MEDICAMENTOS #4,0 M
T40 T46 T47 #4,0
T7-2X200VA #4,0 T22-6500W #4,0
#4,0
T16 #4,0 T17 T28 T29 T31 T32 T33 T34 T35 T36 T37 T38 T39 T41 T42 T43 T44 T45 T49 T50 T51 T53 T55
ATENDIMENTO T15
A T15 T16 SALA DE CURATIVOS T40-1,11kW-220V
T52 T3 T4 T16 T17 T18 T19 T24 T30 T48
#4,0
MULTIPROFISSIONAL T17 #4,0
#4,0
T31 T38
T17
SALA LAVAGEM T52 T54 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17 T18 T19 T20 T21 T24 T25 T26 T27
T5 T6 T46 T47 T17 N
T6 T6 #4,0 E DESINF. MATER. VESTIÁRIO #4,0
#4,0 #4,0 #4,0
T5 T17 T17 T17 T28 T29 T30 T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 T43 T44 T45 T46 T47 T48 T49 T50 T51 T53 T55
#4,0 T5 T6 T17 T17 MASCULINO
T54 T52 T1 T2 T5 T6 T10 T11 T12 T16 T13 T32 T49 T53 T55 T38-1,11kW-220V
#4,0 #4,0 T17 #4,0 #4,0
#4,0 T5-200VA #4,0
T31-1,11kW-220V T17 T19
T52 T3 T4 T16 T17 T18 T19 T24 T30 T48
T5-200VA #4,0
COLETA T5 T47-1,11kW-220V T17 T17
T54 T52 T1 T2 T5 T10 T11 T12 T16 T13 T32 T49 T53 T55 #4,0
#4,0
T5 T19
#4,0 #4,0
T32 T46-1,11kW-220V T19 T18 T19 T18 T19 T52 T3 T4 T16 T17 T19 T24 T30 T48
T52 T5 T5
T12 #4,0 T19 #4,0 #4,0
T32-1,11kW-220V #4,0 T19 T16 T17
T13 #4,0 T5 #4,0 TRIAGEM T18-1kVA NOTAS:
#4,0
T52 #4,0 ESTERIL. #4,0 T23
T11 T11-600VA T12-600VA VESTIÁRIO

CIRC.
#4,0 T19
T54 T52 T1 T2 T10 T11T12 T16 T13 T49 T53 T55 T17 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
T11 T13-1,8kVA #6,0 FEMININO
T17 DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
#4,0 T16 #4,0
T11 T12 T13 T5-200VA T52 T3 T4 T17 T19 T24 T30 T48
T54 T52 T1 T2 T10 T11 T16 T49 T53 T55 T5-200VA ALMOXARIFADO 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
#4,0 #4,0
T10 T10 #4,0
T49-1,11kW-220V T19
3-CONFERIR MEDIDAS NO LOCAL.
T49 SALA DE GERENTE T19 T17
T10 T10 #4,0 #4,0
#4,0 4-COTAS EM CENTÍMETROS.
T23-6500W
ÁREA PERMEÁVEL

T2 T2 T24-200VA
T52 T1 T2 T10 T16
T24-200VA #4,0 5-OS ELETRODUTOS PARA ALIMENTAÇÃO DAS ARANDELAS EXTERNAS DEVERÃO SER INSTALADOS SOBRE AS JANELAS,
#4,0
#4,0 T2 #4,0
A 2,70m DO PISO ACABADO.
T10 T54 T52 T1 T10 T11 T16 T53 T55 T2-200VA
T10 T2-200VA T24 T24
T52 T4 T3 T17 T24 T30 T48
#4,0 T55-1kVA
#4,0 T54
SALA DE REUNIÃO #4,0 T24 #4,0
T54 T53 T55 T53-1kVA #4,0
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
E EDUCAÇÃO T11 T16 AGENTES ACESSO FUNCIONÁRIOS
#4,0
T52 T1 T10 T11 T16 #4,0 SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
RECEPÇÃO DE SAÚDE T52 T4 T3 T17 T24 T30 T48
T10 T1 #4,0 DIRETORIA DE INFRAESTRUTURA FÍSICA
#4,0
#4,0 #4,0
T1-4X200VA T48-1,11kW-220V T48 ROUPARIA
T10
T52
T52 T10

