MANUAL PARA INSTALAÇÃO

ELÉTRICA

COMPRESSOR DE PARAFUSO AIRPOWER – 4 ~ 250HP


ROTOR, ROTOR PLUS, POWERPACK, TOTALPACK, TOTALPACK FLEX,
POWERPACK FLEX DD E TOTALPACK FLEX - DD
PRECAUÇÕES – INFORMAÇÕES GERAIS DE SEGURANÇA
ÍNDICE
INFORMAÇÕES GERAIS.....................................................................................................................3

QUADRO ELÉTRICO...........................................................................................................................3

DIMENSIONAMENTO DOS CABOS ...................................................................................................3

DIMENSIONAMENTO DOS DISJUNTORES OU FUSÍVEIS................................................................5

ATERRAMENTO...................................................................................................................................6

DIMENSIONAMENTO DO CONDUTOR NEUTRO..............................................................................7

CORREÇÃO DO FATOR DE POTÊNCIA.............................................................................................8

Rev.9 – Jan 2019


1. INFORMAÇÕES GERAIS

ESTE MANUAL IRÁ AJUDA-LO NO CORRETO DIMENSIONAMENTO E INSTALAÇÃO DA REDE


ELÉTRICA DO SEU NOVO COMPRESSOR DE PARAFUSO METALPLAN.LEIA TODO O SEU
CONTEÚDOATENTAMENTE ANTES DE INICIAR QUALQUER DÚVIDA ENTRE EM CONTATO COM O
SAC METALPLAN

Todos os compressores Metalplan são trifásicos, disponíveis nas tensões 220 / 380 / 440V 60Hz. Certifique-se sobre as
características específicas do seu equipamento através da placa de identificação e do esquema elétrico.

A instalação elétrica deverá ser executada por profissional habilitado, seguindo as recomendações da ABNT NBR 5410
Instalações elétricas de BAIXA TENSÃO disponíveis no www.abnt.org.br

A rede de distribuição de energia não deve apresentar variação de tensão superior a ± 5%, pois pode acarretar aumento
de temperatura ( sobre corrente ) e redução da vida útil do motor elétrico.

2. QUADRO ELÉTRICO
A alimentação elétrica deve servir somente ao compressor metalplan e possuir um quadro de alimentação exclusivo para
o compressor, no caso de varios compressores o quadro poderá servir a todos os compressores, porém cada
compressor deverá ter seu proprio disjuntor ou seccionadora a fusíveis.

3. DIMENSIONAMENTO DOS CABOS

O dimensionamento dos cabos deverá ser feito com base na corrente nominal do compressor conforme TABELA 1.

Deve-se prever conduto( eletrodutos;calhas;canaletas;etc..) exclusivos para o compressor. Quando não for possivel
aplicar fator de agrupamento por numero de circuitos conforme TABELA 42 ABNT NBR 5410:2004

Temperatura máxima no condutor de PVC: 70ºC


Temperatura ambiente: 40ºC
Até 3 condutores carregados classe B1
Conforme tabela 36 – ABNT NBR 5410:2004

Seção Nominal Corrente de Utilização Seção Nominal Corrente de Utilização


(mm²) (A ) 40º C A mbiente (mm²) (A ) 40º C A mbiente
2,5 18 95 180
4 24 120 208
6 31 150 239
10 44 185 273
16 59 240 322
25 77 300 371
35 96 400 444
50 117 500 511
70 149

TABELA 1

3
TABELA 2

O dimensionamento de fios e cabos ( PVC – 70ºC), para alimentação de motores trifásicos em temperatura de
ambiente de até 40ºC, instalados com condutores aéreos, não poderão ter queda de tensão > 4%.
Seguem as tabelas com os comprimentos máximos recomendados em função da corrente ( A ) e a secção do cabo
( mm² )

Cabo Corrente ( A )
mm² 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
1,5 64 32 21
2,5 104 52 35 26
4 166 83 55 42 33
6 249 124 83 62 50 41 36
10 416 208 139 104 83 69 59 52 46 42
16 657 328 219 164 131 109 94 82 73 66 60 55 51
25 1029 515 343 257 206 172 147 129 114 103 94 86 79 74 69 64 61
35 1408 704 469 352 282 235 201 176 156 141 128 117 108 101 94 88 83 78
50 1872 936 624 468 374 312 267 234 208 187 170 156 144 134 125 117 110 104
70 2627 1313 876 657 525 438 375 328 292 263 239 219 202 188 175 164 155 146
95 3520 1760 1173 880 704 587 503 440 391 352 320 293 271 251 235 220 207 196
120 4293 2146 1431 1073 859 715 613 537 477 429 390 358 330 307 286 268 253 238
150 5176 2588 1725 1294 1035 863 739 647 575 518 471 431 398 370 345 324 304 288
185 6069 3034 2023 1517 1214 1011 867 759 674 607 552 506 467 433 405 379 357 337
240 7333 3667 2444 1833 1467 1222 1048 917 815 733 667 611 564 524 489 458 431 407
300 8800 4400 2933 2200 1760 1467 1257 1100 978 880 800 733 677 629 587 550 518 489
400 10353 5176 3451 2588 2071 1725 1479 1294 1150 1035 941 863 796 739 690 647 609 575
500 11000 5500 3667 2750 2200 1833 1571 1375 1222 1100 1000 917 846 786 733 688 647 611
TABELA 3

