Você está na página 1de 2

1 BASIC....

GENERATOR AND PHASE


GERADOR E FASE VALUE = 0 DISABLE ( DESABILITA FUNÇÃO GERADOR )
OBS: APENAS MOTOR MARITIMO
2 BASIC PRIMARY ON POWER ( AO LIGAR O CONTROLADOR BOTÃO QUE FICA ATIVO )
0= STOP
1 = MANUAL ( EU DEIXO EM MANUAL )
CRANCK SUCCESS CONDITION ( SINAL USADO PARA O CONTROLADOR SABER QUE O
MOTOR ARRANCOU E DESENGATAR O MOTOR DE PARTIDA
0 = RPM do motor
5 = RPM / OP ( OP= PRESSÃO DO OLEO )
2 BASIC
CRANCK DISCONNET ON OIL PRESSURE (150 KPA ) PRESSÃO DO OLEO PRA DESCONECTAR
O MOTOR DE ARRANQUE REDUNDANCIA CASO FALHE O RPM ( CASO CONDIÇÃO SEJA OP
OU RPM/OP)

3 COUTER COOLANT RUNNING TIME : GRUPO GERADOR 120 SEGUNDOS / MOTOR MARITIMO 0
SEGUNDOS ( AO APERTAR BOTÃO PARADA INICIA RESFRIAMENTO DO MOTOR MAIS UM
SETTING APERTO MOTOR PARA ) ZERO SEGUNDOS MOTOR PARA IMEDIATAMENTE.
AJUSTE DOS
TEMPORIZADOE
S
4 ENGINE OVER SPEED WARNING VALUE = 127 = 1905 RPM AVISO ALTO RPM !!!
MOTOR OVER SPEED VALUE = 129= 1935 RPM ALARME RPM ALTO PARA O MOTOR

# UNDER SPEED WARNING = 027 = 405 RPM AVISO BAIXO RPM MOTOR
# UNDER SPEED VALUE = 025 = 375 RPM CORTA O MOTOR POR BAIXO RPM
# LOW OIL PRESSURE WARNING VALUE = 200 KPA = 2.0BAR AVISO BAIXA PRESSÃO ÓLEO
# LOW OIL PRESSURE ALARM VALUE = 100 KPA = 1.0 BAR ALARME PARADA DO MOTOR
POR BAIXA PRESSÃO DO OLEO.
# HIGH WATER TEMPERATURE WARNING VALUE = 95 GRAUS AVISO ALTA TEMPERATURA
# HIGH WATER TEMPERATURE ALARME VALUE = 98 GRAUS ALARME DE CORTE DO
MOTOR
# OVER BATTERY VOLTAGE WARNING VALUE = 125 – 30.0 V AVISO TENSÃO ALTA BATERIA
# LOW BATTERY VOLTAGE WARNING VALUE = 67 = 16.0 V

8 MAINS MAINS PHASE


REDE FASES DA REDE VALUE = 0 DISABLE (APENAS MOTOR MARITIMO )
B CAN SETTING CAM COMUNICATION TREATY = 8 PERKINS

GUIA DE PARAMETRIZAÇÃO MEBAY DC72D ******* SENHA ACESSO 07623


TABELA 2. SETT PARAMETERS
GUIA DE PARAMETRIZAÇÃO MEBAY DC72D

TABELA 1. FAST PARAMETERS ( acesso rápido )

1 BASIC PARAMETERS

1.1 CAN COMMUNICATION = VALUE 8 PERKINS


1.2 GENERATOR = VALUE 0 DISABLE 0
1.3 PRIMARY CURRENTE ( APENAS GMG )
1.4 RATED FREQUENCY – FREQUENCIA NOMINAL
1.5 RATED PHASE – FASE NOMINAL
1.6 RATED PHASE CURRENT – CORRENTE NOMINAL
1.7 RATED TOTAL POWER – POTENCIA DO GERADOR
1.8 RATED BATTERY – TENSÃO NOMINAL BATERIA 12 OU 24
1.9 RATED RPM – RPM NOMINAL
1.10 RATED IDDLE – MARCHA LENTA NOMINAL
1.11 FLYWHEEL TEETH- DENTES CREMALHEIRA ( APENAS QUANDO USAR PICK-UP)

2 SENSOR SETTING

3.1 OIL PRESSURE SENSOR TYPE = FROM ECU ------- TIPO DE SENSOR USADO
3.2 WATER TEMP. SENSOR TYPE = FROM ECU --------TIPO DE SENSOR USADO
OBS: QUAL SENSOR SERA USADO ? MOTOR ELETRONICO FROM ECU – MOTOR CONVENCIONAL
VERICAR OUTRAS OPÇOES NO MODULO

3.3 PROGRAMABLE SENSOR 1 = WATER TEMPERATURE = CONFIMAR SE NAO ESTIVE PONHA


3.4 PROGRAMABLE SENSOR 2= OIL PRESSURE = CONFIRMAR SE NAO ESTIVER PONHA
OBS: CASO NÃ0 ESTEJA DESTA FORMA PODE SER QUE OCASIONE ERRO DE LEITURA DA ECU DO
MOTOR

OBS: PARA RESTAURAR OS PADROES DE FABRICA APENAS USE A SENHA......

97011

Você também pode gostar