T10
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
#4,0 T52 T10 #4,0 T54
#4,0 PROJETO DE ACORDO COM RDC-50/2002 E
RESIDUOS RESIDUOS RESOLUÇÃO 1797/09 DA SES-MG
T10 #4,0 T54 T24-2X200VA T24
T16 T52 T52 T10 T10 T10
T11 T16
#4,0 T52 T4 T3 T17 T24 T30 É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
T16a' #4,0 #4,0 #4,0 #4,0

#4,0 T16a'
#4,0
T11 T16 T52 T10
#4,0 COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
T16a' T17
T16
I.S. #4,0 #4,0
T24
#4,0 T17 T17
T16 #4,0
T52 T4 T3 T24 T30
MASC. T11 T16
T52 T10 T10
ESPERA
T16 #4,0
#4,0 #4,0 #4,0 05 REVISÃO CONFORME COMENTÁRIOS 30/09/2013 VIABILE
T10T10 T24 T52 T3 T4
#4,0 T52 T3 T4 T30
T16b' #4,0 T24 T4
T16b' T52 #4,0
T11 T16 #4,0
#4,0 T16b' T4-600VA #4,0 T3-600VA 04 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 16/09/2013 VIABILE
T16 #4,0
I.S.
COBERTURA

T3 T4
PROJEÇÃO

FEM. T16 #4,0 T11 T52 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 14/02/2013 VIABILE
T11 T10
VACINAÇÃO #4,0
T30
T3 T3 T52 T3 T52 T3 T4
#4,0
02 EMISSÃO FINAL 12/11/2012 VIABILE
ACESSO PRINCIPAL #4,0 #4,0 T4 #4,0
T52
T52 T3 T4
#4,0
VARANDA COBERTA 01 ALIMENTAÇÃO DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
T4-200VA #4,0 VAGA PARA CARGA
T4-200VA
T52 AMBULÂNCIA DESCARGA
T30-1,11kW-220V
00 EMISSÃO INICIAL 27/09/2012 VIABILE

ACESSO VACINAÇÃO REVISÃO OBJETO DATA VERIFICAÇÃO

GERENCIAMENTO E PROJETO:

PROJEÇÃO COBERTURA
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
ÁREA PERMEÁVEL http://www.viabile.com.br
viabile@viabile.com.br

ÁREA PERMEÁVEL
DESENVOLVIMENTO: DATA:

BRENO ASSIS DE OLIVEIRA SETEMBRO/2013


NOME DO ARQUIVO CAD: ESCALA: UNIDADE:

460-UBSSS-R05-ELE-03-PE-T2T.DWG INDICADA MILÍMETROS


RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
CALÇADA

ACESSO PEDESTRES
BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
ACESSO VEÍCULOS

PASSEIO EM CONCRETO ÁSPERO


Secretaria de Estado de Saúde de Minas Gerais
REBAIXO NA CALÇADA P/ ACESSIBILIDADE
Cidade Administrativa Presidente Tancredo Neves
REBAIXO NA CALÇADA P/ ACESSO DE VEÍCULOS
RUA
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

PLANTA DE TOMADAS DO TÉRREO SUBSECRETARIA DE INOVAÇÃO E LOGISTICA


ESCALA: ....................................................................................1/75 SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:

INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T2T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


