1200 SIMBOLOGIA - ILUMINAÇÃO E TOMADAS: SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:

SÍMBOLO DESCRIÇÃO SÍMBOLO

LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C", COM TAMPA. (DIMENSÕES: 150x100mm).
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM
PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO ELETRODUTO LEVE EM AÇO GALVANIZADO ELETROLITICAMENTE, DO TIPO LEVE, INSTALAÇÃO APARENTE NO
ENTREFORRO, Ø3/4" OU CONFORME INDICAÇÃO EM PLANTA.

250
ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA
DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-32W, DA ITAIM ELETRODUTO EM PVC RÍGIDO EMBUTIDO NO TETO, PAREDE OU NO PISO, Ø3/4" OU CONFORME INDICAÇÃO EM
(FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE PLANTA.
DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
BOTOEIRA SIMPLES PARA ACIONAMENTO DE SISTEMA DE ALARME PPNE, FORNECIDO COM TAMPA, A 30cm DO PISO
ACABADO, 10A/250V.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM QUADRO ELÉTRICO PARA DISTRIBUIÇÃO DE CIRCUITOS (QDC).
PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO
MONTANTE ESTRUTURAL ELETROCALHA METÁLICA ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE (OU CONFORME INDICAÇÃO) INSTALADA
(PERFIL C)
A
PERFURADA COM VIROLA DO DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-16W, DA ITAIM A 30cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS. PARÂMETROS GERAIS DE PROJETO:
TIPO "C" COM TAMPA (VER AS (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE
GRAMPO "C" PARA CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE (OU CONFORME INDICAÇÃO) INSTALADA
DIMENSÕES EM PROJETO) DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
SUSTENTAÇÃO DA A 220cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
ELETROCALHA PERFILADO PERFURADO 1 - SISTEMA EM BAIXA TENSÃO TRIFÁSICO 220/127V - 60Hz - Icc MÍNIMO DE 5,0kA.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE - TIPOS C, E, T, TB, L, X e ED, RESPECTIVAMENTE.
TIRANTE ROSCA TOTAL Ø1/4" 38x19mm PARA SUSTENTAÇÃO
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM 2 - A ILUMINÂNCIA MÉDIA DOS AMBIENTES DA EDIFICAÇÃO FORAM DETERMINADAS CONFORME RECOMENDADO
DA ELETROCALHA
ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À PELA NBR-5413:1992.
VISTA EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO PAREDE, INSTALADA A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-32W, DA ITAIM (FORNECIDA COMPLETA, COM 2 3 - ESQUEMA DE ATERRAMENTO ADOTADO: TN-S.
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À
QUE 10%). PAREDE, INSTALADA A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO. 4 - EM RELAÇÃO AS PRESCRIÇÕES DE PROTEÇÃO CONTRA INCÊNDIO, A EDIFICAÇÃO FOI CLASSIFICADA COMO
BD-3 (TUMULTUADA).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À
GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM PAREDE, INSTALADA A 220,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO. 5 - TEMPERATURAS CONSIDERADAS EM PROJETO:
ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. - TEMPERATURA AMBIENTE: 30°C;
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
250

EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO - TEMPERATURA NO SOLO: 20°C.
SOBREPOSTO À PAREDE, INSTALADAS A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU
CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-16W, DA ITAIM (FORNECIDA COMPLETA, COM 2
COMO INDICADO. 6 - LIMITE MÁXIMO DE QUEDA DE TENSÃO ADMITIDA:
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR
50

QUE 10%). UMA TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA METÁLICA - 7% CALCULADO A PARTIR DOS TERMINAIS SECUNDÁRIOS DO TRANSFORMADOR MT/BT ATÉ O PONTO DE
DO TIPO CONDULETE SIMPLES SOBREPOSTO À PAREDE A 15cm ACIMA DA PORTA DOS BANHEIROS PPNE (REF.: UTILIZAÇÃO.
LUMINÁRIA RETANGULAR DE SOBREPOR TIPO ARANDELA PARA 1 LÂMPADA FLUORESCENTE COMPACTA DE 23W. SILENTOQUE DA LEGRAND), POTÊNCIA 50W, PARA O SISTEMA DE SINALIZAÇÃO DE EMERGÊNCIA PPNE.
MONTANTE ESTRUTURAL INSTALADA A 220cm DO PISO ACABADO OU CONFORME INDICAÇÃO EM PLANTA. CORPO EM CHAPA DE AÇO 7 - NORMAS APLICÁVEIS:
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
(PERFIL C) TRATADA COM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM VIDRO PLANO TEMPERADO - ELETRODUTOS DE AÇO GALVANIZADO ELETROLÍTICO: ABNT NBR 13.057;
MONTANTE ESTRUTURAL SOBREPOSTO À PAREDE, INSTALADAS A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU
JATEADO. REF.: MOD.: OLIVINO 1xTC-TSE-23W DA ITAIM, FORNECIDA COM 1 LÂMPADA FLUORESCENTE COMPACTA - ELETRODUTOS DE PVC RÍGIDO: ABNT NBR 15.465;
(PERFIL C) GRAMPO "C" PARA COMO INDICADO.
DE 23W-220V. - CONDUTORES DE COBRE 70°C 750V OU 0,6/1kV, NÃO-PROPAGANTES DE CHAMA, LIVRES DE HALOGÊNIO E
GRAMPO "C" PARA SUSTENTAÇÃO DA
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" INSTALADA DIRETAMENTE NO FORRO DO COM BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS: ABNT NBR 13.248;
ELETROCALHA
SUSTENTAÇÃO DA MÍNIMO 30cm CAIXA DE LIGAÇÃO OU PASSAGEM REDONDA PARA UTILIZAÇÃO EM ÁREA COBERTA APARENTE. REF.: DAILET TETO ACABADO (REF.: PIALPLUS, DA LEGRAND), TENSÃO DE 127V - POTÊNCIA 100VA OU CONFORME INDICAÇÃO. - INTERRUPTORES PARA INSTALAÇÕES ELÉTRICAS FIXAS DOMÉSTICAS E ANÁLOGAS: ABNT NBR NM 60.669-1;
ELETROCALHA PERFILADO PERFURADO
TIRANTE ROSCA TOTAL Ø1/4" MÚLTIPLO REDONDA DA DAISA. - PLUGUES E TOMADAS PARA USO DOMÉSTICO E ANÁLOGO ATÉ 20A/250V EM CORRENTE ALTERNADA: ABNT
38x19mm PARA SUSTENTAÇÃO
TIRANTE ROSCA TOTAL Ø1/4" CAIXA DE DERIVAÇÃO PARA ELETRODUTOS COM LUVA ROSQUEADA EM PVC 2". (DIM.: 100X100X50mm) REF.: MEGA NBR 14.136;
DA ELETROCALHA
ABRAÇADEIRA DO TIPO "D" UM INTERRUPTOR BIPOLAR SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO À - DISJUNTORES TERMINAIS ATÉ 125A (MINI-DISJUNTORES): ABNT NBR IEC 60.947-2;
ELETROCALHA METÁLICA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. - DISJUNTORES ACIMA DE 125A (CAIXA MOLDADA): ABNT NBR IEC 60.947-2;
ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EMCAIXA METÁLICA DO TIPO - DISJUNTORES PADRÃO CEMIG: NEMA (CONFORME HOMOLOGAÇÃO);
ELETRODUTO DE AÇO
PERFURADA COM VIROLA DO TIPO "C" COM TAMPA (VER AS CONDULETE SIMPLES SOBREPOSTO À PAREDE, INSTALADA A 250,0cm DO PISO ACABADO OU CONFORME - DISPOSITIVOS DIFERENCIAL RESIDUAL (DR): ABNT NBR NM 61.008;
GALVANIZADO
TIPO "C" COM TAMPA (VER AS DIMENSÕES EM PROJETO) DOIS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO INDICAÇÃO (REF.: SILENTOQUE DA LEGRAND ). POTÊNCIA 25VA, PARA ATENDIMENTO AO BLOCO AUTÔNOMO. - DISPOSITIVOS PROTETORES DE SURTOS (DPS): NBR IEC 61.643-1;
DIMENSÕES EM PROJETO) PASSAGEM DOS CABOS DE SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. - DUTOS CORRUGADOS DE POLIETILENO (PE) PARA INFRAESTRUTURAS DE ENERGIA E TELECOMUNICAÇÕES
PASSAGEM DOS CABOS DE ILUMINAÇÃO E TOMADAS FIXAÇÃO DO ELETRODUTO NO TETO TRÊS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO
(PEAD): ABNT NBR 15.715;
TELECOMUNICAÇÕES PERCURSO DE CABOS QUE SOBE, QUE PASSA E QUE DESCE EM NÍVEL. INDICAÇÃO EM PLANTA. - CONTATORES MODULARES PARA ILUMINAÇÃO: IEC 61.095;
SUPORTAR A CADA 1,20m SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
- BLOCOS AUTÔNOMOS PARA ILUMINAÇÃO DE EMERGÊNCIA: ABNT NBR 10.898;
SEM ESCALA
CORTE A-A - QUADROS ELÉTRICOS: ABNT NBR IEC 60.439-1.
UM INTERRUPTOR BIPOLAR PARALELO, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES SOBREPOSTO CAIXA DE PASSAGEM 15x15cm (OU CONFORME INDICAÇÃO) COM TAMPA REVERSÍVEL. CONSTRUÍDA EM LIGA DE
À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. ALUMÍNIO SILÍCIO, FUNDIDA EM MOLDE PERMANENTE, DE BOM ACABAMENTO, ALTA RESISTÊNCIA MECÂNICA E À
FIXAÇÃO DE ELETROCALHA PROVA CORROSÃO. TAMPA LISA FIXADA POR PARAFUSOS DE AÇO GALVANIZADO, DOTADAS DE JUNTA DE
DOIS INTERRUPTORES BIPOLARES PARALELOS, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE DUPLO VEDAÇÃO. INSTALADA A 30cm DO PISO ACABADO OU CONFORME INDICAÇÃO. REF.: CP-1515-10 DA WETZEL. NOTAS:
FIXAR A CADA 1,20m
SEM ESCALA SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND. 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70°C DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
750V OU CONFORME INDICAÇÃO EM PLANTA. CLASSE 5 DE ENCORDOAMENTO - NEUTRO, FASE, RETORNO SIMPLES,
UM INTERRUPTOR INTERMEDIÁRIO SIMPLES, 10A/250V EM CAIXA METÁLICA DO TIPO CONDULETE SIMPLES
MONTANTE ESTRUTURAL GRAMPO "C" FIXADO NO MONTANTE RETORNO PARALELO E TERRA, RESPECTIVAMENTE - #2,5mm² OU CONFORME INDICAÇÃO EM PLANTA. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
SOBREPOSTO À PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
(PERFIL C) ESTRUTURAL DA LAJE SECA PARA
PASSAGEM DO CABO DE AÇO QUE 3-CONFERIR MEDIDAS NO LOCAL.
SUSTENTA A LUMINÁRIA
4-COTAS EM CENTÍMETROS.
5-OS COMPONENTES E MATERIAIS ESPECIFICADOS NESTE PROJETO SÃO REFERÊNCIAS, E PODERÃO SER
SUBSTITUÍDOS POR EQUIVALENTES TÉCNICOS (APRESENTAR PROTÓTIPO PARA APROVAÇÃO POR PARTE DA
NOTAS GERAIS: FISCALIZAÇÃO DE OBRAS).

