Monitor de Temperaturas

TM1 / TM2

Sumário
1 ASSISTÊNCIA TÉCNICA ............................................................................................................................ 3
2 HISTÓRICO DE REVISÕES ........................................................................................................................ 3
3 PROTOCOLOS DE COMUNICAÇÃO ....................................................................................................... 3.4

3.1 PROTOCOLO MODBUS RTU - INFORMAÇÕES GERAIS..................................................................................... 3.4

3.1.1 Mapa de Registradores Modbus .................................................................................................. 3.4

3.2 PROTOCOLO DNP 3.0 - INFORMAÇÕES GERAIS ......................................................................................... 3.17

3.2.1 Objetos Suportados no DNP 3.0 ................................................................................................. 3.22

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 2


Monitor de Temperaturas
TM1 / TM2

1 Assistência Técnica
Para obter assistência técnica para o TM ou qualquer outro produto Treetech, entre em contato
através do endereço abaixo:

Treetech Sistemas Digitais Ltda. – Assistência Técnica


Rua José Alvim, 100 – Salas 03 e 04 – Centro
Atibaia – São Paulo – Brasil
CEP: 12.940-800
CNPJ: 74.211.970/0002-53
IE: 190.159.742.110
TEL: +55 (11) 2410-1190 x201
FAX: +55 (11) 2410-1190 x702
Email: suporte.tecnico@treetech.com.br
Site: http://www.treetech.com.br

2 Histórico de Revisões
Revisão Data Descrição Feito por
1.00 08/11/2012 Emissão Inicial Heber Pedrosa
1.01 07/01/2013 Correção de escrita Heber Pedrosa
Adição do Object 50 (Device Profile do DNP) e atualização dos João Victor
2.00 23/07/2015
representantes Miranda

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 3


Monitor de Temperaturas
TM1 / TM2

3 Protocolos de Comunicação
As informações deste apêndice permitem que todas as leituras, seleções e comandos do TM sejam
efetuadospela porta de comunicação serial RS-485. A utilização da porta de comunicação serial é opcional.

3.1 Protocolo Modbus RTU - Informações gerais


Protocolo: Modbus
Modo: RTU (binário)
Taxa de transmissão: 4.800, 9.600, 19.200 ou 38.400, 57.600 ou 115.200bps
Bits de dados: 8
Bits de parada: 1 ou 2, automático
Paridade: Nenhuma
Tipo de variável de memória: Holding Registers (4XXXXX)
03 (Leitura, em blocos ou individualmente)

Comandos implementados: 06 (Escrita em um único registrador)

16 (Escrita em um bloco de registradores)


Base de Endereçamento: Base 1 (PLC Address): O endereço dos dados inicia em 1
Aplicável à versão de firmware: 4.16

3.1.1 Mapa de Registradores Modbus


Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
0 = auto
0 Modo Automático / Manual Grupo R.F.1 - - E/L
1 = manual
0 = auto
1 Modo Automático / Manual Grupo R.F.2 - - E/L
1 = manual
2 Não Utilizado - - - -
1
3 Não Utilizado - - - -
0 = auto
4 Modo Automático / Manual Grupo R.F.3 - - E/L
1 = manual
0 = auto
5 Modo Automático / Manual Grupo R.F.4 - - E/L
1 = manual
2 - Parâmetro ALO (Alarme do Óleo) -55...200 1 °C E/L
3 - Parâmetro DSO (Desligamento do Óleo) -55...200 1 °C E/L
Parâmetro RDO (Retardo Desligamento do
4 - 0...20 0,1 min. E/L
Óleo)
Parâmetro RF1 (Temperatura de partida do
5 - -55...200 1 °C E/L
E.R.1)
Parâmetro RF2 (Temperatura de partida do
6 - -55...200 1 °C E/L
E.R.2)
7 - Parâmetro ALE (Alarme do Enrolamento 1) -55...200 1 °C E/L

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 4


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
Parâmetro DSE (Desligamento do Enrolamento
8 - -55...200 1 °C E/L
1)
Parâmetro RDE (Retardo Desligamento Enrol.
9 - 0...20 0,1 min. E/L
1)
10 - Parâmetro HIS (Histerese do resfriamento) 0...9 1 °C E/L
Parâmetro GEO (Gradiente Enrolamento 1 /
11 - 0...50 0,1 °C E/L
Óleo)
Parâmetro TE (Constante de Tempo
12 - 72...999 1 s E/L
Enrolamento 1)
Parâmetro HS+ (Fator de Hot-Spot
13 - 0...20 0,1 - E/L
ABNT/IEEE)
14 - Parâmetro HS* (Fator de Hot-Spot IEC) 1...1,5 0,01 - E/L
0 = 1,6
15 - Parâmetro 2*M 1 = 1.8 1 - E/L
2 = 2.0
Parâmetro CNT (Corrente Nominal
16 - 0...99,8 0,001 A E/L
Enrolamento 1)
Parâmetro CNS (Corrente Nominal no
17 - 0,50...10,00 0,01 A E/L
Secundário do TC para o Enrolamento 1)
Registro de Temp. Máxima do Enrolamento 1
18 - -55...200 0,1 °C L
(MAX)
Registro de Temperatura Máxima do Óleo
19 - -55...200 0,1 °C L
(MAX)
20 - Valor atual da Temperatura do Óleo -55...200 0,1 °C L
21 - Valor atual da Temperatura do Enrolamento 1 -55...200 0,1 °C L
Valor atual do Gradiente Final Enrolamento 1
22 - 0...200 0,1 °C L
(GFN)
23 - Valor atual da Corrente no Enrolamento 1 0...655,35 0,01 kA L
0 = desligado
0 Estado do Relé de Alarme do Óleo - - L
1 = ligado
0 = desligado
1 Estado do Relé de Desligamento do Óleo - - L
1 = ligado
0 = desligado
2 Estado do Relé do G.R.1 (TM1) - - L
1 = ligado
0 = desligado
3 Estado do Relé do G.R.2 (TM1) - - L
1 = ligado
24
0 = desligado
4 Estado do Relé de Alarme do Enrolamento 1 - - L
1 = ligado
Estado do Relé de Desligamento do 0 = desligado
5 - - L
Enrolamento 1 1 = ligado
Estado do Relé de Sinalização de 0 = desligado
6 - - L
Desligamento Óleo / Enrolamento 1 1 = ligado
0 = desligado
7 Estado do Relé de Auto-Diagnóstico - - L
1 = ligado
25 - Percentual de Carga Enrolamento 1 0...3000 0,1 - L
26 - Parâmetro ALE (Alarme do Enrolamento 2) -55...200 1 °C E/L
Parâmetro DSE (Desligamento do Enrolamento
27 - -55...200 1 °C E/L
2)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 5