PLANTA DE TOMADAS DO TÉRREO 03
05
FORMATO INTERNACIONAL A1 (841 x 594mm)
SIMBOLOGIA P/ QUADRO:
DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES.
ADVERTÊNCIA
CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E CLASSE II,
VER PROJETO ESPECÍFICO SEGUNDO NBR5410: 1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A
DE ALIMENTADORES/IMPLANTAÇÃO - OBEDECER A NBR IEC 61.643-1; Up (NÍVEL DE PROTEÇÃO):
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO.
Pe R S T N INFERIOR A 1,5kV;
- Uc (MÁXIMA TENSÃO DE OPERAÇÃO CONTÍNUA): 175V; DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE
- Iimp (CORRENTE DE IMPULSO): SUPERIOR A 12,5kA (10/350us); SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM)
- In (CORRENTE NOMINAL DE DESCARGA): SUPERIOR A 20kA SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE
(8/20us) PARA REDES TRIFÁSICAS;
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS
UTILIZAR NAS FASES COMO PROTEÇÃO BACKUP, FUSÍVEIS DE MAIOR SEÇÃO (BITOLA).
MODULARES NH-63A gG/gL.
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃO
CONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS
INTERRUPTOR DIFERENCIAL RESIDUAL (IDR). CARACTERÍSTICAS SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE,
TERRA NEUTRO
TÉCNICAS: SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO
- TIPO AC;
PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE
- CORRENTE NOMINAL (In): CONFORME INDICAÇÃO;
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR; SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A
FREQUÊNCIA: 60Hz. DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO.
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES),
CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS,
#10,0
SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA

FUSÍVEL MODULAR DISJUNTOR


Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR,
RESPECTIVAMENTE).
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410
63A GERAL
200A A SER FIXADA NO INTERIOR DO QUADRO ELÉTRICO
DISJUNTOR GERAL:
#10,0 #10,0 MÍNIMO DE 10kA - TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO E
DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V.
#10,0 #10,0

DPS CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO


#6,0
175V HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE I/II CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA).
12,5kA - 10/350us
20kA - 8/20us CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
63A (C) 40A (C)
CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO).
#16,0 #10,0
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE).

TABELA 1: ESPAÇO RESERVA


63A (C) 63A (C)
QUANTIDADE DE CIRCUITOS ESPAÇO MÍNIMO DESTINADO A
#16,0 #16,0 EFETIVAMENTE DISPONÍVEL RESERVA (EM NÚMEROS DE
N CIRCUITOS)
ATÉ 6 2
7 A 12 3
13 A 30 4
N>30 0,15xN
63A (C)

#16,0 NOTAS GERAIS DOS QUADROS:

01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2


(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE
CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS FORAM
BARRA 1 - IN MÍNIMO: 200A - TRIFÁSICO - Icc MÍNIMO: 10kA DIMENSIONADOS PARA Icc >= 10kA/220V E DEVERÃO SER DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA .

02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE


ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NO QUADRO
L1 L2 L3 RES. RES. RES. T10 T2 T3 T1 T5 T6 T4 T8 T9 T7 T14 T15 T50 T26 DE CARGAS.
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0
03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO
NOTAS:
NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
04 - O QUADRO SERÁ METÁLICO, DE SOBREPOR (PREVER ESTRUTURA NO STEEL FRAME PARA DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A
SUSTENTAÇÃO), COM NO MÍNIMO IP-30 (EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
R POSSUIR GRAU DE PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO 3-CONFERIR MEDIDAS NO LOCAL.
COM CHAVE, NÃO ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL
S 4-COTAS EM CENTÍMETROS.
ACESSO E NÃO SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO
T NBR IEC 60.439-1 EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
05 - O QUADRO DEVERÁ POSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE
CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO, DIRETORIA DE INFRAESTRUTURA FÍSICA
T32 T30 T29 T35 T36 T31 T41 T39 T33 T24 T25 T42 T34
SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO,
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 CONFORME LAYOUT SUGESTIVO PRESENTE NO DIAGRAMA MULTIFILAR. PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
RESOLUÇÃO 1797/09 DA SES-MG
06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS,
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
SEGUNDO ORIENTAÇÕES DA NBR-5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A
SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE
R
FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO
QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME 04 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 16/09/2013 VIABILE
S
DETALHADO NO DIAGRAMA MULTIFILAR.
T
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A 07- NO QUADRO DEVER Á SER FIXADO, ATRAVÉS DE DISPOSITIVO PRÓPRIO, O SEU DIAGRAMA , CONTENDO 03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 14/02/2013 VIABILE
TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO .
T44 T45 T37 T46 T47 T38 T48 T49 T40 T27 T28 T52 T43
02 EMISSÃO FINAL 12/11/2012 VIABILE
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADRO ELÉTRICO DEVERÃO SER COM CONECTOR TIPO
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #2,5 #4,0
BOX RETO, COM BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS
ELETROCALHAS DEVERÃO SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE 01 ALIMENTAÇÃO DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
PROJETO.
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA 00 EMISSÃO INICIAL 27/09/2012 VIABILE
PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO AOS
R
BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA REVISÃO OBJETO DATA VERIFICAÇÃO

