Escolar Documentos
Profissional Documentos
Cultura Documentos
GERAL)
Circuito Descrição Esquema Método Tensão Pot. total. Pot. total. Fases Pot. - R Pot. - S Pot. - T FCT FCA In' Ip Seção Ic Disj dV parc dV total Status
de inst. (V) (VA) (W) (W) (W) (W) (A) (A) (mm2) (A) (A) (%) (%)
1 IP4 F+N D 220 V 800 736 R 736 1.00 0.80 4,18 3.35 2.5 24.0 10 0.00 2.29 OK
2 IP5 F+N+T D 220 V 1000 920 S 920 1.00 0.80 5.23 4.18 2.5 24.0 10 0.00 3.77 OK
3 IP6 F+N+T D 220 V 600 552 T 552 1.00 0.80 3.14 2.51 2.5 24.0 10 0.00 2.11 OK
4 QUADRO 1 3F+N+T D 380/220V 5100 4692 R+S+T 2156 1104 1288 1.00 0.80 15.44 12.35 10.0 50.0 40 0.00 0.11 OK CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO
TOTAL 7500 14143 R+S+T 5329 4501 4169 1.00 0.80 27.99 22.39 10.0 50.0 50 0.00 1.55 OK
( AL AO QD GERAL) ( 1 AO QD GERAL)
DISTÂNCIA = 4,50m CABO: 10mm2-PVC-70ºC(450/750V) DISTÂNCIA = 16,3m CABO: 2.5mm2-PVC-70ºC(450/750V)
CORRENTE = 13,92A CORRENTE = 3,75A
Quadro de Cargas (QD. 01) V/Akm= 3,63 V/Akm= 14,3
Circuito Descrição Esquema Método Tensão Pot. total. Pot. total. Fases Pot. - R Pot. - S Pot. - T FCT FCA In' Ip Seção Ic Disj dV parc dV total Status
de inst. (V) (VA) (W) (W) (W) (W) (A) (A) (mm2) (A) (A) (%) (%)
D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km
1 IP1 F+N D 220 V 1300 1196 R 1196 1.00 1.00 5.43 5.43 2.5 24.0 10 0.00 3.10 OK D V = 3,63 x 13,92 x 0,0045 = 0,23V D V = 14,3 x 3,75 x 0,0163 = 0,87 V
D V % = (0,23x 100)/220 = 0,10% D V % = (0,87x 100)/220 = 0,40%
2 IP2 F+N D 220 V 1200 1104 S 1104 0.95 1.00 5.28 5.02 4.0 24.0 10 0.00 2.55 OK
3 IP3 F+N D 220 V 1200 1104 T 0.95 1.00 5.28 5.02 4.0 24.0 10 0.00 1.75 OK
4 TS F+N+T B1 220 V 1200 960 R 960 1.00 0.80 5.45 4.36 2.5 24.0 10 0.00 0.31 OK
TS-A F+N+T B1 220 V 600 480 R 480 1.00 0.80 2.73 2.18 2.5 24.0 0.00 0.21 OK
TS-B F+N+T B1 220 V 600 480 R 480 1.00 0.80 2.73 2.18 2.5 24.0 0.00 0.10 OK
5 IS F+N+T B1 220 V 200 184 T 184 1.00 0.80 1.1 0.84 2.5 24.0 10 0.00 0.06 OK
CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO
IS-A F+N+T B1 220 V 100 92 T 92 1.00 0.65 0.525 0.42 2.5 24.0 0.00 0.05 OK
IS-B F+N+T B1 220 V 100 92 T 92 1.00 0.65 0.525 0.42 2.5 24.0 0.00 0.01 OK ( 3 AO QD GERAL) ( 2 AO QD GERAL)
DISTÂNCIA = 9,70m CABO: 2.5mm2-PVC-70ºC(450/750V) DISTÂNCIA = 7,85m CABO: 2.5mm2-PVC-70ºC(450/750V)
CORRENTE = 2,75A CORRENTE = 10,90A
V/Akm= 14,3 V/Akm= 14,3
TOTAL 5100 4548 R+S+T 2156 1104 1288 1.00 0.80 14.95 11.96 10.0 50.0 30 0.00 0.78 OK
D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km
D V = 14,3 x 2,75 x 0,0097 = 0,38 V D V = 14,3 x 10,90 x 0,00785 = 1,22 V
D V % = (0,38x 100)/220 = 0,2% D V % = (1,22x 100)/220 = 0,60%
2 TOMADA 1 F+N+T B1 220 V 2400 1920 F 1920 1.00 0.80 10.9 8.72 2.5 24.0 10 0.00 0.60 OK
3 TOMADA 2 F+N+T B1 220 V 600 480 F 480 1.00 0.80 2.75 2.20 2.5 24.0 10 0.00 0.20 OK