UNIDUT METÁLICO 1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO. SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
2 - CONSIDERAR AS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
ELETRODUTO DE AÇO ELETRODUTO DE
GALVANIZADO - PASSAGEM AÇO GALVANIZADO DIRETORIA DE INFRAESTRUTURA FÍSICA
DOS CIRCUITOS DE FORRO 3 - AS ELEVAÇÕES INDICADAS TÊM COMO REFERÊNCIA O PISO ACABADO.
ILUMINAÇÃO E TOMADAS ABRAÇADEIRA DO
ELETROCALHA DE ELETRODUTO DE
TIPO "D" 4 - AS TOMADAS INDICADAS EM 220V DEVERÃO SER VERMELHAS DE FÁBRICA, DIFERENTEMENTE DAS TOMADAS PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
INFRAESTRUTURA P/ AÇO GALVANIZADO PROJETO DE ACORDO COM RDC-50/2002 E
CONVENCIONAIS 127V, E ALÉM DISSO DEVERÃO RECEBER MARCAÇÃO INDELÉVEL COM OS DIZERES "220V", CONFORME
ELÉTRICA OU CURVA 90° DE CONDULETE DO DETALHE APRESENTADO NESTE PROJETO. RESOLUÇÃO 1797/09 DA SES-MG
TELECOMUNICAÇÕES AÇO GALVANIZADO TIPO "C" OU "E"
GRAMPO "C" FIXADO NO MONTANTE PLUGUE PADRÃO BRASILEIRO
PARA TOMADAS
5 - TODOS OS CABOS TERMINAIS SERÃO DO TIPO CLASSE 5 DE ENCORDOAMENTO E TERÃO ISOLAMENTO EM DUPLA CAMADA É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
ESTRUTURAL DA LAJE SECA PARA SUPORTE DO ALTAS
ELETRODUTO (VER DETALHE) ELETRODUTO DE
POLIOLEFÍNICO NÃO HALOGENADO 70°C 750V EXCETO EM LOCAIS SUJEITO À UMIDADE, COMO TUBULAÇÕES ENTERRADAS COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
NO SOLO, QUE DEVERÃO SER DO TIPO 0,6/1kV.
AÇO GALVANIZADO
CABO DE AÇO GALVANIZADO Ø1/8" PARA CABO TRIPOLAR 0,6/1,0kV 3#1,5mm² EM HEPR
6 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CIRCUITOS) EM TODAS AS CAIXAS, CAIXAS DE
SUPORTE DA LUMINÁRIA 90°C (LIVRE DE HALÓGENOS) PARA A LIGAÇÃO
PASSAGEM E/OU CONDULETES.
DA LUMINÁRIA
06 REVISÃO DETALHAMENTO 14/10/2013 VIABILE
ABRAÇADEIRA DO
7 - TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA INSTALAÇÃO, DEVEM GARANTIR
TIPO "D"
CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE E PROTEÇÃO MECÂNICA.
FORRO (TETO) BASE CONECTORA 05 REVISÃO DETALHAMENTO 26/09/2013 VIABILE
LUMINÁRIA EMBUTIDA EM CONDULETE DO
FORRO TIPO "C" OU "E" 8 - EM TODAS AS DERIVAÇÕES UTILIZAR CAIXA DE PASSAGEM DO TIPO CONDULETE METÁLICO MÚLTIPLO.