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
Parâmetro RDE (Retardo Desligamento do
28 - 0...20 0,1 min. E/L
Enrol. 2)
29 - Parâmetro ALE (Alarme do Enrolamento 3) -55...200 1 °C E/L
Parâmetro DSE (Desligamento do Enrolamento
30 - -55...200 1 °C E/L
3)
Parâmetro RDE (Retardo Desligamento do
31 - 0...20 0,1 min. E/L
Enrol. 3)
Parâmetro GEO (Gradiente Enrolamento 2 /
32 - 0...50 0,1 °C E/L
Óleo)
Parâmetro TE (Constante Tempo Enrolamento
33 - 72...999 1 s E/L
2)
Parâmetro CNT (Corrente Nominal
34 - 0...99,8 0,001 A E/L
Enrolamento 2)
Parâmetro CNS (Corrente Nominal no
35 - 0,50...10,00 0,01 A E/L
Secundário do TC para o Enrolamento 2)
Parâmetro GEO (Gradiente Enrolamento 3 /
36 - 0...50 0,1 °C E/L
Óleo)
Parâmetro TE (Constante Tempo Enrolamento
37 - 72...999 1 s E/L
3)
Parâmetro CNT (Corrente Nominal
38 - 0...99,8 0,001 A E/L
Enrolamento 3)
Parâmetro CNS (Corrente Nominal no
39 - 0,50...10,00 0,01 A E/L
Secundário do TC para o Enrolamento 3)
Registro de Temperatura Máxima do
40 - -55...200 0,1 °C L
Enrolamento 2
Registro de Temperatura Máxima do
41 - -55...200 0,1 °C L
Enrolamento 3
0 = desligado
0 Estado do Relé de Alarme do Enrolamento 2 - - L
1 = ligado
Estado do Relé de Desligamento do 0 = desligado
1 - - L
Enrolamento 2 1 = ligado
0 = desligado
2 Estado do Relé da G.R.3 (TM2) - - L
1 = ligado
0 = desligado
42 3 Estado do Relé do G.R.4 (TM2) - - L
1 = ligado
0 = desligado
4 Estado do Relé de Alarme do Enrolamento 3 - - L
1 = ligado
Estado do Relé de Desligamento do 0 = desligado
5 - - L
Enrolamento 3 1 = ligado
Estado do Relé de Sinalização de 0 = desligado
6 - - L
Desligamento Enrolamento 2 ou 3 1 = ligado
43 - Valor atual da Temperatura do Enrolamento 2 -55...200 0,1 °C L
44 - Valor atual da Temperatura do Enrolamento 3 -55...200 0,1 °C L
45 - Percentual atual de Carga Enrolamento 2 0...3000 0,1 - L
46 - Percentual atual de Carga Enrolamento 3 0...3000 0,1 - L
Valor atual do Gradiente Final Enrolamento
47 - 0...200 0,1 °C L
2(GFN)
Valor atual do Gradiente Final Enrolamento 3
48 - 0...200 0,1 °C L
(GFN)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 6


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
49 - Valor atual da Corrente Medida Enrolamento 2 0...655,35 0,01 kA L
50 - Valor atual da Corrente Medida Enrolamento 3 0...655,35 100 kA L

Parâmetro DMT (Dif. Máx. de Temp. sensores


51 - 1...6 1 °C E/L
A e B)

Parâmetro FSA TM1 (Faixa das saídas


52 - 0...4 1 - E/L
analógicas)
Parâmetro RTD TM1 (Config. sensores
53 - 0...4 1 - E/L
temperatura)
54 - Parâmetro SUP (Modo de Supervisão) 0...4 1 - E/L
Parâmetro IDI TM1 (Idioma de interface do
55 - 0...2 1 - E/L
TM1)
Corrente secundária atual no TC do enrol. 1
56 - 0...10 100 A L
(AMP)
Medição atual sensor de temperatura A TM1
57 - -55...200 10 °C L
(PTA)
Medição atual sensor de temperatura B TM1
58 - -55...200 10 °C L
(PTB)
59 a 62 - Não Utilizado - - - -
Parâmetro FSA TM2 (Faixa das saídas
63 - 0...4 1 - E/L
analógicas)
Parâmetro IDI TM2 (Idioma de interface do
64 - 0...2 1 - E/L
TM2)
Corrente secundária atual no TC do enrol. 2
65 - 0...10 100 A L
(AMP)
Corrente secundária atual no TC do enrol. 3
66 - 0...10 100 A L
(AMP)
Parâmetro CV1 (Percentual de Carga para
67 - 50...200 1 - E/L
E.R.1)
Parâmetro CV2 (Percentual de Carga para
68 - 50...200 1 - E/L
E.R.2)
Parâmetro HIC (Histerese de carga para
69 - 0...9 1 - E/L
resfriamento)
Parâmetro EVH (Hora p/ exercício dos
70 - 0...23 1 - E/L
ventiladores)
Parâmetro EVM (Minuto exercício dos
71 - 0...59 1 - E/L
ventiladores)
Parâmetro TEV (Tempo de exercício dos
72 - 0...999 1 min. E/L
ventiladores)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 7


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior
Enrolamento
5 = PTA TM1
6 = PTB TM1
7 = PTA TM2
8 = PTB TM2
9 = Diferencial
DT1
Parâmetro VA1 TM1 (Variável de saída 10 = Diferencial
73 - 1 - E/L
analógica 1) DT2
11 = Diferencial
DT3
12 = Maior
Diferencial
13 = Diferencial
DF1
14 = Diferencial
DF2
15 = Diferencial
DF3
16 = Maior Dif.
filtrado
Parâmetro FE1 TM1 (Fundo Escala saída
74 - -55...200 1 °C E/L
analógica 1)
Parâmetro IE1 TM1 (Início Escala saída
75 - -55...200 1 °C E/L
analógica 1)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 8


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior
Enrolamento
5 = PTA TM1
6 = PTB TM1
7 = PTA TM2
8 = PTB TM2
9 = Diferencial
DT1
Parâmetro VA2 TM1 (Variável de saída 10 = Diferencial
76 - 1 - E/L
analógica 2) DT2
11 = Diferencial
DT3
12 = Maior
Diferencial
13 = Diferencial
D1F
14 = Diferencial
D2F
15 = Diferencial
D3F
16 = Maior Dif.
filtrado
Parâmetro FE2 (Fundo de Escala da saída
77 - -55...200 1 °C E/L
analógica 2)
Parâmetro IE2 (Início de Escala da saída
78 - -55...200 1 °C E/L
analógica 2)
0 = Aviso de
desligamento
1 = Alarme dif.
instantâneo
Parâmetro RL7 TM1 (Configuração do Relé
79 - 2 = Alarme dif. 1 - E/L
Programável)
filtrado
3 = Alarme dif.
instantâneo ou
filtrado
Parâmetro TLG (Intervalo entre gravações no
80 - 1...120 1 min. E/L
LOG)
Parâmetro HLG (Histerese para gravações no
81 - 1...20 1 °C E/L
LOG)
Parâmetro ADI (alarme por diferencial
82 - -40,0...40,0 10 °C E/L
instantâneo)
83 - Parâmetro ADF (alarme por diferencial filtrado) -40,0...40,0 10 °C E/L
Parâmetro MAA (margem de temp. p/ ajuste
84 - 1...10 1 °C E/L
autom.)
Parâmetro TAA (tempo de amostragem p/
85 - 1...720 1 min. E/L
ajuste auto)
Parâmetro CTF (constante de tempo para dif.
86 - 0...720 1 min. E/L
filtrado)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 9


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
Parâmetro TAL (temporização p/ alarmes
87 - 0...240 1 min. E/L
diferenciais)
1 = RTD A TM1
2 = RTD B TM1
Parâmetro TTR (seleção sensor de temperatura
88 - 3 = RTD A TM2 1 - E/L
do óleo para diferencial)
4 = RTD B TM2
5 = Temp. óleo
0 = Desabilitado
1 = RTD A TM1
Parâmetro TC1 (seleção sensor de temperatura
89 - 2 = RTD B TM1 1 - E/L
comutador 1)
3 = RTD A TM2
4 = RTD B TM2
0 = Desabilitado
1 = RTD A TM1
Parâmetro TC2 (seleção sensor de temperatura
90 - 2 = RTD B TM1 1 - E/L
comutador 2)
3 = RTD A TM2
4 = RTD B TM2
0 = Desabilitado
1 = RTD A TM1
Parâmetro TC3 (seleção sensor de temperatura
91 - 2 = RTD B TM1 1 - E/L
comutador 3)
3 = RTD A TM2
4 = RTD B TM2
Parâmetro AAA (iniciar/interromper processo de 0 = OFF (interr.)
92 - 1 - E/L
ajuste automático de alarmes diferenciais) 1 = ON (iniciar)
93 - Parâmetro DIA (Ajuste do Relógio) 1...31 1 - E/L
94 - Parâmetro MÊS (Ajuste do Relógio) 1...12 1 - E/L
95 - Parâmetro ANO (Ajuste do Relógio) 00...99 1 - E/L
96 - Parâmetro HORA (Ajuste do Relógio) 0...23 1 - E/L
97 - Parâmetro MIN (Ajuste do Relógio) 0...59 1 - E/L
Parâmetro NGR (Número de Grupos de
98 - 1...4 1 - E/L
Resfriamento)
Parâmetro RF3 (Temperatura de partida do
99 - -55...200 1 °C E/L
E.R.3)
Parâmetro RF4 (Temperatura de partida do
100 - -55...200 1 °C E/L
E.R.4)
Parâmetro CV3 (Percentual de Carga para
101 - 50...200 1 - E/L
E.R.3)
Parâmetro CV4 (Percentual de Carga para
102 - 50...200 1 - E/L
E.R.4)
Parâmetro GR1/E.R.1 (Inscrição do grupo 1 no
103 - 0=Não 1=Sim 1 - E/L
E.R.1)
Parâmetro GR2/E.R.1 (Inscrição do grupo 2 no
104 - 0=Não 1=Sim 1 - E/L
E.R.1)
Parâmetro GR3/E.R.1 (Inscrição do grupo 3 no
105 - 0=Não 1=Sim 1 - E/L
E.R.1)
Parâmetro GR4/E.R.1 (Inscrição do grupo 4 no
106 - 0=Não 1=Sim 1 - E/L
E.R.1)
Parâmetro GR1/E.R.2 (Inscrição do grupo 1 no
107 - 0=Não 1=Sim 1 - E/L
E.R.2)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 10