S ADEQUADA. GERENCIAMENTO E PROJETO:

T 10- O QUADRO DEVER Á ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE Av. Augusto de Lima, nº655
BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A conj. 418 - Centro - BH
CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO.
Telefax: (31) 3324-2702
T51 RES. T53 T54 T55 RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. RES. 11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA http://www.viabile.com.br
viabile@viabile.com.br
#4,0 #4,0 #2,5 #4,0 PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO .

12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM DESENVOLVIMENTO: DATA:
ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO
BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO
16A

16A

16A

16A

A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO "CIRCUITO" DO QUADRO DE CARGAS NOME DO ARQUIVO CAD: ESCALA: UNIDADE:

R CORRESPONDENTE. INDICADA
460-UBSSS-R04-ELE-04-PE-T2T.DWG MILÍMETROS
S 13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
EM PVC 70°C 750V.
T
BARRA 5 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A

BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
T11 T12 T13 T16 T17 T20 T22 T23 T18 T19 T21 L5 L4 RES. RES. RES.
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #6,0 #6,0 #4,0 #4,0 #4,0 #2,5 #4,0 #6,0
INTERRUPTOR Secretaria de Estado de Saúde de Minas Gerais
TETRAPOLAR Cidade Administrativa Presidente Tancredo Neves
DR3-In 40A Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
NEUTRO DR

SENS. 30mA Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
16A

16A

16A

16A

16A

16A

32A

32A

16A

16A

16A

16A

16A

TIPO AC
R #10,0
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
S SUPERINTENDENCIA DE GESTÃO
T DIRETORIA DE GESTÃO DA REDE FÍSICA
BARRA 6 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A
DISCIPLINA:

INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T2T - TÉRREA
QDC-T2/T - DIAGRAMA MULTIFILAR (120 POLOS) ENDEREÇO:

DETALHE SUGESTIVO DO QUADRO VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


QUADRO METÁLICO DE SOBREPOR CONTEÚDO: ETAPA: FOLHA:

abrasip-mg DIAGRAMA MULTIFILAR PROJETO EXECUTIVO


04
05
FORMATO INTERNACIONAL A1 (841 x 594mm)
QDC - T2/T – RELAÇÃO DE CARGAS E MEMÓRIA DE CÁLCULO MEMÓRIA DE CÁLCULO
QUEDA DE TENSÃO
QUEDA DE
BLOCO AR PROTEÇÃO COMPRIMENTO
ILUMINAÇÃO SINALIZAÇÃO TOMADAS CHUVEIROS COMPRESSOR CORRENTE TENSÃO EFETIVA
AUTONOMO CONDICIONADO POTÊNCIA TOTAL TENSÃO EQUILÍBRIO CONDUTOR MÁXIMO DO
CIRCUITO DESCRIÇÃO (W) (W) (W) (W) (W) F.P. FASES NOMINAL
(W) (W) (mm²) CIRCUITO
In LIMITE:
CURVA
16 23 32 25 50 85 170 510 850 1530 6500 1110 850 (kW) (kVA) (V) R S T (A) (A) (m) 3,00%

