DATABOOK – USINA FOTOVOLTAICA

USINA RECRIA

Local: Rodovia Lajedo, n° 1000, 55370-000, Zona Rural, São Bento do


Una, Pernambuco

Potência: 143 kWp – 110 kW


Equipamentos: 260 módulos Canadian Solar 550 Wp e 01 inversores
Sungrow 110 kW

Período de Instalação: 07/11/2022 até 05/05/2023


Data Homologação: 05/06/2023
SUMÁRIO

1. ANEXO I – MEMORIAL DESCRITIVO

2. ANEXO II – PROJETO AS BUILT


i. P.E.01 – Alocação dos módulos
ii. P.E.02 – Diagrama Unifilar
iii. P.E.03 – Strings
iv. P.E.04 – Infraestrutura elétrica
v. P.E.05 – Detalhes
vi. P.E.06 – Estrutura Metálica

3. ANEXO III – ART

4. ANEXO IV – DATASHEET DO MÓDULO E


INVERSOR

5. ANEXO V – RELATÓRIO DE COMISSIONAMENTO

6. ANEXO VI – MANUAL DE OPERAÇÃO E


MANUNTENÇÃO

7. ANEXO VII – TERMO DE GARANTIA DOS


EQUIPAMENTOS

8. ANEXO VIII – RELATÓRIO FOTOGRÁFICO

9. ANEXO IX – TERMO DE RECEBIMENTO


ANEXO I
MEMORIAL DESCRITIVO
SUMÁRIO

1. Dados do Sistema

2. Estrutura de Fixação

3. Cabos CC e CA

4. Disjuntores

5. DPS

6. Aterramento
1. Dados do Sistema
O sistema é composto por 260 módulos do fabricante Canadian Solar,
modelo CS6W–550WMS e conectado ao inversor do fabricante
Sungrow, modelo SG110CX.

2. Estrutura de Fixação
A instalação foi realizada em solo, composta pela estrutura metálica do
fabricante SSM, com toda a estrutura devidamente aterrada.

3. Cabos CC e CA
Com base no critério da capacidade de condução e o critério da queda de
tensão, foi concluído que para corrente contínua será usada cabos de 6
mm², e para corrente alternada, foram usados para os cabos de fase 95
mm², neutro 95 mm² e terra 50 mm².

4. Disjuntores
Para a proteção do(s) inversore(s), analisa a corrente nominal do
dispositivo, foi analisada também a corrente nominal de saída do
inversor. Portanto, o disjuntor comercial que mais se adequa ao sistema é
o de 175 A, da marca STECK. E para o disjuntor geral foi usado com
capacidade de corrente 175 A da marca STECK.
5. DPS
A proteção contra sobretensão é feita nos QGBT’s de conexão do sistema.
Foram instalados quatro dispositivos de proteção contra surto da marca
Steck.
6. Aterramento
Para o aterramento, foram utilizadas hastes de aterramento do tipo
Copperweld com cabos de cobre nú de 50 mm² enterrados a uma
profundidade de 70cm e todas partes metálicas estão equipotencializadas.
ANEXO II
PROJETO AS BUILT
ANEXO III
ART
Página 1/2

Anotação de Responsabilidade Técnica - ART


Lei n° 6.496, de 7 de dezembro de 1977 CREA-PE ART OBRA / SERVIÇO
Nº PE20220850722
Conselho Regional de Engenharia e Agronomia de Pernambuco

INICIAL

1. Responsável Técnico
MURILO ALMEIDA DA SILVA FILHO
Título profissional: ENGENHEIRO ELETRICISTA RNP: 1820914720
Registro: 1820914720PE

2. Dados do Contrato
Contratante: NELSON GALVÃO FILHO CPF/CNPJ: 083.524.024-04
AVENIDA BERNARDO VIEIRA DE MELO Nº: 4535
Complemento: APTO 1502 Bairro: CANDEIAS
Cidade: JABOATÃO DOS GUARARAPES UF: PE CEP: 54440620