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
Parâmetro GR2/E.R.2 (Inscrição do grupo 2 no
108 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR3/E.R.2 (Inscrição do grupo 3 no
109 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR4/E.R.2 (Inscrição do grupo 4 no
110 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR1/E.R.3 (Inscrição do grupo 1 no
111 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR2/E.R.3 (Inscrição do grupo 2 no
112 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR3/E.R.3 (Inscrição do grupo 3 no
113 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR4/E.R.3 (Inscrição do grupo 4 no
114 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR1/E.R.4 (Inscrição do grupo 1 no
115 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR2/E.R.4 (Inscrição do grupo 2 no
116 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR3/E.R.4 (Inscrição do grupo 3 no
117 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR4/E.R.4 (Inscrição do grupo 4 no
118 - 0=Não 1=Sim 1 - E/L
E.R.4)
Reset das temperaturas máximas e mínimas
119 - 0=Não 1=Sim 1 - E/L
registradas pelo opcional DTC.
Parâmetro GR2/E.R.2 (Inscrição do grupo 2 no
108 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR3/E.R.2 (Inscrição do grupo 3 no
109 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR4/E.R.2 (Inscrição do grupo 4 no
110 - 0=Não 1=Sim 1 - E/L
E.R.2)
Parâmetro GR1/E.R.3 (Inscrição do grupo 1 no
111 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR2/E.R.3 (Inscrição do grupo 2 no
112 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR3/E.R.3 (Inscrição do grupo 3 no
113 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR4/E.R.3 (Inscrição do grupo 4 no
114 - 0=Não 1=Sim 1 - E/L
E.R.3)
Parâmetro GR1/E.R.4 (Inscrição do grupo 1 no
115 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR2/E.R.4 (Inscrição do grupo 2 no
116 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR3/E.R.4 (Inscrição do grupo 3 no
117 - 0=Não 1=Sim 1 - E/L
E.R.4)
Parâmetro GR4/E.R.4 (Inscrição do grupo 4 no
118 - 0=Não 1=Sim 1 - E/L
E.R.4)
Reset das temperaturas máximas e mínimas
119 - 0=Não 1=Sim 1 - E/L
registradas pelo opcional DTC.
501 - Não Usado - - - -
502 - Não Usado - - - -

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 11


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior
Enrolamento
5 = PTA TM1
6 = PTB TM1
7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial
Parâmetro VA1 TM2 (Variável de saída
503 - DT2 1 - E/L
analógica 1)
11 = Diferencial
DT3
12 = Maior
Diferencial
13 = Diferencial
D1F
14 = Diferencial
D2F
15 = Diferencial
D3F
16 = Maior Dif.
Filtrado
Parâmetro FE1 TM2 (Fundo Escala saída
504 - -55...200 1 °C E/L
analógica 1)
Parâmetro IE1 TM2 (Início Escala saída
505 - -55...200 1 °C E/L
analógica 1)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 12


Monitor de Temperaturas
TM1 / TM2
Escri
Faixa de
Regist Unid ta /
Bit Descrição do Registrador Medição ou Escala
rador ade Leitu
Estado
ra
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior
Enrolamento
5 = PTA TM1
6 = PTB TM1
7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial
Parâmetro VA2 TM2 (Variável de saída
506 - DT2 1 - E/L
analógica 2)
11 = Diferencial
DT3
12 = Maior
Diferencial
13 = Diferencial
D1F
14 = Diferencial
D2F
15 = Diferencial
D3F
16 = Maior Dif.
Filtrado
Parâmetro FE2 TM2 (Fundo Escala saída
507 - -55...200 1 °C E/L
analógica 2)
Parâmetro IE2 TM2 (Início Escala saída
508 - -55...200 1 °C E/L
analógica 2)
0 = Aviso de
desligamento
1 = Alarme dif.
Instant.
Parâmetro RL7 TM2 (Configuração do Relé
509 - 2 = Alarme dif. 1 - E/L
Programável)
Filtrado
3 = Alarme dif.
Instantâneo ou
filtrado
510 - Parâmetro RTD (Conf. Sensor Temp. TM2) 0...4 1 - E/L
Parâmetro DSP – Válido para o TM2 (Escolha 0 = EN3
511 - da temperatura apresentada no display inferior 1 = PTA – TM2 1 - E/L
do TM2) 2 = PTB – TM2

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 13


Monitor de Temperaturas
TM1 / TM2
Faixa de
Registrador Bit Descrição do Registrador Medição ou Escala
Estado
1001 - Diferencial de Temperatura 1 (DT1) -145...+255 0,1 °C L
1002 - Diferencial de Temperatura 2 (DT2) -145...+255 0,1 °C L
1003 - Diferencial de Temperatura 3 (DT3) -145...+255 0,1 °C L
1004 - Diferencial de Temperatura Filtrado 1 (DF1) -145...+255 0,1 °C L
1005 - Diferencial de Temperatura Filtrado 2 (DF2) -145...+255 0,1 °C L
1006 - Diferencial de Temperatura Filtrado 3 (DF3) -145...+255 0,1 °C L
1007 - Menor valor de Diferencial de Temperatura 1 -145...+255 0,1 °C L
1008 - Menor valor de Diferencial de Temperatura 2 -145...+255 0,1 °C L
1009 - Menor valor de Diferencial de Temperatura 3 -145...+255 0,1 °C L
Menor valor de Diferencial de Temperatura
1010 - -145...+255 0,1 °C L
Filtrado 1
Menor valor de Diferencial de Temperatura
1011 - -145...+255 0,1 °C L
Filtrado 2
Menor valor de Diferencial de Temperatura
1012 - -145...+255 0,1 °C L
Filtrado 3
1013 - Maior valor de Diferencial de Temperatura 1 -145...+255 0,1 °C L
1014 - Maior valor de Diferencial de Temperatura 2 -145...+255 0,1 °C L
1015 - Maior valor de Diferencial de Temperatura 3 -145...+255 0,1 °C L
Maior valor de Diferencial de Temperatura
1016 - -145...+255 0,1 °C L
Filtrado 1
Maior valor de Diferencial de Temperatura
1017 - -145...+255 0,1 °C L
Filtrado 2
Maior valor de Diferencial de Temperatura
1018 - -145...+255 0,1 °C L
Filtrado 3
1019 - Maior valor de temperatura do comutador 1 -145...+255 0,1 °C L
1020 - Maior valor de temperatura do comutador 2 -145...+255 0,1 °C L
1021 - Maior valor de temperatura do comutador 3 -145...+255 0,1 °C L
Tempo restante p/ ajustes automáticos de
1022 - 0...720 1 min. L
diferenciais
0 = Normal
0 Erro de comunicação entre TM1 e TM2. - - L
1 = Erro
1 Programação incorreta do parâmetro SUP - - L 1
2 Falha na memória EEPROM TM1 - - L 2
1023 3 Overflow nas medições TM1 - - L 3
4 Falha medição temperatura do óleo - - L 4
5 Falha no Conversor AD TM1 - - L 5
6 Falha na medição da corrente de carga 1 TM1 - - L 6

