1 Potência P 5500

2 Limite de perda - Monofasicos (3%) 2.0%


3 Distancia Disjuntor-TUG(->) L 36
4 Tensão V 220
5 Resistividade do cobre (STD) 0.0173

6 Seção do fio mm2 S 1.5


7 Resistencia dos Fios de Cobre - seção R 0.415
8 Perda de Tensão no cabo Vf 10.38
9 Tensão Limite de perda (Calculated) Vfio Limit 4.40
10 Current I 25.00
11 Current Limit (Table) I limit 15.5
12 Disjuntor - Valor maior que > 32.5
13 Use/Not Use Current (I) NOT USE
14 Use/Not Use Volts (V) NOT USE

DIMENSIONAMENTOS DE ELETRODUTOS

CABOS (mm²) QUANT. ÁREA


2.50 0.00
4.00 0.00
6.00 0.00
10.00 0.00
16.00 0.00
25.00 0.00
35.00 0.00
50.00 0.00
70.00 0.00
95.00 0.00
120.00
150.00
185.00
240.00 0.00

CABO CAT 6A 0.00

TOTAL 0 0.00
ELETROCALHAS ÁREA
38x38 mm 1,444
50x50 mm 2,500
75x50mm 3,750
100x50mm 5,000
100x75mm 7,500
150x50mm 7,500
200x50mm 10,000
300x75mm 22,500
CÁLCULO DO ELO FUSÍVEL DA CHAVE DO TRANSFORMADOR
TRAFOS CORRENTE ELO FUSÍVEL TIPO K (MAIS RÁPID
75 3.14 5
112.5 4.71 5
150 6.28 10
225 9.41 10
Corrente Calculada Limite de corrente Perda de Tensão Perda Máxima
W 250
120

100 200
m 80
150
V 60
Ω.m 100
40

20 50
0
1.5 2.5 4 6 10 16 25 35 0
1.5 2.5 4 6 10 16

2.5 4 6 10 16
0.249 0.156 0.104 0.062 0.039
6.23 3.89 2.60 1.56 0.97
4.40 4.40 4.40 4.40 4.40
25.00 25.00 25.00 25.00 25.00
21.0 28.0 36.0 50.0 68.0
32.5 32.5 32.5 32.5 32.5
NOT USE OK OK OK OK
NOT USE OK OK OK OK

SIONAMENTOS DE ELETRODUTOS:

qs FATOR (40%) mm² ELETRODUTOS mm


mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm
mm² 0.00 mm² 0.00 mm

mm² 0.00 mm² 0.00 mm


FUSÍVEL TIPO K (MAIS RÁPIDO)
5
5
10
10
Perda de Tensão Perda Máxima de Tensão

2.5 4 6 10 16 25 35

25 35 mm²
0.025 0.018 Ohms
0.62 0.44 %
4.40 4.40 V
25.00 25.00
89.0 111.0 A
32.5 32.5 A
OK OK
OK OK
QUEDA DE TENSÃO DE CABO DE ENTRADA - TABELA 6
ALIMENTADORES - B1
CORRENTE (A) QUEDA V/A.KM
TABELA 6 PIRASTIC TRIFÁSICO CABO EPR
2.5 24.5 14.3
4 28 7.79
6 36 5.25
10 50 3.17
16 68 2.03
25 89 1.33
35 110 0.98 35
50 134 0.76 50
70 171 0.55 70
95 207 0.43 95
120 239 0.36 120
150 275 0.31 150
185 314 0.27 185
240 370 0.23 240
M KM
D (M) = 63.00 0.06
TENSÃO (V) = 220
CABO ESCOLHIDO = 10
QUEDA DE TENSÃO NO CABO ESCOLHIDO 3.17
=
CARGA TOTAL = 14,000

36.78
CORRENTE DE PROJETO TRIFÁSICA (A) =
TEMPERATURA DE 40 GRAUS= 0.77
CORRENTE C/ TEMP. = 47.77

CÁLCULO = 3.34%
CORRENTE (A) QUEDA V/A.KM QUEDA V/A.KM
TRIFÁSICO TRIFÁSICO
14.3
7.79
5.25
3.17
2.03
1.33
144 0.99 0.98
175 0.76 0.76
222 0.56 0.55
269 0.43 0.43
312 0.36 0.36
358 0.31 0.31
408 0.26 0.27
481 0.21 0.23

MONOFÁSICO
220
6

5.25
6,500

29.55

1
29.55

4.44%
QUEDA DE TENSÃO DE CABO DE ENTRADA - NBR 5410
TIPO DE INSTALAÇÃO TIPOS DE LINHAS ELÉTRICAS CONFORM
MÉTODOS DE INSTALAÇÃO 31/32 CARGAS
INSTALAÇÃO EM BADEIJAS PERFURADA B1
QDLF 1º PAV.
QFAC 1º PAV.

CORRENTE (A) QUEDA V/A.KM


TABELA 6 PIRASTIC 750V TRIFÁSICO
35 110 0.98
50 134 0.76
70 171 0.55
95 207 0.43
120 239 0.36
150 275 0.31
185 314 0.27
240 370 0.23
M
D (M) = 65.00
TENSÃO (V) =
CABO ESCOLHIDO =
QUEDA DE TENSÃO NO CABO ESCOLHIDO =
CARGA TOTAL =
CORRENTE DE PROJETO TRIFÁSICA (A) =
TEMPERATURA DE 40 GRAUS=
CORRENTE C/ TEMP. =

CÁLCULO =
A - NBR 5410
NHAS ELÉTRICAS CONFORME NBR 5410
QUEDA DE TENSÃO

CORRENTE (A) QUEDA V/A.KM


CABO EPR TRIFÁSICO
35 144 0.99
50 175 0.76
70 222 0.56
95 269 0.43
120 312 0.36
150 358 0.31
185 408 0.26
240 481 0.21
KM
0.07
380
50
0.76
70,750
107.62

0.77
139.77

1.40%