2200
REATOR ELETRÔNICO DE ALTO PARA TOMADAS 04 01/02/2013 VIABILE
CONDULETE EQUIPADO COM 9 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, EVITANDO-SE ADEQUAÇÃO DA ARQUITETURA CONFORME VISA
FATOR DE POTÊNCIA MÉDIAS E
TOMADA PADRÃO BRASILEIRO TOMADAS 2P+T 20A 250V TOMADAS 2P+T 20A 250V TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
INTERRUPTORES
PARA LIGAÇÃO DA LUMINÁRIA CONFORME NBR 14.136/2002 CONFORME NBR 14.136/2002
EM CONDULETE DUPLO EM CONDULETE SIMPLES 03 EMISSÃO FINAL 08/11/2012 VIABILE
ELETRODUTO DE 10 - NAS INTERLIGAÇÕES DOS ELETRODUTOS METÁLICOS COM AS ELETROCALHAS, UTILIZAR BUCHA E ARRUELA.
AÇO GALVANIZADO
FIXAÇÃO DAS LUMINÁRIAS DE EMBUTIR 11 - SONDAR OS ELETRODUTOS COM CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA CAIXA PARA A PASSAGEM

1100
ABRAÇADEIRA DO 02 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 29/10/2012 VIABILE
DE CABOS.
SEM ESCALA PAREDE SECA "DRY WALL" TIPO "D"

BUCHA S6 PARA PAREDE SECA


TOMADAS PARA USO GERAL CONDULETE DO
12 - TODOS OS ELETRODUTOS EM PVC DEVERÃO OBEDECER À NBR 15.465. NÃO SERÃO ACEITOS PRODUTOS IDENTIFICADOS
COMO "MANGUEIRAS".
01 REVISÃO DA ARQUITETURA 18/10/2012 VIABILE

SEM ESCALA TIPO "E" PARA

300
"DRY WALL"
TOMADAS BAIXAS 13 - NOS TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO, 00 EMISSÃO INICIAL 27/09/2012 VIABILE
PAREDE DA ELETROCALHA ELETRODUTO PARAFUSO CABEÇA REDONDA ENTREFORRO OU ENTREPISO) DEVERÃO SER UTILIZADOS ELETRODUTOS LEVES DE AÇO GALVANIZADO ELETROLITICAMENTE
ROSCA SOBERBA S6 CONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO. PARA INSTALAÇÕES REVISÃO OBJETO DATA VERIFICAÇÃO
BUCHA ARRUELA EXTERNAS, UTILIZAR ELETRODUTOS DE AÇO GALVANIZADO A FOGO DO TIPO PESADO CONFORME NBR 5.624. GERENCIAMENTO E PROJETO:
ABRAÇADEIRA DO TIPO "D" CORTE ESQUEMÁTICO - INSTALAÇÃO APARENTE 14 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO (INCLUSIVE LUMINÁRIAS) ATRAVÉS DO Av. Augusto de Lima, nº655
APARAFUSÁVEL
ELETRODUTO DE AÇO ELETRODUTO DE AÇO
ELETROCALHA GALVANIZADO SOBRE GALVANIZADO SOBRE A DOS COMPONENTES CABO DE PROTEÇÃO Pe (CABO VERDE DOS CIRCUITOS, TERRA) MAIS PRÓXIMO. conj. 418 - Centro - BH
Telefax: (31) 3324-2702
A PAREDE PAREDE 15 - UM MESMO CABO DE PROTEÇÃO (TERRA) PODERÁ SER COMUM A VÁRIOS CIRCUITOS, DESDE QUE SUA BITOLA SEJA http://www.viabile.com.br
METÁLICA MÍNIMO SEM ESCALA
PERFURADA COM viabile@viabile.com.br
15 cm IDÊNTICA AO CABO FASE DE MAIOR SEÇÃO CONTIDO EM UM CONDUTO/NICHO DE ELETROCALHA.
VIROLA DO TIPO "C" BUCHA E ARRUELA
COM TAMPA 16 - ONDE EXISTIR FORRO E/OU PISO ELEVADO, AS ELETROCALHAS DE PASSAGEM DOS CABOS ELÉTRICOS DEVERÃO SER
DESENVOLVIMENTO: DATA:
INSTALADAS SOBRE O FORRO OU ABAIXO DO PISO ELEVADO. ESTAS DEVERÃO SER DE USO EXCLUSIVO PARA OS SISTEMA
ELETRODUTO DE BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
ELÉTRICO E DEVERÃO ESTAR DISTANTES PELO MENOS 30cm DAS ELETROCALHAS QUE CONTENHAM CABOS DE
AÇO GALVANIZADO PROJEÇÃO DO CONDULETE EM
CONDULETE CONDULETE METÁLICO TELECOMUNICAÇÕES. NOME DO ARQUIVO CAD: ESCALA: UNIDADE:
ELETROLITICAMENTE RELAÇÃO À PAREDE
ELETRODUTO DE METÁLICO DUPLO DUPLO PARA TOMADAS INDICADA
AÇO GALVANIZADO (OBSERVAÇÃO: INSTALAR 460-UBSSS-R06-ELE-01-PE-T1T.DWG MILÍMETROS
PARA TOMADAS DE ELÉTRICAS 17 - UTILIZAR O SEGUINTE CÓDIGO DE CORES PARA CABOS:
ELETROLITICAMENTE ABRAÇADEIRA SOBRE O
CABEAMENTO F FASE: PRETO - NEUTRO: AZUL CLARO - TERRA: VERDE - RETORNO: BRANCO - RETORNO PARALELO: CINZA. RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:
CONDULETE METÁLICO CONDULETE - DISTÂNCIA DE
ESTRUTURADO
DO TIPO MÚLTIPLO 3cm)
F CAIXA DE SOBREPOR 18 - EM SITUAÇÕES ONDE A VIGA ESTRUTURAL TORNAR INVIÁVEL A PASSAGEM DOS CONDUTOS ELÉTRICOS, A INSTALAÇÃO
(MÍNIMO DE 105mmX105mm) DEVERÁ SER FEITA ABAIXO DA VIGA PARA TRANSPOSIÇÃO DESTES OBSTÁCULOS UTILIZANDO-SE TIRANTES PARA EXTENSÃO
DETALHE TÍPICO DE CONEXÃO DO T COM SIRENE DE DOS SUPORTES (VER DETALHES), PODENDO TAMBÉM UTILIZAR ELETRODUTOS METÁLICOS FLEXÍVEIS (SEALTUBE). BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
FIXAÇÃO DO ELETRODUTO EM PAREDE INSTALAÇÃO DOS ELETRODUTOS DE ELÉTRICA/LÓGICA TOMADA 2P+T -10A (REF.:
PIALPLUS DA LEGRAND),
SINALIZAÇÃO INTERMITENTE
ELETRODUTO NA ELETROCALHA FIXAR NO MÁXIMO A CADA 1,50m DISTÂNCIA MÍNIMA ENTRE CAIXAS - 15cm PARA ALIMENTAÇÃO DO ALARME
E STROBE LIGHT, FONTE
INTERNA DE 220Vca-12Vcc.
19 - TODO E QUALQUER PONTO DE CABEAMENTO ESTRUTURADO DEVERÁ SER ACOMPANHADO DE SEU RESPECTIVO PONTO
ELÉTRICO, CONFORME INSTALAÇÕES DE CABEAMENTO (VER PROJETO ESPECÍFICO). PARA INSTALAÇÕES EMBUTIDAS, Secretaria de Estado de Saúde de Minas Gerais
SEM ESCALA SEM ESCALA r r PNE
SEM ESCALA PAINEL AUDIOVISUAL PARA FORNECIMENTO COMPLETO PREVER DISTÂNCIA MÍNIMA DE 15cm ENTRE AS CAIXAS DE ELÉTRICA E DE CABEAMENTO PARA ATENDER A UM MESMO Cidade Administrativa Presidente Tancredo Neves
SINALIZAÇÃO DE T EQUIPAMENTO. Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
EMERGÊNCIA. REF.: ALARME Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
HB, EATON OU EQUIVALENTE. 20 - TODAS AS LUMINÁRIAS, POR SEGURANÇA, DEVERÃO SER FIXADAS ATRAVÉS DE CABO DE AÇO AOS MONTANTES
ESTRUTURAIS DA LAJE (VER DETALHE).. SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
ELETRODUTOS PVC/AÇO F 21 - OS ALIMENTADORES DO QDC A PARTIR DO PADRÃO DE ENTRADA (INCLUINDO O PADRÃO DE ENTRADA DE ENERGIA
SUPERINTENDENCIA DE GESTÃO
r INTERRUPTOR BIPOLAR SIMPLES, 10A/250V
ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150 ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 13057 r REF.: PIALPLUS DA LEGRAND.
JUNTO À CONCESSIONÁRIA) DEVERÃO SER OBJETO DE PROJETO ESPECÍFICO. DIRETORIA DE GESTÃO DA REDE FÍSICA
DIÂMETRO ESPESSURA NOMINAL DA PAREDE DIÂMETRO ESPESSURA NOMINAL DA PAREDE F PARA ACIONAMENTO DA SINALIZAÇÃO DE DISCIPLINA:
22 - OS CHUVEIROS ELÉTRICOS DEVERÃO TER RESISTÊNCIA DO TIPO BLINDADA OU SER APROPRIADOS PARA INSTALAÇÕES
NOMINAL-DN EXTERNO-DE e NOMINAL-DN EXTERNO-DE e EMERGÊNCIA DOS BANHEIROS DO TIPO
ACESSÍVEIS (PNE)
EM CIRCUITOS PROTEGIDOS ATRAVÉS DE IDR (INTERRUPTOR DIFERENCIAL RESIDUAL) PARA EVITAR DESLIGAMENTOS INSTALAÇÕES ELÉTRICAS
mm POL mm mm mm POL mm mm INDEVIDOS. PROJETO:
25 3/4 25,9 2,3 20 3/4 25,2 1,5
32 1 33,0 2,7 25 1 31,5 1,5 23 - TODOS OS BANHEIROS DO TIPO ACESSÍVEIS (PNE) DEVERÃO POSSUIR SINALIZAÇÃO DE EMERGÊNCIA DE ACORDO COM A UBS MINAS - PROJETO MODELO
40 1.1/4 42,0 2,9 32 1.1/4 40,5 2,0 DETALHE ESQUEMÁTICO DE SINALIZAÇÃO PARA NBR-9050. PARA ESQUEMÁTICO DE FUNCIONAMENTO DO SISTEMA, VER DETALHE ESPECÍFICO NESTE PROJETO.
TIPO T1T - TÉRREA
50 1.1/2 47,4 3,0 40 1.1/2 46,6 2,25 24 - PROJETO ELABORADO DE ACORDO COM AS ESPECIFICAÇÕES DA NBR-5410:2004, SEGUINDO AS NECESSIDADES
60 2 59,0 3,1 50 2 58,4 2,25 BANHEIROS DO TIPO ACESSÍVEIS (PNE) APONTADAS PELO LAYOUT SUGERIDO PELO CLIENTE. QUALQUER ALTERAÇÃO DEVERÁ SER COMUNICADA AO PROJETISTA ENDEREÇO:

75 2.1/2 74,7 3,8 65 2.1/2 74,1 2,85 SEM ESCALA PARA VERIFICAÇÃO.
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
85 3 87,6 4,0 80 3 86,8 2,65 ETAPA:
CONTEÚDO: FOLHA:
25 - O MEMORIAL DESCRITIVO E QUANTITATIVO FAZEM PARTES INTEGRANTES DESTE PROJETO, E DEVERÃO SER
110 4 113,1 5,0 100 4 111,6 2,65
abrasip-mg PROJETO EXECUTIVO
CONSULTADOS ANTES DE QUAISQUER ORÇAMENTOS OU INSTALAÇÕES. DETALHES CONSTRUTIVOS, NOTAS
GERAIS E SIMBOLOGIA
01
05
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm)
LEGENDA PARA PERCURSO DE CABOS (QDC-T1/T):
L2al
#4,0 2x16W
L2al
L2ak
2x16W L2ak #4,0 A
VER NOTA 5 #4,0
#4,0 #4,0
L2aq
DEPOSITO B
2x32W
GINECOLOGIA #4,0 #4,0
#4,0 #4,0
L1aj L1aj AGENTES #4,0 L2ar
2x32W L2ap L2aq 2x16W C
2x32W L2an L2ao DE SAÚDE
2x32W #4,0 2x32W #4,0 #4,0
#4,0 2x32W 2x32W
L2ar
L2am #4,0 APOIO
L2am #4,0 2x32W L2aq AGENTES D
L2am #4,0 #4,0
#4,0 #4,0
2x32W #4,0 2x32W ENDEMIAS #4,0
2x32W #4,0 #4,0
#4,0
#4,0
L1ai L1ai #4,0 #4,0 L2an,ao L2ap #4,0 #4,0
2x32W
B L2aq #4,0
2x32W #4,0

L2at L2at
#4,0 A B #4,0
B #4,0 C #4,0 L4bm L2at 2x32W 2x32W
#4,0 #4,0 L4bl #4,0 2x16W

CAIXA D'AGUA
2x16W L4bl #4,0

PROJEÇÃO
L4bl #4,0
#4,0 2x16W 2x16W #4,0 D
#4,0
CIRCULAÇÃO #4,0 #4,0
#4,0 #4,0
#4,0 L4bl L4bl L4bm
L1ai #4,0
L1ai L4bk D
2x32W AUTOCLAVE
#4,0
2x32W
L3bf L2au L2au L2au
L1ai,aj #4,0 #4,0
2x32W #4,0 #4,0 2x32W 2x32W
#4,0
L3bg
#4,0
2x32W #4,0
L1ah L4bk #4,0 L3bg
2x16W L4bm #4,0
2x32W #4,0
2x16W ESTERILIZAÇÃO
#4,0 L1ah L3be L3bh
L3be #4,0
#4,0
#4,0 #4,0 2x32W
#4,0
#4,0 L4bm L2av #4,0
#4,0
L1ah #4,0 L3bh
2x32W 2x32W D
#4,0 #4,0 #4,0 #4,0 L2av
L3be L4bm 2x32W
L1ag #4,0
#4,0 2x32W 2x16W NOTAS:
2x32W
L4bk L5ab
#4,0
#4,0 2x16W 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
#4,0 L2ax
#4,0 #4,0 L1ag 2x16W 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
#4,0 #4,0 L4bm
L1ag L3bi L2ax 3-CONFERIR MEDIDAS NO LOCAL.
2x32W 2x32W L3bj
L3bj 4-COTAS EM CENTÍMETROS.
L5ad 2x32W
5-OS ELETRODUTOS PARA ALIMENTAÇÃO DAS ARANDELAS EXTERNAS DEVERÃO SER INSTALADOS SOBRE AS JANELAS,
L1af
#4,0 #4,0 A 2,70m DO PISO ACABADO.
#4,0 COPA
L2ay #4,0
COLETA #4,0
L4bk L2aw
VER NOTA 5
L1af #4,0 #4,0 L4bk
#4,0 2x16W SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
2x32W L1af TRIAGEM
2x32W SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
#4,0
#4,0 DIRETORIA DE INFRAESTRUTURA FÍSICA

PROJETO MODELO UNIDADE BÁSICA DE SAÚDE


PROJETO DE ACORDO COM RDC-50/2002 E
#4,0
L3bb #4,0 RESOLUÇÃO 1797/09 DA SES-MG
L5ab
L1ad L1ad 2x16W
2x32W 2x32W É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
#4,0
#4,0
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
#4,0 #4,0 L5ab
#4,0
L3bb L3bb
#4,0
#4,0 2x32W 2x32W
#4,0

L1ae L1ae L4bn L4bn L4bo L4bo


2x32W 2x32W 2x32W 2x32W 2x32W 2x32W #4,0
L5ab
#4,0 #4,0
#4,0 #4,0 #4,0 #4,0

#4,0

#4,0 #4,0 #4,0


L4bn L4bo L4bo
L1ac 2x32W 2x32W 2x32W 06 EMISSÃO FINAL 14/10/2013 VIABILE
L5aa
L1aa
2x16W #4,0 #4,0 #4,0 #4,0 #4,0
05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 03/09/2013 VIABILE
#4,0 #4,0 L4bn
2x32W #4,0