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 14


Monitor de Temperaturas
TM1 / TM2
Faixa de
Registrador Bit Descrição do Registrador Medição ou Escala
Estado
7 Não usado - - L 7
Falha medição de temperatura sensor A TM1
8 - - L 8
(term. 1)
Falha medição de temperatura sensor B TM1
9 - - L 9
(term. 1)
Falha medição de temperatura sensor A TM1
10 - - L 10
(term. 2)
Falha medição de temperatura sensor B TM1
11 - - L 11
(term. 2)
Falha medição temp. sensor A TM1 - mudança
12 - - L 12
brusca
Falha medição temp. sensor B TM1 - mudança
13 - - L 13
brusca
0 Não usado - - - L
Atingida temperatura de desligamento 0 = Não
1024 2 - - L
enrolamento 1 1 = Sim
Atingida temperatura de desligamento do 0 = Não
3 - - L
óleo 1 = Sim
1025 - Ponteiro da memória de massa - 1 - L
Temp. do óleo do trafo p/ diferencial do
1026 - -55...200 0.1 °C L
Comutador
1027 - Temperatura do óleo do Comutador 1 -55...200 0.1 °C L
1028 - Temperatura do óleo do Comutador 2 -55...200 0.1 °C L
1029 - Temperatura do óleo do Comutador 3 -55...200 0.1 °C L
0 Não usado - - - L
Alarme diferencial de temperatura 0 = Normal
1030 1 - - L
instantâneo do Comutador 1 = Alarme
Alarme diferencial de temperatura filtrado do 0 = Normal
2 - - L
Comutador 1 = Alarme
Tempo restante p/ desligamento por temp. do
1031 - 0...20 0.1 min. L
óleo
Tempo restante p/ desligamento por temp. do
1032 - 0...20 0.1 min. L
enrol. 1
Medição atual sensor de temperatura A TM2
1501 - -55...200 0,1 °C L
(PTA)
Medição atual sensor de temperatura B TM2
1502 - -55...200 0,1 °C L
(PTB)
0 Erro de comunicação entre TM1 e TM2. - - L
1 Não Usado 0 = Normal - - L
1503
2 Falha na memória EEPROM TM2 1 = Erro - - L
3 Overflow nas medições TM2 - - L

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 15


Monitor de Temperaturas
TM1 / TM2
Faixa de
Registrador Bit Descrição do Registrador Medição ou Escala
Estado
4 Não Usado - - L
5 Falha no Conversor AD TM2 - - L
6 Falha na medição da corrente de carga 1 TM2 - - L
7 Falha na medição da corrente de carga 2 TM2 - - L
Falha medição de temperatura sensor A TM2
8 - - L
(term. 1)
Falha medição de temperatura sensor B TM2
9 - - L
(term. 1)
Falha medição de temperatura sensor A TM2
10 - - L
(term. 2)
Falha medição de temperatura sensor B TM2
11 - - L
(term. 2)
Falha medição temp. sensor A TM2 - mudança
12 - - L
brusca
Falha medição temp. sensor B TM2 - mudança
13 - - L
brusca
0 Não usado - - - L
1 Não usado - - - L
1504 Atingida temperatura de desligamento 0 = Não
2 - - L
enrolamento 2 1 = Sim
Atingida temperatura de desligamento 0 = Não
3 - - L
enrolamento 3 1 = Sim
Tempo restante p/ desligamento por temp. do
1505 - 0...20 0.1 min. L
enrol. 2
Tempo restante p/ desligamento por temp. do
1506 - 0...20 0.1 min. L
enrol. 3

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 16


Monitor de Temperaturas
TM1 / TM2
3.2 Protocolo DNP 3.0 - Informações Gerais
Protocolo DNP 3.0 Nível 1
Taxa de transmissão 4800, 9600, 19200 ou 38400, 57600, 115200 bps, selecionável pelo usuário
Bits de parada 1 ou 2, selecionável pelo usuário
Paridade Nenhuma
Aplicável à versão de firmware 4.16

DNP V3.0
DEVICE PROFILE DOCUMENT

This document is accompanied by table 1, Supported DNP 3.0 Objects, Function Codes, and
Qualifiers,and table 2, Point List.

Vendor Name: Treetech Sistemas Digitais

Device Name: Monitor de Temperatura TM1 e Monitor de Temperatura TM2

Highest DNP Level Supported: Device Function:

For Requests: Level 1 Master Remote


For Responses: ______

Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:

 Reads of Binary Inputs (Object 01, Variation 01, Qualifier 00, 01 and 06)

 Reads of 16-bit Analog Inputs (Object 30, Variation 04, Qualifier 00, 01 and 06)

GENERAL INFORMATION:

Maximum Data Link Frame Size (octets): Maximum Application Frame Size (octets):

Transmitted: 292 Transmitted: 500


Received: (must be 292) Received: 200

Maximum Data Link Re-tries: Maximum Application Layer Re-tries:

None None
Fixed at ___ Configurable, range ___ to ___
Configurable, range 0 to 255 (Fixed is not permitted)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 17


Monitor de Temperaturas
TM1 / TM2
Requires Data Link Layer Confirmation:

Never
Always
Sometimes If Sometimes, when? ______________________________
Configurable as: __________________________________________

Requires Application Layer Confirmation:

Never
Always (Not recommended)
When reporting Event Data (Slave devices only)
When sending mult-fragment responses (Slave devices only)
Sometimes: If ‘Sometimes’, when? __________________________________________
Configurable: If ‘Configurable’, how? _________________________________________
Timeouts while waiting for:

Data link confirm:


None Fixed at _____ Variable Configurable*
Complete Appl. Fragment:
None Fixed at _____ Variable Configurable*
Aplication Confirm: None Fixed at _____ Variable Configurable*
Complete Appl. Response: None Fixed at _____ Variable Configurable*
Others: ______________________________________________________________________
*Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout
Sends/Executes Control Operations:

WRITE Binary Outputs: Never Always Sometimes Configurable


SELECT/OPERATE: Never Always Sometimes Configurable
DIRECT OPERATE: Never Always Sometimes Configurable
DIRECT OPERATE-No ACK: Never Always Sometimes Configurable

Count > 1: Never Always Sometimes Configurable


Pulse On: Never Always Sometimes Configurable
Pulse Off: Never Always Sometimes Configurable
Latch On: Never Always Sometimes Configurable
Latch Off: Never Always Sometimes Configurable

Queue: Never Always Sometimes Configurable


Clear Queue: Never Always Sometimes Configurable

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.


FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:

Expects Binary Input Change Events:

Either time-tagged or non-time-tagged for a single event.


Both time-tagged and non-time-tagged for a single event.
Configurable (Attach explanation)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 18


Monitor de Temperaturas
TM1 / TM2
FILL OUT THE FOLLOWING ITEMS FOR REMOTE DEVICES ONLY:
Default Status Object/Variation: Default Analog Object/Variation:

No Status objects reported No Analog objects reported


Configurable (attach explanation) Configurable (attach explanation)
Default Static Object_____________ Default Static Object______________
Default Static Variation __________ Default Static Variation ___________
Default Event Object_____________ Default Event Object______________
Default Event Variation __________ Default Event Variation ___________
Point-by-point list attached Point-by-point list attached

Default Counter Object/Variation: Counters Roll Over at:

No Counters reported No Counters Reported


Configurable (attach explanation) Configurable (attach explanation)
Default Static Object____________ 16 Bits
Default Static Variation__________ 32 Bits
Default Event Object____________ Other Value _________
Default Event Variation _________ Point-by-point list attached
Point-by-point list attached

Default Frozen Counter Object/Variation: Counters frozen by means of:

No Frozen Counters reported No Frozen Counters reported


Configurable (attach explanation) Remote device time based
Default Static Object____________ Fixed time
Default Static Variation__________ Configurable; range _____ to _____
Default Event Object____________ Master Request (see implementation table)
Default Event Variation __________ Both
Point-by-point list attached