TOTAL 3720 3062 F 3062 1.00 1.00 13.92 13.92 10.0 50.0 20 0.00 0.10 OK
CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO
( QD GERAL AO QD CS MÁQ) ( IP1 AO QD 1) ( 5 AO QD CS MÁQ) ( IP5 AO QD GERAL)
DISTÂNCIA = 29,45m CABO: 10mm2-PVC-70ºC(450/750V) DISTÂNCIA = 87,74m CABO: 2.5mm2-PVC-70ºC(450/750V) DISTÂNCIA = 2,50m CABO: 2.5mm2-PVC-70ºC(450/750V)
DISTÂNCIA = 111,0m CABO: 2.5mm2-PVC-70ºC(450/750V)
CORRENTE = 28,80A CORRENTE = 5,43A CORRENTE = 0,42A
CORRENTE = 5,23A
V/Akm= 3,63 V/Akm= 14,3 V/Akm= 14,3
V/Akm= 14,3
CONVÊNIO: 870889/2018
D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km
DV = (V/A . Km) x A x Km
D V = 3,63 x 28,80 x 0,02945 = 3,10V D V = 14,3 x 5,43 x 0,08774 = 6,81V D V = 14,3 x 0,42 x 0,0025 = 0,02 V 8,30 V
DV = 14,3 x 5,23 x 0,111 =
D V % = (3,10x 100)/380 = 0,82% D V % = (6,81x 100)/220 = 3,10% D V % = (0,02x 100)/220 = 0,01%
DV % = (8,30x 100)/220 = 3,77% PROJETO ELÉTRICO
REFORMA PRAÇA SANTA BÁRBARA
CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO CÁLCULO DE QUEDA DE TENSÃO ENDEREÇO:
( IP2 AO QD 1) ( IP3 AO QD 1) ( IP6 AO QD GERAL) AV. OSVALDO CRUZ, ESQ. C/ RUA ATALIBA R. TÉLES, ESQ. C/ AV. RIO BRANCO, ESQ. C/ RUA JOSÉ SANTOS
( 1 AO QD CS MÁQ)
PROPRIETÁRIO:
DISTÂNCIA = 103,3m CABO: 2.5mm2-PVC-70ºC(450/750V)
DISTÂNCIA = 118,70m CABO: 4.0mm2-PVC-70ºC(450/750V) DISTÂNCIA = 81,24m CABO: 4.0mm2-PVC-70ºC(450/750V) DISTÂNCIA = 24,80m CABO: 2.5mm2-PVC-70ºC(450/750V)
CORRENTE = 3,14A
CORRENTE = 5,28A CORRENTE = 5,28A CORRENTE = 0,90A V/Akm= 14,3 PREFEITURA MUNICIPAL DE CROMÍNIA - GO
V/Akm= 8,96 V/Akm= 8,96 V/Akm= 14,3
RESPONSÁVEL TÉCNICO:
DV = (V/A . Km) x A x Km
D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km DV = 14,3 x 3,14 x 0,1033 = 4,64 V ENG° CIVIL GIVAGO ARAÚJO VALADARES CREA - GO 1015879675/D
D V = 8,96 x 5,28 x 0,1187 = 5,62V D V = 8,96 x 5,28 x 0,08124 = 3,84V D V = 14,3 x 0,90 x 0,0248 = 0,32 V
DV % = (4,64x 100)/220 = 2,11% AUTOR DO PROJETO:
D V % = (5,62x 100)/220 = 2,55% D V % = (3,84x 100)/220 = 1,75% D V % = (0,32x 100)/220 = 0,15%
2/3
DISTÂNCIA = 8,80m CABO: 2.5mm2-PVC-70ºC(450/750V) DISTÂNCIA = 8,80m CABO: 2.5mm2-PVC-70ºC(450/750V) DISTÂNCIA = 2,10m CABO: 2.5mm2-PVC-70ºC(450/750V)
CORRENTE = 5,45A CORRENTE = 1,10A CORRENTE = 1,10A
V/Akm= 14,3 V/Akm= 14,3 V/Akm= 14,3
ÁREA:
D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km D V = (V/A . Km) x A x Km Área Total do Terreno: 7.478,998 m²
D V = 14,3 x 5,45 x 0,0088 = 0,68V D V = 14,3 x 1,10 x 0,0088 = 0,14V D V = 14,3 x 1,10 x 0,0021 = 0,03 V Área Pavimentada: 2.430,02 m²
D V % = (0,68x 100)/220 = 0,31% D V % = (0,14x 100)/220 = 0,06% D V % = (0,03x 100)/220 = 0,01% VALADARES Área Permeável: 4.023,23 m²
ENGENHARIA
DATA: ESCALA: DESENHO:
FONE: (62) 3636-8075
ABRIL /2019 INDICADA WESLEI RODRIGUES