L1aa L4bn,bo 04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE


L5aa
#4,0
L5aa 03 EMISSÃO FINAL 08/11/2012 VIABILE
L1ab L1ac
2x16W 2x32W L5aa
02 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 29/10/2012 VIABILE
#4,0

01 REVISÃO DA ARQUITETURA 18/10/2012 VIABILE

L5aa
00 EMISSÃO INICIAL 27/09/2012 VIABILE

REVISÃO OBJETO DATA VERIFICAÇÃO

GERENCIAMENTO E PROJETO:

Av. Augusto de Lima, nº655


conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br

DESENVOLVIMENTO: DATA:

BRENO ASSIS DE OLIVEIRA SETEMBRO/2013


NOME DO ARQUIVO CAD: ESCALA: UNIDADE:
CALÇADA INDICADA
460-UBSSS-R06-ELE-02-PE-T1T.DWG MILÍMETROS
RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:

BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS

RUA Secretaria de Estado de Saúde de Minas Gerais


Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
PLANTA DE ILUMINAÇÃO SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
ESCALA: ..................................................... 1/75 SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:

INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T1T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


PLANTA DE ILUMINAÇÃO 02
05
FORMATO INTERNACIONAL A1 (841 x 594mm)
T16-1,0kVA-220V

T38-1,11kW-220V LEGENDA PARA PERCURSO DE CABOS (QDC-QDC-T1/T):


T13 T13
T36-1,11kW-220V T15 T39-1,11kW-220V T40-1,11kW-220V
#4,0 T13 T20 T21
T15 T13 T14
T38 T39 T44 T19 T33 T1 T2 T3 T4 T9 T10 T11 T13 T28 T49 T12
#4,0 #4,0 GINECOLOGIA
T40 #4,0
T20 T13
A
#4,0 T17 #4,0 #4,0 #6,0

21-200VA
#4,0 T13 T20 T21

21-200VA
T15 T13
T17 #4,0 T17 T21 T21 #4,0 T19 T33 T1 T2 T3 T4 T5 T9 T10 T11 T13 T13 T28 T29 T46 T49 T12
T14 2x200VA #4,0 T20 B
#4,0 T15 T14 T21 #4,0 #6,0
T16 T17 T40 T44 AGENTES
T36 #4,0 T20 T13 T19 T33 T1 T2 T3 T6 T9 T10 T11 T4 T5 T13 T28 T29 T46 T49 T12
#4,0 T15 #4,0 #4,0 #4,0 T20-2x200VA #4,0
#4,0 DE SAÚDE C
#4,0 #4,0 #4,0 #6,0
T14 T14 T20
T15 T13 T38 T39 T21
T8 T19 T33 T1 T2 T3 T6 T9 T10 T11 T4 T5 T13 T28 T29 T37 T46 T49 T12
T14-200VA #4,0 #4,0 T18-600VA T17 T21 T21 D
#4,0 T14-200VA #4,0 T20 #4,0 T13 T20 T21 #4,0
T15 T15 T14 T17 T18-600VA T21 #4,0 #6,0
T15
T19 #4,0
T14 T14 #4,0 T22 T8 T19 T33 T1 T2 T3 T6 T9 T10 T11 T4 T5 T13 T28 T29 T30 T31 T32 T37 T46 T49 T12
T15 T13 #4,0
#4,0 #4,0
T22 T22 E
T19 #4,0 #6,0
T15 T13 T33 T13 T21 T22
#4,0
#4,0 T8 T19 T33 T1 T2 T3 T6 T7 T9 T10 T11 T4 T5 T13 T28 T29 T30 T31 T32 T37 T46 T49 T12
T36 #4,0 J K L M N N N N T19 O #4,0 P T22 #4,0 F

CAIXA D'AGUA
T22

PROJEÇÃO
#4,0 #6,0
#4,0 Q #4,0 T22 T45 T45 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9
I T20
T45 G
T35 CIRCULAÇÃO #4,0 T22 #4,0
#4,0 #4,0
T22 1kVA T43-1,11kW-220V
T35
2x200VA T15 #4,0 H R T45 #4,0
T43 T10 T11 T13 T28 T29 T30 T31 T32 T34 T37 T41 T46 T47 T48 T49 T12
#4,0
#4,0 T15 T15
#4,0 T22 T22 #4,0 #4,0 #6,0
T20 R
T35-1,11kW-220V #4,0 T15 #4,0 T33 #4,0 T42-1,11kW-220V T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10
G T42 T43
H
T15 T15 T34 T41 T47 T48 T42 T43
#4,0
T7 T20
S #4,0 T22 T22
T22 T22 #4,0 T11 T13 T15 T28 T29 T30 T31 T32 T34 T37 T41 T46 T47 T48 T49 T12
T7 #4,0 T20 #4,0 #4,0
T34-1,11kW-220V #4,0
#4,0 T7 T13 T23 T23
S ESTERILIZAÇÃO #4,0 T22 #4,0 #4,0 #6,0
T41 T47 T48 T22 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10
T7
T6 T7 T6 T7 #4,0
#4,0
F #4,0
T22 T escaninhos I
#4,0
T41-1,11kW-220V #4,0 #4,0
#4,0
6500W
T7-2x200VA T6 T7 T7 T13 T22 #4,0 T11 T13 T15 T28 T29 T30 T31 T32 T34 T35 T37 T41 T46 T47 T48 T49 T12
T47 T48
T32-1,11kW-220V #4,0 T #4,0 #6,0
#4,0 T23
T7 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10
T6 T6
T47-1,11kW-220V T32
#4,0 J
#4,0
T48 #4,0 #4,0 #4,0 U
T6 E T23 T24
T11 T13 T15 T28 T29 T30 T31 T32 T34 T35 T36 T37 T41 T46 T47 T48 T49 T12
NOTAS:
#4,0 T31-1,11kW-220V T2-2x200VA T37-1,11kW-220V
#4,0 #6,0
T48-1,11kW-220V T6 T8 #4,0 T22 T25 T26 T27 T13
T30 T31 T32
T30 D T8 T8 T27
T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
#4,0
#4,0
T27
#4,0 K
T8 T37 T13 #4,0
T8
#4,0 T22 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
T8 6500W
#4,0 T27 T13 T14 T15 T28 T29 T30 T31 T32 T34 T35 T36 T37 T41 T46 T47 T48 T49 T12
T8 T37
T25 T26 T27 #4,0 #6,0 3-CONFERIR MEDIDAS NO LOCAL.
T33
T6 #4,0
T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14
T6 #4,0
L 4-COTAS EM CENTÍMETROS.
1,8kVA T25 600VA T27
C T26 T25 #4,0
#4,0
T5 5-OS COMPONENTES E MATERIAIS ESPECIFICADOS NESTE PROJETO SÃO REFERÊNCIAS, E PODERÃO SER
T6 T5 T27 T27 T15 T16 T20 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T41 T46 T47 T48 T49 T12 SUBSTITUÍDOS POR EQUIVALENTES TÉCNICOS (APRESENTAR PROTÓTIPO PARA APROVAÇÃO POR PARTE DA
T27 FISCALIZAÇÃO DE OBRAS).
T25 T27 #4,0 #6,0
T30 COLETA
#4,0
T5 B T27
T5
600VA T25 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15
T5
#4,0 #4,0 M
#4,0
B TRIAGEM
#4,0 SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
T5-2x200VA T19 T25 T25 COPA T25 T16 T17 T20 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T41 T46 T47 T48 T49 T12
T30-1,11kW-220V T19
T5 SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
12-1,8kVA #4,0 #6,0
T29
T10 T10 600VA
#4,0 T5
T29 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16
DIRETORIA DE INFRAESTRUTURA FÍSICA
T12 T11 T11 T5
#4,0 N
T10
T10 #4,0 T5 #4,0 #4,0
T10
T10
#6,0 #4,0
A
#4,0
T5-200VA #4,0
T17 T18 T20 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T41 T46 T47 T48 T49 T12
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
#4,0 #4,0 T10 T12
T5-200VA T29-1,11kW-220V
PROJETO DE ACORDO COM RDC-50/2002 E
T10 T11 T12
#4,0 #4,0 #6,0 T49 #4,0 #6,0 RESOLUÇÃO 1797/09 DA SES-MG
T49-1kVA T46-1kVA
#4,0 #6,0 T33 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16
T33 T46 T49 T33
T9 T13 #4,0
T46
O
#4,0
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
T9 #4,0
#4,0