Analog Deadbands: Configuring Analog Deadbands:

Fixed Not Applicable


Configurable: ____ Configuration Software
Per Point Using Object 34 from the master station
Per Analog Type Both configuration software and Object 34
Global

Are the updated deadband values preserved through a device reset:

YES
NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: 3

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 19


Monitor de Temperaturas
TM1 / TM2
Ability to DISABLE/ENABLE DNP database points: IIN 1-6 Device Trouble Bit:

Not Applicable Never used


Per point Reason for setting:
Per object
Global

Time Sync Information:

Time Sync Period:

Never
Fixed at ______ seconds
Configurable, range ______ to _______ seconds

a) Maximum time base drift over a 10 minute interval: _________ ms


b) Maximum Internal Time Reference Error when set via DNP: _________ ms
c) Maximum Delay Measurement error: _________ ms
d) Maximum Response time: _________ ms
e) Event data time-tag error – if different than ( c ) :
Binary Input Change Events __________ ms
Counter Change Events __________ ms
Frozen Counter Change Events __________ ms
Analog Change Events __________ ms
Frozen Analog Change Events __________ ms

Sends/Executes Digital Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable


DIRECT OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE – NO ACK* Never Always Sometimes Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.


*To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be
selected.

Count > 1 Never Always Sometimes Configurable


Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Trip/Close Never Always Sometimes Configurable
Raise/Lower Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable


Clear Queue Never Always Sometimes Configurable

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 20


Monitor de Temperaturas
TM1 / TM2
Sends/Executes Analog Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable


DIRECT OPERATE* Never Always Sometimes Configurable
DIRECT OPERATE – NO ACK* Never Always Sometimes Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.


*To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be
selected.

Queue Never Always Sometimes Configurable


Clear Queue Never Always Sometimes Configurable

The maximum number of objects supported in a single control request for objects 12 and 41.

Number of objects allowed for object 12: 1


Number of objects allowed for object 41: 1

Control Points per address:


Do all indices support the same control codes:
Configurable
YES– Controls codes 3 and 4
1 control point per address
NO – attached points list stating configuration ability
2 control points per address
and supported control codes per point or group of points

Maximum Select/Execute Delay Time: Ability for REMOTE/LOCAL control mode:

Not Applicable Not Applicable


Fixed at _____ seconds Per point
Configurable, range ______ to ______ seconds Per object
Global

Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

Never Never
Configurable (attach explanation) When Device Restarts
Only certain objects When Status Flags Change
Sometimes (attach explanation)
*No other options permitted.
ENABLE/DISABLE Unsolicited: Minimum number of events and/or minimum time
before transmission of an unsolicited message.
Not Supported
Configurable # of events:__________
Function codes 20,21 supported min. amount of time(msec) :___________

Assign Class Function code supported: Is the Event Buffer size configurable:

NO NO fixed size: _______


YES YES: range: _________to_________
Per Object
Per Point Configurable Per Class buffer:
Configurable NO
YES

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 21


Monitor de Temperaturas
TM1 / TM2

Are the updated ENABLE/DISABLE unsolicited settings saved Are the updated Assign Class settings saved through a
through a device reset: device reset:

YES YES
NO NO

Supports Collision Avoidance:

Never
Always (attach explanation)
Configurable (attach explanation)

Source Address Filtering:

Not Supported
Configurable (attach explanation)

Supports Multi-drop communications: Yes No

Sends Multi-Fragment Responses: Yes No

3.2.1 Objetos Suportados no DNP 3.0


Supported DNP 3.0 Objects, Function Codes, and Qualifiers
REQUESTS RESPONSES
OBJECTS
(slave will parse) (master must parse)
Function Qualifier Function Qualifier
Object Variation Description
Codes Codes(hex) Codes Codes(hex)
01 01 Binary Input 01 06 00, 129 00, 01
10 02 Binary Output 01, 02 06 00, 129 00, 01
12 01 Control Relay Output Block 05, 06 17, 28 00, 129 Echo
30 04 16 bit Analog Input without flag 01 06 00, 129 00, 01
40 02 16 bit Analog Output Status 01 06 00, 129 00, 01
41 02 16-bit Analog Output Block 05, 06 17, 28 00, 129 Echo
50 01 Time and Date – Absolute Time
60 01 Class 0 Data 01 06 129 00, 01
60 02 Class 1 Data 01 06 129 00, 01
60 03 Class 2 Data 01 06 129 00, 01
60 04 Class 3 Data 01 06 129 00, 01
80 01 Internal Indications 02 00, index=7 129 -
- - Cold Restart 13 - 129 -

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 22


Monitor de Temperaturas
TM1 / TM2

Point List
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Binary output 0 12 01 No status - Modo Auto / Manual Grupo R.F.1
Binary output 1 12 01 No status - Modo Auto / Manual Grupo R.F.2
Binary output 2 12 01 No status - Não Usado
Binary output 3 12 01 No status - Não Usado
Binary output 4 12 01 No status - Modo Auto / Manual Grupo R.F.3
Binary output 5 12 01 No status - Modo Auto / Manual Grupo R.F.4
Binary output 6...7 12 01 No status - Não Usado
Analog output block 0 41 02 16-bit - Parâmetro ALO (Alarme do Óleo)
Parâmetro DSO (Desligamento
Analog output block 1 41 02 16-bit -
do Óleo)
Parâmetro RDO (Retardo do
Analog output block 2 41 02 16-bit 1x10
Desligamento do Óleo)
Parâmetro RF1 (Partida do
Analog output block 3 41 02 16-bit -
E.R.1)
Parâmetro RF2 (Partida do
Analog output block 4 41 02 16-bit -
E.R.2)
Parâmetro ALE (Alarme do
Analog output block 5 41 02 16-bit -
Enrolamento 1)
Parâmetro DSE (Desligamento
Analog output block 6 41 02 16-bit -
do Enrolamento 1)
Parâmetro RDE (Retardo do
Analog output block 7 41 02 16-bit 1x10
Desligamento Enrolamento 1)
Parâmetro HIS (Histerese do
Analog output block 8 41 02 16-bit -
resfriamento)
Parâmetro GEO (Gradiente
Analog output block 9 41 02 16-bit 1x10
Enrolamento 1/Óleo)
Parâmetro TE (Constante de
Analog output block 10 41 02 16-bit -
Tempo Enrolamento 1)
Parâmetro HS+ (Fator de Hot-
Analog output block 11 41 02 16-bit -
Spot ABNT/IEEE)
Parâmetro HS* (Fator de Hot-
Analog output block 12 41 02 16-bit 1x100
Spot IEC)
Parâmetro Expoente 2M
0 = 1.6
Analog output block 13 41 02 16-bit -
1 = 1.8
2 = 2.0
Parâmetro CNT (Corrente
Analog output block 14 41 02 16-bit 1x1000
Nominal Enrolamento 1)
Parâmetro CNS (Corrente
Analog output block 15 41 02 16-bit 1x100 Nominal no Secundário do TC
para o Enrolamento 1)
Registro de Temperatura Máxima
Analog output block 16 41 02 16-bit -
do Enrolamento 1
Registro de Temperatura Máxima
Analog output block 17 41 02 16-bit -
do Óleo
Parâmetro DMT (Dif. Máx. de
Analog output block 18 41 02 16-bit 1x10
Temp. sensores A e B)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 23