4
Cabo Corrente ( A )
mm² 85 90 95 100 120 140 160 180 200 220 240 260 280 300 320 350 400 450
1,5
2,5
4
6
10
16
25 61
35 83 78 74
50 110 104 99 94 78
70 155 146 138 131 109 94 82
95 207 196 185 176 147 126 110 98 88
120 253 238 226 215 179 153 134 119 107 98
150 304 288 272 259 216 185 162 144 129 118 108 100
185 357 337 319 303 253 217 190 169 152 138 126 117 108 101 95
240 431 407 386 367 306 262 229 204 183 167 153 141 131 122 115 105
300 518 489 463 440 367 314 275 244 220 200 183 169 157 147 138 126 110
400 609 575 545 518 431 370 324 288 259 235 216 199 185 173 162 148 129 115
500 647 611 579 550 458 393 344 306 275 250 229 212 196 183 172 157 138 122
TABELA 4

4. DIMENSIONAMENTO DOS DISJUNTORES OU FUSÍVEIS


Deverá ser instalado um disjuntor ou seccionadora a fusiveis na entrada dos compressores. Em caso de máquinas flex
deve ser instalado obrigatóriamente os fusiveis indicados na tabela 5, os demais equipamentos seguem o padrão da
tabela 6.

FUSÍVEIS ULTRA FUSÍVEIS ULTRA


BASE FUSIVEIS CHAVE SECCIONADORA BASE FUSIVEIS CHAVE SECCIONADORA
EQUIPAMENTO TENSÃO (V) I máx (A) RÁPIDOS SIEMENS EQUIPAMENTO TENSÃO (V) I máx (A) RÁPIDOS SIEMENS
SIEMENS SIEMENS ERGONFUSE SIEMENS SIEMENS ERGONFUSE
SITOR SITOR

POWER PACK 220 33 3NE1 802-0 (40A) 3NH3 030-C ERGONFUSE-160 POWERPACK 220 157 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250
TOTAL PACK 380 19 3NE1 815-0 (25A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 91 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160
FLEX 10 HP 440 16 3NE1 814-0 (20A) 3NH3 030-C ERGONFUSE-160 50 HP – DD 440 80 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160

POWER PACK 220 48 3NE1 817-0 (50A) 3NH3 030-C ERGONFUSE-160 POWERPACK 220 192 3NE1 225-0 (200A) 3NH3 230-3YB ERGONFUSE-250
TOTAL PACK 380 28 3NE1 803-0 (35A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 110 3NE1 022-0 (125A) 3NH3 030-C ERGONFUSE-160
FLEX 15 HP 440 24 3NE1 803-0 (35A) 3NH3 030-C ERGONFUSE-160 60 HP – DD 440 95 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160

POWER PACK 220 81 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160 POWERPACK --- --- --- --- ---
TOTAL PACK 380 47 3NE1 817-0 (50A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 138 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250
FLEX 25 HP 440 40 3NE1 817-0 (50A) 3NH3 030-C ERGONFUSE-160 75 HP – DD 440 120 3NE1 022-0 (125A) 3NH3 030-C ERGONFUSE-160

POWER PACK 220 93 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160 POWERPACK --- --- --- --- ---
TOTAL PACK 380 54 3NE1 818-0 (63A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 176 3NE1 225-0 (200A) 3NH3 230-3YB ERGONFUSE-250
FLEX 30 HP 440 46 3NE1 817-0 (50A) 3NH3 030-C ERGONFUSE-160 100 HP – DD 440 152 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250

POWER PACK 220 128 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250 POWERPACK --- --- --- --- ---
TOTAL PACK 380 73 3NE1 820-0 (80A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 255 3NE1 230-0 (315A) 3NH3 330-3YB ERGONFUSE-400
FLEX 40 HP 440 64 3NE1 820-0(80A) 3NH3 030-C ERGONFUSE-160 125 HP – DD 440 220 3NE1 227-0 (250A) 3NH3 230-3YB ERGONFUSE-250