#4,0
T19 T33 T1 T2 T3 T4 T9 T13 T28
#4,0
T17 T18 T20 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T44 T46 T47 T48 T49 T12 COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
T2 #4,0 #4,0 #6,0
T9 T13
2x200VA T2
T9 #4,0 T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13T14 T15 T16 T17
T19 T33 T1 T3 T4 T9 T13 T28 #4,0 2x200VA #4,0 P
T28 T1 T28 #4,0
#4,0
T33 T33 T19 T1 T3 T4 T9 T13 T18 T20 T21 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T44 T46 T47 T48 T49 T12
#4,0 T1 #4,0
T19 T3 T4 T9 T13
#4,0 #4,0
T28-1,11kW-220V #4,0 #6,0
T19 T1 T1 T1 T1
#4,0
600VA T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16 T17 T18
T9 #4,0 #4,0 #4,0 #4,0 T1 T1 T4 Q
T19 T3 T4 T13 #4,0
#4,0 T4 #4,0
T9 T4 T20 T21 T22 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T44 T46 T47 T48 T49 T12 06 EMISSÃO FINAL 14/10/2013 VIABILE
#4,0 T1 T19 T3 T4
#4,0 T19 T3 T4 T3
#4,0 #4,0 #6,0
#4,0 #4,0
#4,0 T19 T3 T4 T19 T3 T4 T3 T19 T3 #4,0
T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16 T17 T18T20 05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 03/09/2013 VIABILE
T13b' #4,0 #4,0 #4,0
R
T19 T3 T4 #4,0
T19 T4
T1 T21 T22 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T44 T45 T46 T47 T48 T49 T12
T13b' T1 #4,0 04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 31/01/2013 VIABILE
#4,0 T4-200VA #4,0
#4,0 T19 #4,0 #6,0
T1 T1 T1 T4-200VA
T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16 T17 T18T20
#4,0 T4
S 03 EMISSÃO FINAL 08/11/2012 VIABILE
T1 #4,0
#4,0
T13a' T13a' T13 T21 T22 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T42 T43 T44 T45 T46 T47 T48 T49 T12
02 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 29/10/2012 VIABILE
#4,0 #6,0
#4,0
T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16 T17 T18T20
T 01 REVISÃO DA ARQUITETURA 18/10/2012 VIABILE
#4,0
T13
T13 T13 T21 T22 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T42 T43 T44 T45 T46 T47 T48 T49 T12
00 EMISSÃO INICIAL 27/09/2012 VIABILE
#4,0 #6,0

T8 T19 T33 T1 T2 T3 T4 T5 T6 T7 T9 T10 T11 T13 T14 T15 T16 T17 T18T20 REVISÃO OBJETO DATA VERIFICAÇÃO
U
#4,0 GERENCIAMENTO E PROJETO:

T25 T26 T27 T28 T29 T30 T31 T32 T34 T35 T36 T37 T38 T39 T40 T41 T42 T43 T44 T45 T46 T47 T48 T49 T12
Av. Augusto de Lima, nº655
#4,0 #6,0 conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br

DESENVOLVIMENTO: DATA:

BRENO ASSIS DE OLIVEIRA SETEMBRO/2013


NOME DO ARQUIVO CAD: ESCALA: UNIDADE:

460-UBSSS-R06-ELE-03-PE-T1T.DWG INDICADA MILÍMETROS


RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:

BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS

Secretaria de Estado de Saúde de Minas Gerais


Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

SUBSECRETARIA DE INOVAÇÃO E LOGISTICA


SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
PLANTA DE TOMADAS DISCIPLINA:
ESCALA: ............................................ 1/75
INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T1T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


PLANTA DE TOMADAS
03
05
SIMBOLOGIA P/ QUADRO:
DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES.
ADVERTÊNCIA
CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E CLASSE II,
VER PROJETO ESPECÍFICO SEGUNDO NBR5410: 1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A
DE ALIMENTADORES/IMPLANTAÇÃO - OBEDECER A NBR IEC 61.643-1; Up (NÍVEL DE PROTEÇÃO):
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO.
Pe R S T N INFERIOR A 1,5kV;
- Uc (MÁXIMA TENSÃO DE OPERAÇÃO CONTÍNUA): 175V; DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE
- Iimp (CORRENTE DE IMPULSO): SUPERIOR A 12,5kA (10/350us); SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM)
- In (CORRENTE NOMINAL DE DESCARGA): SUPERIOR A 20kA SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE
(8/20us) PARA REDES TRIFÁSICAS;
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS
UTILIZAR NAS FASES COMO PROTEÇÃO BACKUP, FUSÍVEIS DE MAIOR SEÇÃO (BITOLA).
MODULARES NH-63A gG/gL.
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃO
CONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS
INTERRUPTOR DIFERENCIAL RESIDUAL (IDR). CARACTERÍSTICAS SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE,
TERRA NEUTRO
TÉCNICAS: SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO
- TIPO AC;
PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE
- CORRENTE NOMINAL (In): CONFORME INDICAÇÃO;
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR; SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A
FREQUÊNCIA: 60Hz. DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO.
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES),
CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS,
#10,0
SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA

FUSÍVEL MODULAR DISJUNTOR


Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR,
RESPECTIVAMENTE).
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410
63A GERAL
200A A SER FIXADA NO INTERIOR DO QUADRO ELÉTRICO
DISJUNTOR GERAL:
#10,0 #10,0 MÍNIMO DE 10kA - TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO E
DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V.
#10,0 #10,0

#10,0 #10,0 CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO


DPS #10,0
175V HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
CLASSE I/II CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA).
12,5kA - 10/350us
20kA - 8/20us CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,
63A (C) 40A (C)
CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO).
#16,0 #10,0 TABELA 1: ESPAÇO RESERVA
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO
HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, QUANTIDADE DE CIRCUITOS ESPAÇO MÍNIMO DESTINADO A
CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE). EFETIVAMENTE DISPONÍVEL RESERVA (EM NÚMEROS DE
N CIRCUITOS)
ATÉ 6 2
63A (C) 63A (C) 7 A 12 3
13 A 30 4
#16,0 #16,0 NOTAS GERAIS DOS QUADROS: N>30 0,15xN

01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2


(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE
CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS FORAM
DIMENSIONADOS PARA Icc >= 10kA/220V E DEVERÃO SER DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA . NOTAS:

BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA 02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NO QUADRO
L1 L2 RES. RES. L4 RES. T8 T2 T3 T1 T5 T6 T4 T15 T9 T7 T19 T17 T14 T45 T20 DE CARGAS. 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
#4,0 #4,0 #4,0 #2,5 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #2,5 #4,0 #4,0 #4,0 #4,0 03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO 3-CONFERIR MEDIDAS NO LOCAL.
NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004.
4-COTAS EM CENTÍMETROS.
04 - O QUADRO SERÁ METÁLICO, DE SOBREPOR (PREVER ESTRUTURA NO STEEL FRAME PARA
5-OS COMPONENTES E MATERIAIS ESPECIFICADOS NESTE PROJETO SÃO REFERÊNCIAS E PODERÃO SER SUBSTITUÍDOS
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A
SUSTENTAÇÃO), COM NO MÍNIMO IP-30 (EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO
10

POR EQUIVELENTES TÉCNICOS (APRESENTAR PROTÓTIPO PARA APROVAÇÃO POR PARTE DA FISCALIZAÇÃO DAS OBRAS).
POSSUIR GRAU DE PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO
R
COM CHAVE, NÃO ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL
S ACESSO E NÃO SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO
NBR IEC 60.439-1 EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
T SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
05 - O QUADRO DEVERÁ POSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE
CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO, SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
T28 T29 T30 T31 T32 RES. RES. T34 T35 T36 T37 T38 T39 SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO, DIRETORIA DE INFRAESTRUTURA FÍSICA
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 CONFORME LAYOUT SUGESTIVO PRESENTE NO DIAGRAMA MULTIFILAR.