ILUMINAÇÃO SALA DE REUNIÃO E EDUCAÇÃO, ESPERA, COLETA,


L1 ATENDIMENTO MULTIPROFISSIONAL 1, ATENDIMENTO - - 48 - - - - - - - - - - 0,95 1,54 1,62 220 RS 0,81 0,81 0,00 7,35 16 C 4,0 44 1,26%
MULTIPROFISSIONAL 2, CUIDADOS BASICOS

ILUMINAÇÃO GINECOLOGIA,CONSULTORIO ODONTOLOGICO,


DEPOSITO, ATENDIMENTO MULTIPROFISSIONAL 3, SALA DE
L2 4 - 46 - - - - - - - - - - 0,95 1,54 1,62 220 TR 0,81 0,00 0,81 7,35 16 C 4,0 27 0,78%
CURATIVOS,TRIAGEM,SALA DE GERENTE, VACINAÇÃO, SALA DE
APOIO AGENTES ENDEMIAS
ILUMINAÇÃO AGENTES DE SAUDE, ALMOXARIFADO,
L3 ESTERILIZACAO, SALA LAVAGEM E DESINFECÇÃO DE MATERIAS, 4 - 26 - - - - - - - - - - 0,95 0,90 0,94 220 ST 0,00 0,47 0,47 4,29 16 C 4,0 25 0,42%
GUARDA MEDICAMENTOS, ESCOVÁRIO,RESIDUOS 1, RESIDUOS 2
ILUMINAÇÃO CIRCULAÇÃO, COPA, DML, BANHEIROS,
L4 38 - 10 - - - - - - - - - - 0,95 0,93 0,98 220 RS 0,49 0,49 0,00 4,44 16 C 4,0 30 0,52%
COMPRESSOR
L5 ILUMINAÇÃO AREAS EXTERNAS. - 20 - - - - - - - - - - - 0,95 0,46 0,48 220 ST 0,00 0,24 0,24 2,20 16 C 2,5 56 0,77%

T1 TOMADAS RECEPÇÃO - - - - - - 4 - - - - - - 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 16 C 4,0 37 1,58%

T2 TOMADAS SALA GERENTE - - - - - 1 2 - - - - - - 0,85 0,43 0,50 127 S 0,00 0,50 0,00 3,94 16 C 4,0 34 0,91%

T3 TOMADAS VACINAÇÃO - - - - - 1 - 1 - - - - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 28 1,05%

T4 TOMADAS VACINAÇÃO - - - - - - 2 1 - - - - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 28 1,49%

T5 TOMADAS TRIAGEM/ COLETA - - - - - 3 4 - - - - - - 0,85 0,94 1,10 127 S 0,00 1,10 0,00 8,66 16 C 4,0 31 1,82%

T6 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 1 - - - - - 3 2 - - - - - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 31 1,16%

T7 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 2 - - - - - 3 2 - - - - - - 0,85 0,60 0,70 127 R 0,70 0,00 0,00 5,51 16 C 4,0 28 1,05%

T8 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 3 - - - - - 3 2 - - - - - - 0,85 0,60 0,70 127 S 0,00 0,70 0,00 5,51 16 C 4,0 28 1,05%

T9 TOMADAS CUIDADOS BÁSICOS - - - - - 4 2 - - - - - - 0,85 0,68 0,80 127 T 0,00 0,00 0,80 6,30 16 C 4,0 29 1,24%

T10 TOMADAS SALA DE REUNIÃO E EDUCAÇÃO/ SALA ESPERA - - - - - 9 - - - - - - - 0,85 0,77 0,90 127 R 0,90 0,00 0,00 7,09 16 C 4,0 36 1,73%

T11 TOMADAS SALA DE REUNIÃO E EDUCAÇÃO/ BEBEDOUROS - - - - - 4 - 1 - - - - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 34 1,81%

