Escolar Documentos
Profissional Documentos
Cultura Documentos
© SA-T Training
1MRG005481
Seção 10
Conteúdo
SMBRREC - Religamento
Principais sinais para o disparo
Principais sinais para o intertravamento
Ajustes de Religamento
© SA-T Training
1MRG005481
Slide 2
Seção 10
SMBRREC - Religamento
© SA-T Training
1MRG005481
Slide 3
Seção 10
Os diferentes programas de Religamento
© SA-T Training
1MRG005481
Slide 4
Seção 10
Religamento – Principais sinais para o disparo
On/Off se o Religamento for ajustado para controle externo
© SA-T Training
1MRG005481
Slide 5
Seção 10
SMBRREC Religamento
Lógica de partida/restrição
Sinais de restrição17-32
© SA-T Training
1MRG005481
Slide 6
Seção 10
SMBRREC – Ajustes de partida do religamento
Operação
Off/External Controlled/On
StartByCBOpen Off/On
Se em On, lembre-se que a abertura manual
do CB precisa inibir o AR
CBAuxContType
Normally Open/Normally Closed
Ajustes de tempo morto para 5 shots t1-t5
tReclaim
Define o ciclo de AR
Novo Start (START ou TRSOTF) depois de
um comando “fechar” (do último shot) dentro
do tempo de recuperação A/R mal sucedido
tInhibit
Tempo de reset para restrição/inibição
tTrip
Duração máxima do “pulso para fechar”
CutPulse On/Off
Novo start de AR reseta o “pulso para fechar”
tPulse
Duração do “pulso para fechar”
© SA-T Training
1MRG005481
Slide 7
Seção 10
Sinais de intertravamento para o Religamento
© SA-T Training
1MRG005481
Slide 8
Seção 10
Sinais de intertravamento para o Religamento
© SA-T Training
1MRG005481
Slide 9
Seção 10
Sinais de intertravamento para o Religamento
CBReadyType
CO (Close Open) or OCO (Open Close
Open)
If CO, A/R checks that CB is ready before
issuing the CB CLOSE command.
If OCO, A/R checks that CB is ready when the
START signal is received.
tSync
Max waiting time for SC OK
Follow CB Off/On
If On, continue to next shot if CB is closed
during dead time
tCBCloseMin
Minimum time that CB must be closed
before new sequence is allowed
AutoCont Off/On
If On, Continue to next shot if CB did not
close within set tAutoContWait
tAutoContWait
Wait time after close command, before
continue to next shot
© SA-T Training
1MRG005481
Slide 10
Seção 10
SMBRREC – Ajustes de Religamento
Extended t1 Off/On
If On, the dead time is extended with tExtended t1
at active PLCLOST input
UnsucClByCBChk
NoCBCheck or CBCheck
Unsuccessful closing signal obtained by checking CB
position
BlockByUnsucCl Off/On
If On, Blocks AR at unsuccessful CB closing
tUnsucCl
Waiting time to indicate unsuccessful CB closing
Priority
None/Low/High
tWaitForMaster
Max time to wait for the release from the master
ZoneSeqCoord Off/On
If On, Coordination of down stream devices to
local protection units AR
© SA-T Training
1MRG005481
Slide 11
Seção 10
SMBRREC – Ajustes de Religamento
UnsucClByCBChk
NoCBCheck or CBCheck
Unsuccessful closing signal obtained by checking
CB position
BlockByUnsucCl
Off/On
If On, Blocks AR at unsuccessful CB closing
tUnsucCl
Waiting time to indicate unsuccessful CB closing
Priority
None/Low/High
tWaitForMaster
Max time to wait for the release from the master
ZoneSeqCoord
Off/On
If On, Coordination of down stream devices to local
protection units AR
© SA-T Training
1MRG005481
Slide 12
Seção 10
SMBRREC - Religamento Mestre-Escravo A/R
O disjuntor MESTRE é fechado
primeiro, e se o religamento é bem
sucediso, então o segundo
disjuntor (ESCRAVO) é fechado.
Único disjuntor na
configuração
Um disjuntor pode permanecer com todas as fases abertas, mas nunca somente uma!
O A/R deve comandar e preparar Trip trifásico através da entrada P3PTR!
© SA-T Training
1MRG005481
Slide 14
Seção 10
Religamento
Exercício 9
© SA-T Training
1MRG005481
Slide 15
Seção 10
© SA-T Training
1MRG005481
Slide 16