06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS, PROJETO DE ACORDO COM RDC-50/2002 E
SEGUNDO ORIENTAÇÕES DA NBR-5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E RESOLUÇÃO 1797/09 DA SES-MG
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A
SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE
R FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
S
QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME
DETALHADO NO DIAGRAMA MULTIFILAR.
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
T 07- NO QUADRO DEVER Á SER FIXADO, ATRAVÉS DE DISPOSITIVO PRÓPRIO, O SEU DIAGRAMA , CONTENDO
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO .

T40 T41 T42 T43 T44 T16 T18 RES. T46 T21 T48 T47 RES. RES. T33 T49 05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 17/09/2013 VIABILE
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADRO ELÉTRICO DEVERÃO SER COM CONECTOR TIPO
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #2,5 #4,0 BOX RETO, COM BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS
ELETROCALHAS DEVERÃO SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE
04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
PROJETO.

09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA
EMISSÃO FINAL
16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

03 08/11/2012 VIABILE
PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO AOS
R BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA
ADEQUADA. 02 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 29/10/2012 VIABILE
S
10- O QUADRO DEVER Á ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE
T
BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO. 01 REVISÃO DA ARQUITETURA 18/10/2012 VIABILE

T10 T11 T12 T13 T22 T25 T23 T27 T26 T24 RES. L3 RES. L5 RES. RES. 11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA
PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO . 00 EMISSÃO INICIAL 27/09/2012 VIABILE
#4,0 #4,0 #6,0 #4,0 #4,0 #4,0 #6,0 #4,0 #4,0 #6,0 #4,0 #2,5 #10,0
INTERRUPTOR REVISÃO OBJETO DATA VERIFICAÇÃO
12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM
TETRAPOLAR ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO GERENCIAMENTO E PROJETO:
DR3-In 40A SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO

NEUTRO DR
SENS. 30mA Av. Augusto de Lima, nº655
16A

16A

16A

16A

16A

16A

32A

16A

16A

32A

16A

16A

A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO "CIRCUITO" DO QUADRO DE CARGAS


TIPO AC conj. 418 - Centro - BH
CORRESPONDENTE.
R Telefax: (31) 3324-2702
#10,0 http://www.viabile.com.br
13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE viabile@viabile.com.br
S
EM PVC 70°C 750V.
T
BARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A DESENVOLVIMENTO: DATA:

BRENO ASSIS DE OLIVEIRA SETEMBRO/2013


NOME DO ARQUIVO CAD: ESCALA: UNIDADE:

460-UBSSS-R05-ELE-04-PE-T1T.DWG INDICADA MILÍMETROS


RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:

QDC-T1/T - DIAGRAMA MULTIFILAR (96 POLOS)


BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
DETALHE SUGESTIVO DO QUADRO
QUADRO METÁLICO DE SOBREPOR
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar

SUBSECRETARIA DE INOVAÇÃO E LOGISTICA


SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:

INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T1T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


DIAGRAMA MULTIFILAR
04
05
FORMATO INTERNACIONAL A1 (841 x 594mm)
QDC-T1T-RELAÇÃO DE CARGAS E MEMÓRIA DE CÁLCULO MEMÓRIA DE CÁLCULO
QUEDA DE TENSÃO
QUEDA DE
BLOCO AR PROTEÇÃO COMPRIMENTO
ILUMINAÇÃO SINALIZAÇÃO TOMADAS CHUVEIROS COMPRESSOR CORRENTE TENSÃO EFETIVA
AUTONOMO CONDICIONADO POTÊNCIA TOTAL TENSÃO EQUILÍBRIO CONDUTOR MÁXIMO DO
CIRCUITO DESCRIÇÃO (W) (W) (W) (W) (W) F.P. FASES NOMINAL
(W) (W) (mm²) CIRCUITO
In LIMITE:
CURVA
16 23 32 25 50 85 170 510 850 1530 6500 1110 850 (kW) (kVA) (V) R S T (A) (A) (m) 3,00%

ILUMINAÇÃO CUIDADOS BÁSICOS URG. E EMERG., ATEND.


L1 MULTIPROFISSIONAL, COLETA, SALA DE REUNIÃO E EDUCAÇÃO, IS MASC. E 4 - 34 - - - - - - - - - - 0,95 1,15 1,21 220 RS 0,61 0,61 0,00 5,51 16 C 4,0 48 1,03%
FEM., CIRCULAÇÃO

ILUMINAÇÃO COMPRESSOR, IS, GINECOLOGIA, CONSULTÓRIO


ODONTOLÓGICO, GUARDA MEDICAMENTOS, AGENTES DE SAÚDE,
L2 14 - 28 - - - - - - - - - - 0,95 1,12 1,18 220 TR 0,59 0,00 0,59 5,36 16 C 4,0 31 0,65%
DEPÓSITO, APOIO AGENTES ENDEMIAS, SALA LAVAGEM E DESINF.
MATERIAIS, ESTERILIZAÇÃO, ACESSO FUNCIONÁRIOS, DML E RESÍDUOS.

ILUMINAÇÃO RECEPÇÃO, VACINAÇÃO, TRIAGEM, SALA DE CURATIVOS,


L3 ÁREA COBERTA, ESCOVÁRIO, ALMOXARIFADO, VEST. MASC E FEM, COPA. - - 28 - - - - - - - - - - 0,95 0,90 0,94 220 ST 0,00 0,47 0,47 4,29 16 C 4,0 54 0,90%

L4 ILUMINAÇÃO CIRCULAÇÃO E ESPERA 20 - 24 - - - - - - - - - - 0,95 1,09 1,15 220 RS 0,57 0,57 0,00 5,21 16 C 4,0 49 1,00%

L5 ILUMINAÇÃO ÁREA EXTERNA - 23 - - - - - - - - - - - 0,95 0,53 0,56 220 ST 0,00 0,28 0,28 2,53 16 C 2,5 51 0,81%

T1 TOMADAS SALA DE ESPERA - - - - - 6 - - - - - - - 0,85 0,51 0,60 127 R 0,60 0,00 0,00 4,72 16 C 4,0 47 1,50%

T2 TOMADAS RECEPÇÃO - - - - - - 4 - - - - - - 0,85 0,68 0,80 127 S 0,00 0,80 0,00 6,30 16 C 4,0 42 1,79%

T3 TOMADAS VACINAÇÃO - - - - - 1 - 1 - - - - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 44 1,64%

T4 TOMADAS VACINAÇÃO - - - - - - 2 1 - - - - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 44 2,35%

T5 TOMADAS TRIAGEM/ TOLETA - - - - - 3 4 - - - - - - 0,85 0,94 1,10 127 S 0,00 1,10 0,00 8,66 16 C 4,0 40 2,35%

T6 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 1 - - - - - 3 2 - - - - - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 37 1,38%

T7 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 2 - - - - - 3 2 - - - - - - 0,85 0,60 0,70 127 R 0,70 0,00 0,00 5,51 16 C 4,0 32 1,19%