POWER PACK 220 157 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250 POWERPACK --- --- --- --- ---
TOTAL PACK 380 90 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 265 3NE1 230-0 (315A) 3NH3 330-3YB ERGONFUSE-400
FLEX 50 HP 440 78 3NE1 820-0 (80A) 3NH3 030-C ERGONFUSE-160 150 HP – DD 440 229 3NE1 227-0 (250A) 3NH3 230-3YB ERGONFUSE-250

POWER PACK 220 --- --- --- --- POWERPACK --- --- --- --- ---
TOTAL PACK 380 105 3NE1 022-0 (125A) 3NH3 030-C ERGONFUSE-160 TOTALPACK FLEX 380 423 3NE1 333-0 (450A) 3NH3 430-3YB ERGONFUSE-630
FLEX 60 HP 440 91 3NE1 021-0 (100A) 3NH3 030-C ERGONFUSE-160 200 HP – DD 440 367 3NE1 332-0 (400A) 3NH3 330-3YB ERGONFUSE-400

POWER PACK 220 --- --- --- --- POWERPACK --- --- --- --- ---
TOTAL PACK 380 127 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250 TOTALPACK FLEX 380 431 3NE1 333-0 (450A) 3NH3 430-3YB ERGONFUSE-630
FLEX 75 HP 440 110 3NE1 022-0 (125A) 3NH3 030-C ERGONFUSE-160 250 HP – DD 440 374 3NE1 332-0 (400A) 3NH3 330-3YB ERGONFUSE-400

POWER PACK 220 --- --- --- ---


TOTAL PACK 380 170 3NE1 225-0 (200A) 3NH3 230-3YB ERGONFUSE-250
FLEX 100 HP 440 147 3NE1 224-0 (160A) 3NH3 230-3YB ERGONFUSE-250

TABELA 5

5
DISJUNTOR FUSIVEIS NH FUSIVEIS NH
TENSÃO I máx I máx
EQUIPAMENTO PADRÃO IEC 60898 DISJUNTOR WEG RETARDADO 500V EQUIPAMENTOTENSÃO (V DISJUNTOR WEG DISJUNTOR SIEMENS RETARDADO 500V
(V) (A) (A)
(CURVA C) SIEMENS OU SIMILAR SIEMENS OU SIMILAR

*220 24 32 --- 25 A TOTALPACK 220 32 DWB160N32-3MF 3VL27 06-1AP33-0AA0 35 A


ROTOR PLUS
220 15,5 20 --- 20 A POWERPACK 10 380 19 DWB160N25-3MF 3VL27 06-1AP33-0AA0 20 A
4 HP
380 9 16 --- 16 A HP 440 16 DWB160N25-3MF 3VL27 06-1AP33-0AA0 20 A

220 26 32 DWB160N32-3MF 35 A TOTALPACK 220 45 DWB160N50-3MF 3VL27 06-1AP33-0AA0 50 A


ROTOR PLUS
380 15 20 DWB160N25-3MF 16 A POWERPACK 15 380 26 DWB160N32-3MF 3VL27 06-1AP33-0AA0 35 A
6 HP
440 --- --- --- --- HP 440 23 DWB160N32-3MF 3VL27 06-1AP33-0AA0 25 A

220 30 40 DWB160N32-3MF 35 A TOTALPACK 220 79 DWB160N80-3MF 3VL27 10-1AP33-0AA0 80 A


ROTOR PLUS
380 18 20 DWB160N25-3MF 20 A POWERPACK 25 380 46 DWB160N50-3MF 3VL27 06-1AP33-0AA0 50 A
10 HP
440 15 20 DWB160N25-3MF 16 A HP 440 40 DWB160N40-3MF 3VL27 06-1AP33-0AA0 50 A

220 44 50 DWB160N50-3MF 50 A TOTALPACK 220 90 DWB160N95-3MF 3VL27 16-1AP33-0AA0 100 A


ROTOR PLUS
380 25 32 DWB160N25-3MF 25 A POWERPACK 30 380 53 DWB160N65-3MF 3VL27 10-1AP33-0AA0 63 A
15 HP
440 22 25 DWB160N25-3MF 25 A HP 440 45 DWB160N50-3MF 3VL27 06-1AP33-0AA0 50 A

220 51 63 DWB160N63-3MF 63 A TOTALPACK 220 124 DWB250N150-3MF 3VL27 16-1AP33-0AA0 125 A


ROTOR PLUS
380 30 40 DWB160N40-3MF 35 A POWERPACK 40 380 72 DWB160N80-3MF 3VL27 10-1AP33-0AA0 80 A
20HP
440 26 32 DWB160N32-3MF 35 A HP 440 63 DWB160N65-3MF 3VL27 10-1AP33-0AA0 63 A

