Você está na página 1de 2

2400

k ≔ ――= 10 P ≔ 50 kV ⋅ A V1n ≔ 2400 V V2n ≔ 240 V


240

P P
I1n ≔ ―― = 20.8 A I2n ≔ ―― = 208 A
V1n V2n

Como elevador
V1n
VT ≔ V1n + V2n = 2.64 kV Kat ≔ ―― = 0.909
VT
N1 I2n
k ≔ ―― k ≔ ―――― = 0.909
N2 I1n + I2n

Como reductor
V1n + V2n I1n + I2n
k ≔ ―――― = 1.1 k ≔ ―――― = 1.1
V1n I2n

Ien ≔ I2n Isa ≔ I2n ⋅ k = 229 A Vsa ≔ V1n

Ps P
η ≔ ――― η ≔ 98% Perd ≔ ―- P = 1.02 kW
Pe + Per η

Ps1 ≔ Isa ⋅ Vsa = 550 kW

Ps1
Pe ≔ Ien ⋅ VT = 550 kW η ≔ ―――― = 99.8%
Pe + Perd
S
S ≔ 10 kV ⋅ A V1 ≔ 2300 V V2 ≔ 230 V I1n ≔ ―― = 4.348 A
V1
S
VT ≔ V1 + V2 = 2530 V I2n ≔ ―― = 43.5 A
V2

V1 + V2
k ≔ ―――= 1.1
V1

S
Ie ≔ ―― = 43.5 A Is ≔ k ⋅ Ie = 47.8 A
V2

P ≔ Is ⋅ V2 = 11 kW