RELÉ (PEXTRON)
15 RTC (Fase/Neutro) NE 40 40
16 I partida (If>) NE 187 187
17 CURVA NE EI EI
18 DT (If> ) NE 0,3 0,3
19 I def. (If mag) NE 4001 (bloq) 4001 (bloq)
20 T def. (Dt mag) NE 240 (bloq) 240 (bloq)
21 I inst (If>>) NE 2501 2501
PARÂMETROS NEUTRO (50N/51N)
ITEM FUNÇÃO PROJETO ENCONTRADO DEIXADO
(ESTUDO SELETIVIDADE)
ATUAÇÃO DISJUNTOR
ATUAÇÃO DISJUNTOR
ATUAÇÃO DISJUNTOR
FIAÇÃO (TC P/RELÉ)
CORRENTE
MONOFÁSICO
TRIFÁSICO
TC
FUNÇÃO ABERTURA DO
DISJUNTOR
ABERTURA DO
DISJUNTOR
ABERTURA DO
DISJUNTOR
L2
FASE (L1) FASE (L2) FASE (L3)
L3
X X 280 A 17,2 s OP NR NR NR NR
28 I> NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR NR NR
29 I> NR NR NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR NR NR
X X 67,7 A 8,8 s OP NR NR NR NR
30 In > NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR
X X 86,1 A 4,9 s OP NR NR NR NR
X X 83,5 A NA NA NA NA 5,1 s OP
X X 131 A 2,1 s OP NR NR NR NR
32 In > NA NA NA NA NA NA NA NA NA
NA NA NA NA NA NA NA NA NA
ENSAIO DE MEDIÇÃO DE INJEÇÃO CORRENTE (A)
ATUAÇÃO DISJUNTOR
ATUAÇÃO DISJUNTOR
ATUAÇÃO DISJUNTOR
FIAÇÃO (TC P/RELÉ)
CORRENTE
MONOFÁSICO
TRIFÁSICO
L1 TEMPO TEMPO TEMPO
ENCONTRADO NA ENCONTRADO NA ENCONTRADO NA
ITEM
TC
FUNÇÃO ABERTURA DO
DISJUNTOR
ABERTURA DO
DISJUNTOR
ABERTURA DO
DISJUNTOR
L2
FASE (L1) FASE (L2) FASE (L3)
L3
X X 183,7 A 1,1 s OP NR NR NR NR
33 In > NA NA NA NA NA NA NA NA NA
NA NA NA NA NA NA NA NA NA
NR NR NR NR NR NR NR NR NR NR NR
34 In > NR NR NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR NR NR
35 In > NR NR NR NR NR NR NR NR NR NR NR
NR NR NR NR NR NR NR NR NR NR NR
ITEM DEFICIÊNCIAS ENCONTRADAS E AÇÕES CORRETIVAS
4 DF (não possui fonte capacitiva NBR 14039 item 5.3.4.1nota 3) AC (instalação de fonte capacitiva)
11 Não evidenciado o estudo de curto-circuito e seletividade para conferência dos parâmetros durante
a manutenção.
LEGENDA
(VE) VERIFICADO (OP) OPERACIONAL (NR) NÃO REALIZADO (NE) NÃO ENCONTRADO
(CO) COMENTÁRIO (NP) NÃO POSSUI (NA) NÃO APLICÁVEL (DF) DEFICIÊNCIA (AC) AÇÃO CORRETIVA
12,9 77,0
INSTRUMENTO DA CAIXA DE CALIBRAÇÃO DE RELÉS TCR 0100 (Electric Teste Serta)
EXECUTOR TÉCNICO PELO ENSAIOS DE MEDIÇÃO Engenheiro Eletricista Alexandre Diener
RESPONSÁVEL TÉCNICO PELA MANUTENÇÃO PREVENTIVA Rogério Santos Júnior (CREA: 178378/D/SP)