Você está na página 1de 1

QUADRO 

DE DISTRIBUIÇÃO APARTAMENTOS TIPO 02 - COM CHUVEIRO
Tensão Iluminação (W) Tomadas (W) Pot. total. Pot. total. Pot. - R Pot. - S Pot. - T Ip Seção Disj
Circuito Descrição Esquema Fases FP FCT FCA
(V) 20 30 60 100 200 400 100 300 600 815 1000 1630 4400 (VA) (W) (W) (W) (W) (A) (mm2) (A)
1 ILUMINAÇÃO F+N+T 220 14 913 840 R 840 0 0 0,92 1,0 1,0 4,2 2,5 10
2 TOMADAS SALA E QUARTOS F+N+T 220 8 2 2174 2000 S 0 2000 0 0,92 1,0 1,0 9,9 2,5 16
3 TOMADAS BANHEIROS F+N+T 220 3 1957 1800 T 0 0 1800 0,92 1,0 1,0 8,9 2,5 16
4 TOMADAS COZINHA 01 F+N+T 220 1 1 2 1739 1600 R 1600 0 0 0,92 1,0 1,0 7,9 2,5 16
5 TOMADAS COZINHA 02 F+N+T 220 1 1 2 1739 1600 S 0 1600 0 0,92 1,0 1,0 7,9 2,5 16
6 TOMADA ÁREA DE SERVIÇO F+N+T 220 1 1 1739 1600 T 0 0 1600 0,92 1,0 1,0 7,9 2,5 16
7 CHUVEIRO 01 F+N+T 220 1 4400 4400 R 4400 0 0 1,00 1,0 1,0 20,0 6,0 32
8 CHUVEIRO 02 F+N+T 220 1 4400 4400 S 0 4400 0 1,00 1,0 1,0 20,0 6,0 32
9 CHUVEIRO 03 F+N+T 220 1 4400 4400 T 0 0 4400 1,00 1,0 1,0 20,0 6,0 32
10 CHUVEIRO 04 F+N+T 220 1 4400 4400 R 4400 0 0 1,00 1,0 1,0 20,0 6,0 32
11 AR CONDICIONADO 1 F+N+T 220 1 886 815 S 0 815 0 0,92 1,0 1,0 4,0 2,5 16
12 AR CONDICIONADO 2 F+N+T 220 1 886 815 T 0 0 815 0,92 1,0 1,0 4,0 2,5 16
13 AR CONDICIONADO 3 F+N+T 220 1 886 815 R 815 0 0 0,92 1,0 1,0 4,0 2,5 16
14 AR CONDICIONADO 4 F+N+T 220 1 1772 1630 S 0 1630 0 0,92 1,0 1,0 8,1 2,5 16
TOTAL 0 0 14 0 0 0 10 2 10 1 1 0 4 28747 27855 12055 10445 8615

QD-TIP01 QUADRO DISTRIBUIÇÃO TIPO 02 3F+N+T 380 0 0 14 0 0 0 10 2 10 1 1 0 4 28747 27855 R+S+T 12055,0 10445,0 8615,0 0,95 43,56 10 50

QUADRO DE DISTRIBUIÇÃO APARTAMENTOS TIPO 02 - SEM CHUVEIRO
Tensão Iluminação (W) Tomadas (W) Pot. total. Pot. total. Pot. - R Pot. - S Pot. - T Ip Seção Disj
Circuito Descrição Esquema Fases FP FCT FCA
(V) 20 30 60 100 200 400 100 300 600 815 1000 1630 4400 (VA) (W) (W) (W) (W) (A) (mm2) (A)
1 ILUMINAÇÃO F+N+T 220 14 913 840 R 840 0 0 0,92 1,0 1,0 4,2 2,5 10
2 TOMADAS SALA E QUARTOS F+N+T 220 8 2 2174 2000 S 0 2000 0 0,92 1,0 1,0 9,9 2,5 16
3 TOMADAS BANHEIROS F+N+T 220 3 1957 1800 R 1800 0 0 0,92 1,0 1,0 8,9 2,5 16
4 TOMADAS COZINHA 01 F+N+T 220 1 1 2 1739 1600 S 0 1600 0 0,92 1,0 1,0 7,9 2,5 16
5 TOMADAS COZINHA 02 F+N+T 220 1 1 2 1739 1600 R 1600 0 0 0,92 1,0 1,0 7,9 2,5 16
6 TOMADA ÁREA DE SERVIÇO F+N+T 220 1 1 1739 1600 S 0 1600 0 0,92 1,0 1,0 7,9 2,5 16
7 CHUVEIRO 01 F+N+T 220 1 4400 4400 R 4400 0 0 1,00 1,0 1,0 20,0 6,0 32
8 CHUVEIRO 02 F+N+T 220 0 0 0 S 0 0 0 1,00 1,0 1,0 0,0 --- ---
9 CHUVEIRO 03 F+N+T 220 0 0 0 R 0 0 0 1,00 1,0 1,0 0,0 --- ---
10 CHUVEIRO 04 F+N+T 220 0 0 0 S 0 0 0 1,00 1,0 1,0 0,0 --- ---
11 AR CONDICIONADO 1 F+N+T 220 1 886 815 R 815 0 0 0,92 1,0 1,0 4,0 2,5 16
12 AR CONDICIONADO 2 F+N+T 220 1 886 815 S 0 815 0 0,92 1,0 1,0 4,0 2,5 16
13 AR CONDICIONADO 3 F+N+T 220 1 886 815 R 815 0 0 0,92 1,0 1,0 4,0 2,5 16
14 AR CONDICIONADO 4 F+N+T 220 1 1772 1630 S 0 1630 0 0,92 1,0 1,0 8,1 2,5 16
TOTAL 0 0 14 0 0 0 10 2 10 1 1 0 1 15547 14655 10270 7645 0

QD-TIP01 QUADRO DISTRIBUIÇÃO TIPO 02 2F+N+T 220 0 0 14 0 0 0 10 2 10 1 1 0 1 15547 14655 R+S 10270,0 7645,0 0,0 0,95 35,33 10 50