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro FSA (Faixa das
Analog output block 19 41 02 16-bit -
saídas analógicas TM1)
Parâmetro RTD (Config. dos
Analog output block 20 41 02 16-bit - sensores de temperatura do
TM1)
Parâmetro IDI (Idioma de
Analog output block 21 41 02 16-bit -
interface do TM1)
Analog output block 22 41 02 16-bit - Uso Interno
Parâmetro ALE (Alarme do
Analog output block 23 41 02 16-bit -
Enrolamento 2)
Parâmetro DSE (Desligamento
Analog output block 24 41 02 16-bit -
do Enrolamento 2)
Parâmetro RDE (Retardo
Analog output block 25 41 02 16-bit 1x10
Desligamento do Enrol. 2)
Parâmetro ALE (Alarme do
Analog output block 26 41 02 16-bit -
Enrolamento 3)
Parâmetro DSE (Desligamento
Analog output block 27 41 02 16-bit -
do Enrolamento 3)
Parâmetro RDE (Retardo
Analog output block 28 41 02 16-bit 1x10
Desligamento do Enrol. 3)
Parâmetro GEO (Gradiente
Analog output block 29 41 02 16-bit 1x10
Enrolamento 2 / Óleo)
Parâmetro TE (Constante Tempo
Analog output block 30 41 02 16-bit -
Enrolamento 2)
Parâmetro CNT (Corrente
Analog output block 31 41 02 16-bit 1x1000
Nominal Enrolamento 2)
Parâmetro CNS (Corrente
Analog output block 32 41 02 16-bit 1x100 Nominal no Secundário do TC
para o Enrolamento 2)
Parâmetro GEO (Gradiente
Analog output block 33 41 02 16-bit 1x10
Enrolamento 3 / Óleo)
Parâmetro TE (Constante Tempo
Analog output block 34 41 02 16-bit -
Enrolamento 3)
Parâmetro CNT (Corrente
Analog output block 35 41 02 16-bit 1x1000
Nominal Enrolamento 3)
Parâmetro CNS (Corrente
Analog output block 36 41 02 16-bit 1x100 Nominal no Secundário do TC
para o Enrolamento 3)
Registro de Temperatura Máxima
Analog output block 37 41 02 16-bit -
do Enrolamento 2
Registro de Temperatura Máxima
Analog output block 38 41 02 16-bit -
do Enrolamento 3
Parâmetro FSA (Faixa das
Analog output block 39 41 02 16-bit -
saídas analógicas TM2)
Parâmetro IDI (Idioma de
Analog output block 40 41 02 16-bit -
interface do TM2)
Parâmetro CV1 (Percentual de
Analog output block 41 41 02 16-bit -
Carga para E.R.1)
Parâmetro CV2 (Percentual de
Analog output block 42 41 02 16-bit -
Carga para E.R.2)
Parâmetro HIC (Histerese de
Analog output block 43 41 02 16-bit -
carga para resfriamento)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 24


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro EVH (Hora p/
Analog output block 44 41 02 16-bit -
exercício dos ventiladores)
Parâmetro EVM (Minuto
Analog output block 45 41 02 16-bit -
exercício dos ventiladores)
Parâmetro TEV (Tempo de
Analog output block 46 41 02 16-bit -
exercício dos ventiladores)
Analog output block 47 41 02 16-bit - Ajustar Dia
Analog output block 48 41 02 16-bit - Ajustar Mês
Analog output block 49 41 02 16-bit - Ajustar Ano
Analog output block 50 41 02 16-bit - Ajustar Horas
Analog output block 51 41 02 16-bit - Ajustar Minutos
Parâmetro VA1 (Variável de
saída analógica 1 do TM1):
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior Enrolamento
5 = PTA TM1
6 = PTB TM1
Analog output block 52 41 02 16-bit - 7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial DT2
11 = Diferencial DT3
12 = Maior Diferencial
13 = Diferencial D1F
14 = Diferencial D2F
15 = Diferencial D3F
16 = Maior Dif. filtrado
Parâmetro FE1 (Fundo de Escala
Analog output block 53 41 02 16-bit -
da saída analógica 1 do TM1)
Parâmetro IE1 (Início de Escala
Analog output block 54 41 02 16-bit -
da saída analógica 1 do TM1)
Parâmetro VA2 (Variável de
saída analógica 2 do TM1):
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior Enrolamento
5 = PTA TM1
6 = PTB TM1
Analog output block 55 41 02 16-bit - 7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial DT2
11 = Diferencial DT3
12 = Maior Diferencial
13 = Diferencial D1F
14 = Diferencial D2F
15 = Diferencial D3F
16 = Maior Dif. filtrado

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 25


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro FE2 (Fundo de Escala
Analog output block 56 41 02 16-bit -
da saída analógica 2 do TM1)
Parâmetro IE2 (Início de Escala
Analog output block 57 41 02 16-bit -
da saída analógica 2 do TM1)
Parâmetro RL7 (Configuração do
Relé Programável do TM1):
0 = Aviso de desligamento
Analog output block 58 41 02 16-bit - 1 = Alarme dif. instantâneo
2 = Alarme dif. filtrado
3 = Alarme dif. instantâneo ou
filtrado
Parâmetro TLOG (Intervalo entre
Analog output block 59 41 02 16-bit -
gravações no LOG)
Parâmetro HLOG (Histerese para
Analog output block 60 41 02 16-bit -
gravações no LOG)
Parâmetro ADI (alarme por
Analog output block 61 41 02 16-bit -
diferencial instantâneo)
Parâmetro ADF (alarme por
Analog output block 62 41 02 16-bit -
diferencial filtrado)
Parâmetro MAA (margem de
Analog output block 63 41 02 16-bit -
temp. p/ ajuste autom.)
Parâmetro TAA (tempo de
Analog output block 64 41 02 16-bit -
amostragem p/ ajuste auto)
Parâmetro CTF (constante de
Analog output block 65 41 02 16-bit -
tempo para dif. filtrado)
Parâmetro TAL (temporização p/
Analog output block 66 41 02 16-bit -
alarmes diferenciais)
Parâmetro TTR (seleção sensor
de temperatura do óleo p/
diferencial):
1 = RTD A TM1
Analog output block 67 41 02 16-bit -
2 = RTD B TM1
3 = RTD A TM2
4 = RTD B TM2
5 = Temp. óleo
Parâmetro TC1 (seleção sensor
de temperatura comutador 1):
0 = Desabilitado
Analog output block 68 41 02 16-bit - 1 = RTD A TM1
2 = RTD B TM1
3 = RTD A TM2
4 = RTD B TM2
Parâmetro TC2 (seleção sensor
de temperatura comutador 2):
0 = Desabilitado
Analog output block 69 41 02 16-bit - 1 = RTD A TM1
2 = RTD B TM1
3 = RTD A TM2
4 = RTD B TM2

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 26


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro TC3 (seleção sensor
de temperatura comutador 3):
0 = Desabilitado
Analog output block 70 41 02 16-bit - 1 = RTD A TM1
2 = RTD B TM1
3 = RTD A TM2
4 = RTD B TM2
Parâmetro AAA
(iniciar/interromper processo de
ajuste automático de alarmes
Analog output block 71 41 02 16-bit -
diferenciais):
0 = OFF (interromper)
1 = ON (iniciar)
Parâmetro VA1 (Variável de
saída analógica 1 do TM2):
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior Enrolamento
5 = PTA TM1
6 = PTB TM1
Analog output block 72 41 02 16-bit - 7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial DT2
11 = Diferencial DT3
12 = Maior Diferencial
13 = Diferencial D1F
14 = Diferencial D2F
15 = Diferencial D3F
16 = Maior Dif. filtrado
Parâmetro FE1 (Fundo de Escala
Analog output block 73 41 02 16-bit -
da saída analógica 1 do TM2)
Parâmetro IE1 (Início de Escala
Analog output block 74 41 02 16-bit -
da saída analógica 1 do TM2)
Parâmetro VA2 (Variável de
saída analógica 1 do TM2):
0 = Temp. Óleo
1 = Temp. Enrol. 1
2 = Temp. Enrol. 2
3 = Temp. Enrol. 3
4 = Maior Enrolamento
5 = PTA TM1
6 = PTB TM1
Analog output block 75 41 02 16-bit - 7 = PTA TM2
8 = PTB TM2
9 = Diferencial DT1
10 = Diferencial DT2
11 = Diferencial DT3
12 = Maior Diferencial
13 = Diferencial D1F
14 = Diferencial D2F
15 = Diferencial D3F
16 = Maior Dif. filtrado