Contrato: Não especificado Celebrado em:


Valor: R$ 3.000,00 Tipo de contratante: Pessoa Física
Ação Institucional: Outros

3. Dados da Obra/Serviço
RODOVIA LAJEDO Nº: 1000
Complemento: GRANJA LAGOA DO FORTE II Bairro: ZONA RURAL
Cidade: SÃO BENTO DO UNA UF: PE CEP: 55370000
Data de Início: 15/11/2022 Previsão de término: 31/01/2023 Coordenadas Geográficas: 0, 0
Finalidade: Comercial Código: Não Especificado
Proprietário: NELSON GALVÃO FILHO CPF/CNPJ: 083.524.024-04

4. Atividade Técnica
14 - Elaboração Quantidade Unidade
80 - Projeto > ELETROTÉCNICA > SISTEMAS DE ENERGIA ELÉTRICA > #11.9.5 - DE 110,00 kw
MINIGERAÇÃO DISTRIBUÍDA
80 - Projeto > ELETROTÉCNICA > SISTEMAS DE ENERGIA ELÉTRICA > #11.9.24 - DE 1,00 un
ATERRAMENTO ELÉTRICO
80 - Projeto > ELETROTÉCNICA > EQUIPAMENTOS ELÉTRICOS > #11.4.7 - DE PAINEL 1,00 un
ELÉTRICO
16 - Execução Quantidade Unidade
49 - Execução de obra > ELETROTÉCNICA > SISTEMAS DE ENERGIA ELÉTRICA > #11.9.5 - DE 110,00 kw
MINIGERAÇÃO DISTRIBUÍDA
49 - Execução de obra > ELETROTÉCNICA > SISTEMAS DE ENERGIA ELÉTRICA > #11.9.24 - DE 1,00 un
ATERRAMENTO ELÉTRICO
49 - Execução de obra > ELETROTÉCNICA > EQUIPAMENTOS ELÉTRICOS > #11.4.7 - DE PAINEL 1,00 un
ELÉTRICO

Após a conclusão das atividades técnicas o profissional deve proceder a baixa desta ART

5. Observações
ELABORAÇÃO DE PROJETO E EXECUÇÃO DO GERADOR FOTOVOLTAICO CONECTADO À REDE, COMPOSTO POR MÓDULOS,
INVERSORES, QUADRO DE PROTEÇÃO EM CORRENTE ALTERNADA E SISTEMA DE PROTEÇÃO DE CONEXÃO À REDE. ALÉM DE SISTEMA
DE ATERRAMENTO PARA OS COMPONENTES DO GERADOR EM QUESTÃO.

6. Declarações

7. Entidade de Classe
NÃO OPTANTE

8. Assinaturas
Declaro serem verdadeiras as informações acima MURILO ALMEIDA DA SILVA FILHO - CPF: 063.207.544-94

18 OUTUBRO
RECIFE ________ de ___________________ de ________
________________,
2022
Local data NELSON GALVÃO FILHO - CPF: 083.524.024-04

9. Informações
* Conforme Art. 4º da Resolução 1025/2009: O registro da ART efetiva-se após o seu cadastro no sistema eletrônico do CREA e o recolhimento do
valor correspondente

10. Valor

A autenticidade desta ART pode ser verificada em: http://crea-pe.sitac.com.br/publico, com a chave: 4y5c4
Impresso em: 05/10/2022 às 09:10:25 por: , ip: 187.59.117.35

www.creape.org.br creape@creape.org.br
CREA-PE
Conselho Regional de Engenharia
Tel: (81) 3423-4383 Fax: (81) 3423-4383 e Agronomia de Pernambuco
Página 2/2

Anotação de Responsabilidade Técnica - ART


Lei n° 6.496, de 7 de dezembro de 1977 CREA-PE ART OBRA / SERVIÇO
Nº PE20220850722
Conselho Regional de Engenharia e Agronomia de Pernambuco