220 71 80 DWB160N80-3MF 80 A TOTALPACK 220 152 DWB250N150-3MF 3VL37 20-1AP36-0AA0 160 A


ROTOR PLUS
380 41 50 DWB160N50-3MF 50 A POWERPACK 50 380 88 DWB160N95-3MF 3VL27 16-1AP33-0AA0 100 A
25HP
440 36 40 DWB160N40-3MF 50 A HP 440 76 DWB160N80-3MF 3VL27 10-1AP33-0AA0 80 A

* ROTOR 4 HP 220v MONOFÁSICO TOTALPACK 220 179 DWB250N185-3MF 3VL37 25-1AP36-0AA0 200 A
POWERPACK 60 380 104 DWB250N105-3MF 3VL27 16-1AP33-0AA0 125 A
HP 440 90 DWB160N95-3MF 3VL27 16-1AP33-0AA0 100 A

TOTALPACK 220 216 DWM400H-250-3 3VL47 31-1AP36-0AA0 224 A


POWERPACK 75 380 125 DWB250N150-3MF 3VL37 20-1AP36-0AA0 125 A
HP 440 108 DWB250N150-3MF 3VL37 20-1AP36-0AA0 125 A

TOTALPACK 220 289 DWM400H-320-3 3VL47 31-1AP36-0AA0 315 A


POWERPACK 380 168 DWB250N185-3MF 3VL37 25-1AP36-0AA0 200 A
100 HP 440 145 DWB250N185-3MF 3VL37 25-1AP36-0AA0 160 A

TOTALPACK 220 361 DWM800H-420-3 3VL57 50-1AP36-0AA0 400 A


POWERPACK 380 209 DWM400H-250-3 3VL47 31-1AP36-0AA0 224 A
125 HP 440 181 DWB250N200-3MF 3VL47 31-1AP36-0AA0 200 A

TOTALPACK 220 448 DWM800H-500-3 3VL57 50-1AP36-0AA0 500 A


POWERPACK 380 260 DWM400H-320-3 3VL47 31-1AP36-0AA0 315 A
150 HP 440 224 DWM400H-250-3 3VL47 31-1AP36-0AA0 225 A

TOTALPACK 220 - - - -
POWERPACK 380 415 DWM800H-500-3 3VL57 50-1AP36-0AA0 450 A
200 HP 440 359 DWM800H-420-3 3VL57 50-1AP36-0AA0 400 A

TOTALPACK 220 - - - -
POWERPACK 380 423 DWM800H-500-3 3VL57 50-1AP36-0AA0 450 A
250 HP 440 365 DWM800H-420-3 3VL57 50-1AP36-0AA0 400 A

TABELA 6

5. ATERRAMENTO

Providencie aterramento exclusivo para os compressores, conforme esquema TT da norma ABNT NBR 5410:2004, com
resistência menor ou igual a 5Ω, dimensionado de acordo com a potência instalada. No caso de existir mais e um
compressor, o mesmo aterramento pode ser usado, desde que condutores independentes sejam usados para a ligação.
O aterramento deve ser o mais proximo possível do compressor

6
ATERRAMENTO EM SÉRIE (NUNCA FAÇA ESTE TIPO DE ATERRAMENTO)

REGRA GERAL PARA DIMENSIONAMENTO DOS CONDUTORES DE ATERRAMENTO

6. DIMENSIONAMENTO DO CONDUTOR NEUTRO

Utilizado nos modelos 380V para alimentação do comando 220V monofásico ( fase + neutro ), atentar para as seguintes
situações:

Seção reduzida do • O condutor neutro não pode ser comum a mais de um circuito
Seção dos condutores
condutor neutro
de fase mm²
mm² • O condutor neutro de um circuito monofásico deve ter a mesma
S < 25 S seção do condutor fase.
35 25
50 25 • Seção reduzida do condutor neutro
70 35
95 50
120 70
150 70
185 95
240 120
300 150
400 185
TABELA 7

7
7. CORREÇÃO DO FATOR DE POTÊNCIA

É recomendável corrigir o fator de potência para dar maior disponibilidade de potência ativa e aproveitamento da rede
elétrica. O aumento do fator de potência é realizado com a ligação de uma carga capacitiva em paralelo com a carga. O
dimensionamento dos capacitores bem como sua instalação, deverá ser realizado por um profissional habilitado. Abaixo,
segue um exemplo de ligação elétrica para os capacitores e seus fusíveis de proteção.