T12 TOMADA SALA DE REUNIÃO E EDUCAÇÃO – GELADEIRA - - - - - - - 1 - - - - - 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 16 C 4,0 34 1,09%

T13 TOMADA SALA DE REUNIÃO E EDUCAÇÃO – MICRO-ONDAS - - - - - - - - - 1 - - - 0,85 1,53 1,80 127 T 0,00 0,00 1,80 14,17 16 C 4,0 30 2,88%

T14 TOMADAS GINECOLOGIA - - - - - 4 2 - - - - - - 0,85 0,68 0,80 127 S 0,00 0,80 0,00 6,30 16 C 4,0 21 0,90%

T15 TOMADAS SALA DE CURATIVOS/ GUARDA MEDICAMENTOS - - - - - 4 2 - - - - - - 0,85 0,68 0,80 127 T 0,00 0,00 0,80 6,30 16 C 4,0 27 1,15% NOTAS:
TOMADAS I.S./ SALA DE APOIO AGENTES ENDEMIAS/ CIRCULAÇÃO/
T16 - - - - 2 9 - - - - - - - 0,85 0,87 1,02 127 R 1,02 0,00 0,00 8,01 16 C 4,0 34 1,84% 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
DEPOSITO/ ESCOVÁRIO
TOMADAS LAVAGEM E DESINFECÇÃO DE MATERIAIS/ VESTIÁRIO
T17 MASC./ VESTIÁRIO FEM./ RESÍDUOS/ VESTIÁRIO FEMININO PNE/ - - - - - 12 - - - - - - - 0,85 1,02 1,20 127 S 0,00 1,20 0,00 9,45 16 C 4,0 22 1,41% 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
VESTIÁRIO MASC.PNE
3-CONFERIR MEDIDAS NO LOCAL.
T18 TOMADA ESTERELIZAÇÃO – AUTOCLAVE - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 15 0,80%
4-COTAS EM CENTÍMETROS.
T19 TOMADAS ALMOXARIFADO/ ESTERILIZAÇÃO - - - - - 6 - - - - - - - 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 16 C 4,0 18 0,58%

T20 TOMADAS COPA/ DML/ BEBEDOURO - - - - - 6 - 1 - - - - - 0,85 1,02 1,20 127 T 0,00 0,00 1,20 9,45 16 C 4,0 11 0,70% SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
T21 TOMADA COPA – MICRO-ONDAS - - - - - - - - - 1 - - - 0,85 1,53 1,80 127 R 1,80 0,00 0,00 14,17 16 C 4,0 11 1,06% SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
T22 CHUVEIRO VESTIÁRIO MASCULINO – 220V - - - - - - - - - - 1 - - 1,00 6,50 6,50 220 RS 3,25 3,25 0,00 29,55 32 C 6,0 13 1,00% DIRETORIA DE INFRAESTRUTURA FÍSICA

T23 CHUVEIRO VESTIÁRIO FEMININO – 220V - - - - - - - - - - 1 - - 1,00 6,50 6,50 220 TR 3,25 0,00 3,25 29,55 32 C 6,0 19 1,46% PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
T24 TOMADAS AGENTES DE SAÚDE - - - - - 3 4 - - - - - - 0,85 0,94 1,10 127 R 1,10 0,00 0,00 8,66 16 C 4,0 25 1,47% RESOLUÇÃO 1797/09 DA SES-MG
T25 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - 6 - - - - - - - 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 16 C 4,0 21 0,67% É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
T26 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - - - 2 - - - - - 0,85 1,02 1,20 127 T 0,00 0,00 1,20 9,45 16 C 4,0 15 0,96% COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
T27 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - 6 - - - - - - - 0,85 0,51 0,60 127 R 0,60 0,00 0,00 4,72 16 C 4,0 13 0,42%

T28 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - - - 2 - - - - - 0,85 1,02 1,20 127 S 0,00 1,20 0,00 9,45 16 C 4,0 8 0,51%