INICIAL

Valor da ART: R$ 88,78 Registrada em: 04/10/2022 Valor pago: R$ 88,78 Nosso Número: 8304730216

A autenticidade desta ART pode ser verificada em: http://crea-pe.sitac.com.br/publico, com a chave: 4y5c4
Impresso em: 05/10/2022 às 09:10:25 por: , ip: 187.59.117.35

www.creape.org.br creape@creape.org.br
CREA-PE
Conselho Regional de Engenharia
Tel: (81) 3423-4383 Fax: (81) 3423-4383 e Agronomia de Pernambuco
ANEXO IV
DATASHEET DO MÓDULO E INVERSOR
SUMÁRIO

1. Datasheet Módulo

2. Datasheet Inversor
HiKu6 Mono PERC
530 W ~ 550 W
CS6W-530|535|540|545|550MS

MORE POWER

Module power up to 550 W


550 W Module efficiency up to 21.5 %

12
Years
Enhanced Product Warranty on Materials
and Workmanship*
Up to 4.5 % lower LCOE
Up to 5.6 % lower system cost

Linear Power Performance Warranty*


Years
Comprehensive LID / LeTID mitigation
technology, up to 50% lower degradation
1st year power degradation no more than 2%
Subsequent annual power degradation no more than 0.55%

Compatible with mainstream trackers, *According to the applicable Canadian Solar Limited Warranty Statement.

cost effective product for utility power plant


MANAGEMENT SYSTEM CERTIFICATES*
ISO 9001:2015 / Quality management system
ISO 14001:2015 / Standards for environmental management system
Better shading tolerance ISO 45001: 2018 / International standards for occupational health & safety

PRODUCT CERTIFICATES*
MORE RELIABLE IEC 61215 / IEC 61730 / CE / INMETRO / MCS / UKCA
CEC listed (US California)
UL 61730 / IEC 61701 / IEC 62716 / IEC 60068-2-68
UNI 9177 Reaction to Fire: Class 1 / Take-e-way
Minimizes micro-crack impacts

* The specific certificates applicable to different module types and markets will vary,
Heavy snow load up to 5400 Pa, and therefore not all of the certifications listed herein will simultaneously apply to the
products you order or use. Please contact your local Canadian Solar sales representative
wind load up to 2400 Pa* to confirm the specific certificates available for your Product and applicable in the regions
in which the products will be used.

CSI Solar Co., Ltd. is committed to providing high quality solar


products, solar system solutions and services to customers
around the world. Canadian Solar was recognized as the No. 1
module supplier for quality and performance/price ratio in the
IHS Module Customer Insight Survey, and is a leading PV project
developer and manufacturer of solar modules, with over 55 GW
deployed around the world since 2001.
* For detailed information, please refer to the Installation Manual.

CSI Solar Co., Ltd.


199 Lushan Road, SND, Suzhou, Jiangsu, China, 215129, www.csisolar.com, support@csisolar.com
ENGINEERING DRAWING (mm) CS6W-530MS / I-V CURVES
A A

Rear View Frame Cross Section A-A 14 14


13 13
12 12
11 11
6-Ф5
Grounding Hole
32
10 10
9 9
8 8
4-14x9
Mounting Hole 7 7

35
6 6
8-10x7 A A

Mounting hole 5 5
(tracker)
4 4

2261
1155
400
790 3 3
2 2
1 1
Mounting Hole 0 V0 V
5 10 15 20 25 30 35 40 45 50 55 60 5 10 15 20 25 30 35 40 45 50 55 60
R
1089
R 1000 W/m2 5°C
800 W/m2 25°C
14