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 27


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro FE2 (Fundo de Escala
Analog output block 76 41 02 16-bit -
da saída analógica 2 do TM2)
Parâmetro IE2 (Início de Escala
Analog output block 77 41 02 16-bit -
da saída analógica 2 do TM2)
Parâmetro RL7 (Configuração do
Relé Programável do TM2):
0 = Aviso de desligamento
Analog output block 78 41 02 16-bit - 1 = Alarme dif. instantâneo
2 = Alarme dif. filtrado
3 = Alarme dif. instantâneo ou
filtrado
Parâmetro RTD (Configuração
Analog output block 79 41 02 16-bit -
do sensor de temperatura TM2)
Parâmetro NGR (Número de
Analog output block 80 41 02 16-bit -
Grupos de Resfriamento)
Parâmetro RF3 (Partida do
Analog output block 81 41 02 16-bit -
E.R.3)
Parâmetro RF4 (Partida do
Analog output block 82 41 02 16-bit -
E.R.4)
Parâmetro CV3 (Percentual de
Analog output block 83 41 02 16-bit -
Carga para E.R.3)
Parâmetro CV4 (Percentual de
Analog output block 84 41 02 16-bit -
Carga para E.R.4)
Parâmetro GR1/E.R.1 (Inscrição
Analog output block 85 41 02 16-bit - do grupo 1 no E.R.1) - 0=Não /
1=Sim
Parâmetro GR2/E.R.1 (Inscrição
Analog output block 86 41 02 16-bit - do grupo 2 no E.R.1) - 0=Não /
1=Sim
Parâmetro GR3/E.R.1 (Inscrição
Analog output block 87 41 02 16-bit - do grupo 3 no E.R.1) - 0=Não /
1=Sim
Parâmetro GR4/E.R.1 (Inscrição
Analog output block 88 41 02 16-bit - do grupo 4 no E.R.1) - 0=Não /
1=Sim
Parâmetro GR1/E.R.2 (Inscrição
Analog output block 89 41 02 16-bit - do grupo 1 no E.R.2) - 0=Não /
1=Sim
Parâmetro GR2/E.R.2 (Inscrição
Analog output block 90 41 02 16-bit - do grupo 2 no E.R.2) - 0=Não /
1=Sim
Parâmetro GR3/E.R.2 (Inscrição
Analog output block 91 41 02 16-bit - do grupo 3 no E.R.2) - 0=Não /
1=Sim
Parâmetro GR4/E.R.2 (Inscrição
Analog output block 92 41 02 16-bit - do grupo 4 no E.R.2) - 0=Não /
1=Sim
Parâmetro GR1/E.R.3 (Inscrição
Analog output block 93 41 02 16-bit - do grupo 1 no E.R.3) - 0=Não /
1=Sim
Parâmetro GR2/E.R.3 (Inscrição
Analog output block 94 41 02 16-bit - do grupo 2 no E.R.3) - 0=Não /
1=Sim

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 28


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Parâmetro GR3/E.R.3 (Inscrição
Analog output block 95 41 02 16-bit - do grupo 3 no E.R.3) - 0=Não /
1=Sim
Parâmetro GR4/E.R.3 (Inscrição
Analog output block 96 41 02 16-bit - do grupo 4 no E.R.3) - 0=Não /
1=Sim
Parâmetro GR1/E.R.4 (Inscrição
Analog output block 97 41 02 16-bit - do grupo 1 no E.R.4) - 0=Não /
1=Sim
Parâmetro GR2/E.R.4 (Inscrição
Analog output block 98 41 02 16-bit - do grupo 2 no E.R.4) - 0=Não /
1=Sim
Parâmetro GR3/E.R.4 (Inscrição
Analog output block 99 41 02 16-bit - do grupo 3 no E.R.4) - 0=Não /
1=Sim
Parâmetro GR4/E.R.4 (Inscrição
Analog output block 100 41 02 16-bit - do grupo 4 no E.R.4) - 0=Não /
1=Sim
Valor atual da Temperatura do
Analog input 0 30 04 Without flag 1x10
Óleo
Valor atual da Temperatura do
Analog input 1 30 04 Without flag 1x10
Enrolamento 1
Valor atual do Gradiente Final
Analog input 2 30 04 Without flag 1x10
Enrolamento 1 (GFN)
Valor atual da Corrente no
Analog input 3 30 04 Without flag 1x100
Enrolamento 1 (kA)
Percentual de Carga
Analog input 4 30 04 Without flag 1x10
Enrolamento 1
Corrente secundária atual no TC
Analog input 5 30 04 Without flag 1x100
do enrol. 1 (AMP)
Medição atual sensor de
Analog input 6 30 04 Without flag 1x10
temperatura A (PTA) TM1
Medição atual sensor de
Analog input 7 30 04 Without flag 1x10
temperatura B (PTB) TM1
Valor atual da Temperatura do
Analog input 8 30 04 Without flag 1x10
Enrolamento 2
Valor atual da Temperatura do
Analog input 9 30 04 Without flag 1x10
Enrolamento 3
Percentual atual de Carga
Analog input 10 30 04 Without flag 1x10
Enrolamento 2
Percentual atual de Carga
Analog input 11 30 04 Without flag 1x10
Enrolamento 3
Valor atual do Gradiente Final
Analog input 12 30 04 Without flag 1x10
Enrolamento 2(GFN)
Valor atual do Gradiente Final
Analog input 13 30 04 Without flag 1x10
Enrolamento 3 (GFN)
Valor atual da Corrente Medida
Analog input 14 30 04 Without flag 1x100
Enrolamento 2 (kA)
Valor atual da Corrente Medida
Analog input 15 30 04 Without flag 1x100
Enrolamento 3 (kA)
Corrente secundária atual no TC
Analog input 16 30 04 Without flag 1x100
do enrol. 2 (AMP)
Corrente secundária atual no TC
Analog input 17 30 04 Without flag 1x100
do enrol. 3 (AMP)

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 29


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Medição atual sensor de
Analog input 18 30 04 Without flag 1x10
temperatura A TM2 (PTA)
Medição atual sensor de
Analog input 19 30 04 Without flag 1x10
temperatura B TM2 (PTB)
Diferencial de Temperatura 1
Analog input 20 30 04 Without flag 1x10
(DT1)
Diferencial de Temperatura 2
Analog input 21 30 04 Without flag 1x10
(DT2)
Diferencial de Temperatura 3
Analog input 22 30 04 Without flag 1x10
(DT3)
Diferencial de Temperatura
Analog input 23 30 04 Without flag 1x10
Filtrado 1 (DF1)
Diferencial de Temperatura
Analog input 24 30 04 Without flag 1x10
Filtrado 2 (DF2)
Diferencial de Temperatura
Analog input 25 30 04 Without flag 1x10
Filtrado 3 (DF3)
Menor valor de Diferencial de
Analog input 26 30 04 Without flag 1x10
Temperatura 1
Menor valor de Diferencial de
Analog input 27 30 04 Without flag 1x10
Temperatura 2
Menor valor de Diferencial de
Analog input 28 30 04 Without flag 1x10
Temperatura 3
Menor valor de Diferencial de
Analog input 29 30 04 Without flag 1x10
Temperatura Filtrado 1
Menor valor de Diferencial de
Analog input 30 30 04 Without flag 1x10
Temperatura Filtrado 2
Menor valor de Diferencial de
Analog input 31 30 04 Without flag 1x10
Temperatura Filtrado 3
Maior valor de Diferencial de
Analog input 32 30 04 Without flag 1x10
Temperatura 1
Maior valor de Diferencial de
Analog input 33 30 04 Without flag 1x10
Temperatura 2
Maior valor de Diferencial de
Analog input 34 30 04 Without flag 1x10
Temperatura 3
Maior valor de Diferencial de
Analog input 35 30 04 Without flag 1x10
Temperatura Filtrado 1
Maior valor de Diferencial de
Analog input 36 30 04 Without flag 1x10
Temperatura Filtrado 2
Maior valor de Diferencial de
Analog input 37 30 04 Without flag 1x10
Temperatura Filtrado 3
Maior valor de temperatura do
Analog input 38 30 04 Without flag 1x10
comutador 1
Maior valor de temperatura do
Analog input 39 30 04 Without flag 1x10
comutador 2
Maior valor de temperatura do
Analog input 40 30 04 Without flag 1x10
comutador 3
Tempo restante p/ ajustes
Analog input 41 30 04 Without flag -
automáticos de diferenciais
Temp. do óleo do trafo p/
Analog input 42 30 04 Without flag 1x10
diferencial do Comutador
Analog input 43 30 04 Without flag 1x10 Temper. do óleo do Comutador 1
Analog input 44 30 04 Without flag 1x10 Temper. do óleo do Comutador 2
Analog input 45 30 04 Without flag 1x10 Temper. do óleo do Comutador 3