T29 PONTO DE FORÇA COMPRESSOR - - - - - - - - - - - - 1 0,85 0,85 1,00 220 ST 0,00 0,50 0,50 4,55 16 C 4,0 23 0,41% 04 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 17/09/2013 VIABILE

T30 PONTO DE FORÇA AR-CONDICIONADO VACINAÇÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 25 0,58%
03 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 14/02/2013 VIABILE
T31 PONTO DE FORÇA AR-CONDICIONADO TRIAGEM - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 32 0,74%

T32 PONTO DE FORÇA AR-CONDICIONADO COLETA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 32 0,74% 02 EMISSÃO FINAL 12/11/2012 VIABILE

PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO


T33 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 27 0,63%
MULTIPROFISSIONAL 1 01 ALIMENTAÇÃO DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 26/10/2012 VIABILE
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO
T34 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 27 0,63%
MULTIPROFISSIONAL 2
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO 00 EMISSÃO INICIAL 27/09/2012 VIABILE
T35 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 18 0,42%
MULTIPROFISSIONAL 3
REVISÃO OBJETO DATA VERIFICAÇÃO
T36 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 1 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 28 0,65%
GERENCIAMENTO E PROJETO:
T37 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 2 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 24 0,56%
Av. Augusto de Lima, nº655
T38 PONTO DE FORÇA AR-CONDICIONADO SALA DE CURATIVOS - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 32 0,74% conj. 418 - Centro - BH
Telefax: (31) 3324-2702
T39 PONTO DE FORÇA AR-CONDICIONADO GINECOLOGIA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 20 0,46% http://www.viabile.com.br
viabile@viabile.com.br
T40 PONTO DE FORÇA AR-CONDICIONADO GUARDA MEDICAMENTOS - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 15 0,35%
PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO E DESENVOLVIMENTO: DATA:
T41 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 30 0,70%
EDUCAÇÃO BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
T42 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO E - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 30 0,70%
EDUCAÇÃO NOME DO ARQUIVO CAD: ESCALA: UNIDADE:
PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO INDICADA
T43
ODONTOLÓGICO 2
- - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 20 0,46% 460-UBSSS-R04-ELE-05-PE-T2T.DWG MILÍMETROS
PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
T44 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 10 0,23%
ODONTOLÓGICO 1
PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO
T45 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 12 0,28%
ODONTOLÓGICO 1
T46 PONTO DE FORÇA AR-CONDICIONADO ESTERILIZAÇÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 17 0,39% BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS

PONTO DE FORÇA AR-CONDICIONADO LAVAGEM E DESINFECÇÃO


T47 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 17 0,39%
DE MATERIAIS Secretaria de Estado de Saúde de Minas Gerais
T48 PONTO DE FORÇA AR-CONDICIONADO AGENTES DE SAÚDE - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 23 0,53% Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
T49 PONTO DE FORÇA AR-CONDICIONADO SALA DO GERENTE - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 36 0,84% Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

T50 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 30 0,70% SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
T51 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 30 0,70% SUPERINTENDENCIA DE GESTÃO
T52 BLOCO AUTONOMO - - - 7 - - - - - - - - - 0,85 0,18 0,21 127 T 0,00 0,00 0,21 1,62 16 C 2,5 50 0,88%
DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:
T53 TOMADA RACK - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 37 1,97%
INSTALAÇÕES ELÉTRICAS
T54 TOMADAS CFTV - - - 5 - - - - - - - - - 0,85 0,13 0,15 127 S 0,00 0,15 0,00 1,16 16 C 2,5 50 0,63% PROJETO:

T55 TOMADA RACK SONORIZAÇÃO - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 37 1,97%
UBS MINAS - PROJETO MODELO
TOTAL 46,00 20,00 130,00 12,00 2,00 87,00 28,00 9,00 3,00 2,00 2,00 22,00 1,00 0,88 66,38 75,14 220 RST 29,32 23,00 22,82 197,42 200 - - - - TIPO T2T - TÉRREA