600 W/m2 45°C

10
180

400 W/m2 65°C


200 W/m2
7
35 1134 9

ELECTRICAL DATA | STC* MECHANICAL DATA


CS6W 530MS 535MS 540MS 545MS 550MS Specification Data
Nominal Max. Power (Pmax) 530 W 535 W 540 W 545 W 550 W Cell Type Mono-crystalline
Opt. Operating Voltage (Vmp) 40.9 V 41.1 V 41.3 V 41.5 V 41.7 V Cell Arrangement 144 [2 x (12 x 6) ]
Opt. Operating Current (Imp) 12.96 A 13.02 A 13.08 A 13.14 A 13.20 A 2261 ˣ 1134 ˣ 35 mm
Dimensions
Open Circuit Voltage (Voc) 48.8 V 49.0 V 49.2 V 49.4 V 49.6 V (89.0 ˣ 44.6 ˣ 1.38 in)
Short Circuit Current (Isc) 13.80 A 13.85 A 13.90 A 13.95 A 14.00 A Weight 27.8 kg (61.3 lbs)
Module Efficiency 20.7% 20.9% 21.1% 21.3% 21.5% Front Cover 3.2 mm tempered glass
Operating Temperature -40°C ~ +85°C Frame Anodized aluminium alloy
Max. System Voltage 1500V (IEC/UL) or 1000V (IEC/UL) J-Box IP68, 3 bypass diodes
TYPE 1 (UL 61730 1500V) or TYPE 2 (UL 61730 Cable 4 mm2 (IEC), 12 AWG (UL)
Module Fire Performance 1000V) or CLASS C (IEC 61730) 410 mm (16.1 in) (+) / 290 mm (11.4
Max. Series Fuse Rating 25 A Cable Length in) (-) (supply additional jumper
(Including Connector) cable: 2 lines / Pallet) or customized
Application Classification Class A length*
Power Tolerance 0 ~ + 10 W Connector T4 series or MC4-EVO2
* Under Standard Test Conditions (STC) of irradiance of 1000 W/m2, spectrum AM 1.5 and cell
Per Pallet 30 pieces
temperature of 25°C.
Per Container (40' HQ) 600 pieces
* For detailed information, please contact your local Canadian Solar sales and
ELECTRICAL DATA | NMOT* technical representatives.
CS6W 530MS 535MS 540MS 545MS 550MS
Nominal Max. Power (Pmax) 397 W 401 W 405 W 409 W 412 W
Opt. Operating Voltage (Vmp) 38.3 V 38.5 V 38.7 V 38.9 V 39.1 V TEMPERATURE CHARACTERISTICS
Opt. Operating Current (Imp) 10.38 A 10.42 A 10.47 A 10.52 A 10.55 A Specification Data
Open Circuit Voltage (Voc) 46.1 V 46.3 V 46.5 V 46.7 V 46.9 V Temperature Coefficient (Pmax) -0.34 % / °C
Short Circuit Current (Isc) 11.13 A 11.17 A 11.21 A 11.25 A 11.29 A Temperature Coefficient (Voc) -0.26 % / °C
* Under Nominal Module Operating Temperature (NMOT), irradiance of 800 W/m spectrum AM 1.5,
2, Temperature Coefficient (Isc) 0.05 % / °C
ambient temperature 20°C, wind speed 1 m/s. Nominal Module Operating Temperature 41 ± 3°C

PARTNER SECTION

* The specifications and key features contained in this datasheet may deviate slightly from our actu-
al products due to the on-going innovation and product enhancement. CSI Solar Co., Ltd. reserves
the right to make necessary adjustment to the information described herein at any time without
further notice.
Please be kindly advised that PV modules should be handled and installed by qualified people who
have professional skills and please carefully read the safety and installation instructions before
using our PV modules.

CSI Solar Co., Ltd.