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 30


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Tempo restante p/ desligamento
Analog input 46 30 04 Without flag 1x10
por temperatura do óleo
Tempo restante p/ desligamento
Analog input 47 30 04 Without flag 1x10
por temperatura do enrol. 1
Tempo restante p/ desligamento
Analog input 48 30 04 Without flag 1x10
por temperatura do enrol. 2
Tempo restante p/ desligamento
Analog input 49 30 04 Without flag 1x10
por temperatura do enrol. 3
Estado do Relé de Alarme do
Binary input 0 01 01 No status -
Óleo*
Estado do Relé de Desligamento
Binary input 1 01 01 No status -
do Óleo*
Binary input 2 01 01 No status - Estado do Relé da R.F.1 TM1*
Binary input 3 01 01 No status - Estado do Relé da R.F.2 TM1*
Estado do Relé de Alarme do
Binary input 4 01 01 No status -
Enrolamento 1*
Estado do Relé de Desligamento
Binary input 5 01 01 No status -
do Enrolamento 1*
Estado do Relé Programável
Binary input 6 01 01 No status -
TM1*
Estado do Relé de
Binary input 7 01 01 No status -
Autodiagnóstico*
Estado do Relé de Alarme do
Binary input 8 01 01 No status -
Enrolamento 2*
Estado do Relé de Desligamento
Binary input 9 01 01 No status -
do Enrolamento 2*
Binary input 10 01 01 No status - Estado do Relé da R.F.3 TM2*
Binary input 11 01 01 No status - Estado do Relé da R.F.4 TM2*
Estado do Relé de Alarme do
Binary input 12 01 01 No status -
Enrolamento 3*
Estado do Relé de Desligamento
Binary input 13 01 01 No status -
do Enrolamento 3*
Estado do Relé Programável
Binary input 14 01 01 No status -
TM2*
Binary input 15 01 01 No status - Não Usado
Erro de comunicação entre TM1
Binary input 16 01 01 No status -
e TM2.*
Programação incorreta do
Binary input 17 01 01 No status -
parâmetro SUP*
Falha na memória EEPROM
Binary input 18 01 01 No status -
TM1*
Binary input 19 01 01 No status - Overflow nas medições TM1*
Falha na medição de
Binary input 20 01 01 No status - temperatura do óleo – mudança
brusca*
Binary input 21 01 01 No status - Falha no Conversor AD TM1*
Falha na medição da corrente de
Binary input 22 01 01 No status -
carga 1 TM1*
Binary input 23 01 01 No status - Não usado
Falha na medição de
Binary input 24 01 01 No status - temperatura do sensor A TM1
(terminal 1)*

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 31


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Falha na medição de
Binary input 25 01 01 No status - temperatura do sensor B TM1
(terminal 1)*
Falha na medição de
Binary input 26 01 01 No status - temperatura do sensor A TM1
(terminal 2)*
Falha na medição de
Binary input 27 01 01 No status - temperatura do sensor B TM1
(terminal 2)*
Falha medição temp. sensor A
Binary input 28 01 01 No status -
TM1 - mudança brusca*
Falha medição temp. sensor B
Binary input 29 01 01 No status -
TM1 - mudança brusca*
Binary input 30...31 01 01 No status - Não Usado
Erro de comunicação entre TM1
Binary input 32 01 01 No status -
e TM2*
Binary input 33 01 01 No status - Não Usado
Falha na memória EEPROM
Binary input 34 01 01 No status -
TM2*
Binary input 35 01 01 No status - Overflow nas medições TM2*
Binary input 36 01 01 No status - Não usado
Binary input 37 01 01 No status - Falha no Conversor AD TM2*
Falha na medição da corrente de
Binary input 38 01 01 No status -
carga 1 TM2*
Falha na medição da corrente de
Binary input 39 01 01 No status -
carga 2 TM2*
Falha na medição de
Binary input 40 01 01 No status - temperatura do sensor A TM2
(terminal 1)*
Falha na medição de
Binary input 41 01 01 No status - temperatura do sensor B TM2
(terminal 1)*
Falha na medição de
Binary input 42 01 01 No status - temperatura do sensor A TM2
(terminal 2)*
Falha na medição de
Binary input 43 01 01 No status - temperatura do sensor B TM2
(terminal 2)*
Falha medição temp. sensor A
Binary input 44 01 01 No status -
TM2 - mudança brusca*
Falha medição temp. sensor B
Binary input 45 01 01 No status -
TM2 - mudança brusca*
Binary input 46...47 01 01 No status - Não Usado
Binary input 48 01 01 No status - Não Usado
Binary input 49 01 01 No status - Não Usado
Atingida temperatura de
Binary input 50 01 01 No status -
desligamento do Enrolamento 1*
Atingida temperatura de
Binary input 51 01 01 No status -
desligamento do Óleo*
Binary input 52...55 01 01 No status - Não Usado
Binary input 56 01 01 No status - Não Usado

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 32


Monitor de Temperaturas
TM1 / TM2
Default Static / Event Variation
Description Index Scale Point Name
Object Var. Description
Binary input 57 01 01 No status - Não Usado
Atingida temperatura de
Binary input 58 01 01 No status -
desligamento do Enrolamento 2*
Atingida temperatura de
Binary input 59 01 01 No status -
desligamento do Enrolamento 3*
Binary input 60...63 01 01 No status - Não Usado
Binary input 64 01 01 No status - Não Usado
Alarme por Diferencial de
Binary input 65 01 01 No status -
Temperatura Instantâneo
Alarme por Diferencial de
Binary input 66 01 01 No status -
Temperatura Filtrado
Binary input 67...71 01 01 No status - Não Usado

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 33


Monitor de Temperaturas
TM1 / TM2

BRASIL
Treetech Sistemas Digitais Ltda
Praça Claudino Alves, 141, Centro
CEP 12.940-000 - Atibaia/SP
+ 55 11 2410-1190
comercial@treetech.com.br
www.treetech.com.br

REPRESENTANTES/ DISTRIBUIDORES INTERNACIONAIS

AMÉRICA DO SUL AMÉRICA DO NORTE OCEANIA

CHILE - Santiago ESTADOS UNIDOS DA AMÉRICA - Portland AUSTRÁLIA/NOVA ZELÂNDIA - Melbourne


INMOHA TechSales Martec Asset Solutions
+56 2531-7986 +1 503 345 9710 +61 (0)430 149 665
felix.morales.h@gmail.com terry@techsales-nw.com selwyn.braver@martecassetsolutions.com.au

PARAGUAI - Asunción MÉXICO - Hidalgo EUROPA


Enertec MCT
+595 21 214 814 +52 779 796 4286 PORTUGAL - Linda a Velha
paraguay@treetech.com.br jgchirino@monitoreoycontrol.com Trafotech
+351 214 146 740
PERU - Lima ÁSIA trafotech@trafotech.pt
Logytec
+511 452 3111 ÍNDIA - Raipur NORUEGA - Hokksund
ventas@logytec.com.pe Global Technology EB Elektro
+91 98261 22000 +47 31 01 37 00
COLÔMBIA - Medellín info@global-technology.in simen.andreassen@eb-elektro.no
Enersafe S.A
+57 4 604 32 72
daniel.restrepo@enersafe.com.co

Protocolos de Comunicação – TM | PC-029 | 23/07/2015 | Revisão: 2.10 34

Você também pode gostar