T8 TOMADAS SALA DE CURATIVOS - - - - - 3 - - - - - - - 0,85 0,26 0,30 127 R 0,30 0,00 0,00 2,36 16 C 2,5 32 0,82%

T9 TOMADAS SALA DE REUNIÃO - - - - - 4 - - - - - - - 0,85 0,34 0,40 127 T 0,00 0,00 0,40 3,15 16 C 4,0 40 0,85%

T10 TOMADAS SALA DE REUNIÃO - - - - - 2 - 1 - - - - - 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 16 C 4,0 41 1,75%

T11 TOMADA GELADEIRA SALA DE REUNIÃO - - - - - - - 1 - - - - - 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 16 C 4,0 41 1,31%

T12 TOMADA MICRO-ONDAS SALA DE REUNIÃO - - - - - - - - - 1 - - - 0,85 1,53 1,80 127 T 0,00 0,00 1,80 14,17 16 C 6,0 41 2,62%
TOMADAS I.S./ SALA DE APOIO AGENTES ENDEMIAS/ CIRCULAÇÃO/ NOTAS:
T13 - - - - 2 10 - - - - - - - 0,85 0,95 1,12 127 R 1,12 0,00 0,00 8,80 16 C 4,0 48 2,86%
BEBEDOUROS
T14 TOMADAS GINECOLOGIA - - - - - 4 2 - - - - - - 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 16 C 4,0 32 1,36% 1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.

T15 TOMADAS CUIDADOS BÁSICOS - - - - - 4 2 - - - - - - 0,85 0,68 0,80 127 S 0,00 0,80 0,00 6,30 16 C 4,0 29 1,24% 2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.

T16 PONTO DE FORÇA COMPRESSOR - - - - - - - - - - - - 1 0,85 0,85 1,00 220 ST 0,00 0,50 0,50 4,55 16 C 4,0 20 0,36% 3-CONFERIR MEDIDAS NO LOCAL.

4-COTAS EM CENTÍMETROS.
T17 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - 6 - - - - - - - 0,85 0,51 0,60 127 T 0,00 0,00 0,60 4,72 16 C 4,0 15 0,48%

T18 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - - - 2 - - - - - 0,85 1,02 1,20 127 R 1,20 0,00 0,00 9,45 16 C 4,0 9 0,58%
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
T19 BLOCO AUTONOMO - - - 6 - - - - - - - - - 0,85 0,15 0,18 127 S 0,00 0,18 0,00 1,39 16 C 2,5 9 0,14% SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
TOMADAS ESCOVÁRIO/ GUARDA MEDICAMENTOS/ ALMOXARIFADO/
T20
DEPÓSITO
- - - - - 5 2 - - - - - - 0,85 0,77 0,90 127 T 0,00 0,00 0,90 7,09 16 C 4,0 22 1,06% DIRETORIA DE INFRAESTRUTURA FÍSICA
T21 TOMADAS AGENTES DE SAÚDE - - - - - 3 4 - - - - - - 0,85 0,94 1,10 127 R 1,10 0,00 0,00 8,66 16 C 4,0 17 1,00%
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
TOMADAS LAVAGEM E DESINFECÇÃO DE MATERIAIS/ ESTERILIZAÇÃO/ PROJETO DE ACORDO COM RDC-50/2002 E
T22 - - - - - 10 - - - - - - - 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 16 C 4,0 11 0,59%
VESTIÁRIO MASC. E FEM. RESOLUÇÃO 1797/09 DA SES-MG
T23 PONTO DE FORÇA CHUVEIRO VESTIÁRIO MASCULINO – 220V - - - - - - - - - - 1 - - 1,00 6,50 6,50 220 RS 3,25 3,25 0,00 29,55 32 C 4,0 8 0,92%
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
T24 PONTO DE FORÇA CHUVEIRO VESTIÁRIO FEMININO – 220V - - - - - - - - - - 1 - - 1,00 6,50 6,50 220 ST 0,00 3,25 3,25 29,55 32 C 4,0 9 1,04%
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
T25 TOMADAS COPA - - - - - 4 - 1 - - - - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 16 0,85%

T26 TOMADA COPA – MICRO-ONDAS - - - - - - - - - 1 - - - 0,85 1,53 1,80 127 R 1,80 0,00 0,00 14,17 16 C 4,0 15 1,44%

T27 TOMADAS DML/ RESÍDUOS/ PÁTIO DE ATIVIDADES - - - - - 4 - 1 - - - - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 16 0,85%

T28 PONTO DE FORÇA AR-CONDICIONADO VACINAÇÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 43 1,00% 05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS 17/09/2013 VIABILE

T29 PONTO DE FORÇA AR-CONDICIONADO TRIAGEM - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 39 0,90%
04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA 01/02/2013 VIABILE
T30 PONTO DE FORÇA AR-CONDICIONADO COLETA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 39 0,90%
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL 03 EMISSÃO FINAL 08/11/2012 VIABILE
T31 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 32 0,74%
1
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL
T32 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 32 0,74%
2 02 ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS 29/10/2012 VIABILE
T33 TOMADAS CFTV - - - 5 - - - - - - - - - 0,85 0,13 0,15 127 S 0,00 0,15 0,00 1,16 16 C 2,5 9 0,11%
01 REVISÃO DA ARQUITETURA 18/10/2012 VIABILE
T34 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 36 0,84%

T35 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 1 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 29 0,67% 00 EMISSÃO INICIAL 27/09/2012 VIABILE

T36 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 2 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 24 0,56% REVISÃO OBJETO DATA VERIFICAÇÃO

GERENCIAMENTO E PROJETO:
T37 PONTO DE FORÇA AR-CONDICIONADO SALA DE CURATIVOS - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 28 0,65%
Av. Augusto de Lima, nº655
T38 PONTO DE FORÇA AR-CONDICIONADO GINECOLOGIA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 33 0,77%
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
T39 PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 1 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 15 0,35%
http://www.viabile.com.br
viabile@viabile.com.br
T40 PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 2 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 12 0,28%

T41 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 36 0,84% DESENVOLVIMENTO: DATA:

T42 PONTO DE FORÇA AR-CONDICIONADO ESTERILIZAÇÃO - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 14 0,32% BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
PONTO DE FORÇA AR-CONDICIONADO LAVAGEM E DESINFECÇÃO DE NOME DO ARQUIVO CAD: ESCALA: UNIDADE:
T43 - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 14 0,32%
MATERIAIS 460-UBSSS-R05-ELE-05-PE-T1T.DWG INDICADA MILÍMETROS
T44 PONTO DE FORÇA AR-CONDICIONADO AGENTES DE SAÚDE - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 14 0,32% RESPONSÁVEL TÉCNICO: PROPRIETÁRIO:

T45 TOMADA ESTERELIZAÇÃO - AUTOCLAVE - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 16 C 4,0 10 0,53%

T46 TOMADA RACK - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 40 2,13%
BRENO ASSIS DE OLIVEIRA CREA: 78.667/D SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS

T47 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 36 0,84%

T48 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - - - 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 36 0,84%
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
T49 TOMADA RACK SONORIZAÇÃO - - - - - - - - 1 - - - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 40 2,13% Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
TOTAL 38,00 23,00 114,00 11,00 2,00 75,00 24,00 8,00 3,00 2,00 2,00 18,00 1,00 0,89 56,07 63,07 220 RST 22,27 21,08 19,72 165,72 200 D - - -
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
DISCIPLINA:

INSTALAÇÕES ELÉTRICAS
PROJETO:

UBS MINAS - PROJETO MODELO


TIPO T1T - TÉRREA
ENDEREÇO:

VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS


CONTEÚDO: ETAPA: FOLHA:

abrasip-mg PROJETO EXECUTIVO


QUADRO DE CARGAS
05
05