199 Lushan Road, SND, Suzhou, Jiangsu, China, 215129, www.csisolar.com, support@csisolar.com

June 2021. All rights reserved, PV Module Product Datasheet V1.6_EN


SG110CX New
Multi-MPPT String Inverter for 1000 Vdc System

HIGH YIELD EASY O&M


9 MPPTs with max. efficiency 98.7% Touch free commissioning and remote
Compatible with bifacial module firmware upgrade
Built-in PID recovery function optional Online IV curve scan and diagnosis
Fuse free design with smart string current
monitoring

LOW COST PROVEN SAFETY


Compatible with Al and Cu AC cables IP66 and C5 protection
DC 2 in 1 connection enabled Type II SPD for both DC and AC
Q at night function Compliant with global safety and grid code

CIRCUIT DIAGRAM EFFICIENCY CURVE

100%

98%
MPPT
DC1
(Boost1)
Eff iciency

L1 96%
DC EMI AC AC AC EMI
Filter Filter Relays Filter
L2 94%
Vdc=550V
MPPT L3 92% Vdc=600V
DC9 (Boost9)
N Vdc=850V
90%
Current DC DC SPD DC Bus Inverter Circuit AC SPD PE
Monitoring Switch 88%
(DC/AC)
0% 20% 40% 60% 80% 100%

Normalized Output Power

© 2019 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.2
SG110CX

Type designation SG110CX


Input (DC)
Max. PV input voltage 1100 V
Min. PV input voltage / Startup input voltage 200 V / 250 V
Nominal PV input voltage 585 V
MPP voltage range 200 – 1000 V
MPP voltage range for nominal power 550V – 850 V
No. of independent MPP inputs 9
Max. number of PV strings per MPPT 2
Max. PV input current 26 A * 9
Max. current for input connector 30 A
Max. DC short-circuit current 40 A * 9
Output (AC)
AC output power 110 kVA @ 45 ℃ / 100 kVA @ 50 ℃
Max. AC output current 158.8 A
Nominal AC voltage 3 / N / PE, 400 V
AC voltage range 320 – 460 V  
Nominal grid frequency / Grid f requency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
THD < 3 % (at nominal power)
DC current injection < 0.5 % In
Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / connection phases 3/3
Efficiency
Max. efficiency 98.7 %
Euro. efficiency 98.5 %
Protection
DC reverse connection protection Yes
AC short circuit protection Yes
Leakage current protection Yes
Grid monitoring Yes
Ground fault monitoring Yes
DC switch / AC switch Yes / No
PV String current monitoring Yes
Q at night function Yes
PID recovery function Optional
Overvoltage protection DC Type II / AC Type II
General Data
Dimensions (W*H*D) 1051*660*362.5 mm
Weight 85 kg
Isolation method Transformerless
Ingress protection rating IP66
Night power consumption < 2W
Operating ambient temperature range -30 to 60 ℃ (> 50 ℃ derating)
Allowable relative humidity range (non-condensing) 0 – 100 %
Cooling method Smart forced air cooling
Max. operating altitude 4000 m (> 3000 m derating)
Display LED, Bluetooth+APP
Communication RS485 / Optional: Wi-Fi, Ethernet
DC connection type MC4 (Max. 6 mm² )
AC connection type OT terminal (Max. 240 mm²)
Compliance IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018,
VDE-AR-N 4120:2018, IEC 61000-6-3, EN 50438, AS/NZS 4777.2:2015, CEI 0-21,
VDE 0126-1-1/A1 VFR 2014, UTE C15-712-1:2013, DEWA
Grid Support Q at night function, LVRT, HVRT,active & reactive power control and power
ramp rate control

© 2019 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.2
ANEXO V
RELATÓRIO DE COMISSIONAMENTO
COMISSIONAMENTO

INVERSOR 01 DJ200A
S/N:
CONDIÇÕES CLIMÁTICAS: NUBLADO

 TESTE DE STRINGS – DATA: 27/04/2023


HORÁRIO DE INÍCIO/FIM: 8:07h

VOC (V) VOC (V)


MÓDULOS MPPT RISO + (MΩ) RISO - (MΩ)
TEÓRICO MEDIDO

STRING 01 1 647 145 120


STRING 02 1 643 123 132
STRING 03 2 642 57,2 155
STRING 04 2 645 187 149
STRING 05 3 643 130 87,2
STRING 06 3 643 85 150
STRING 07 4 691 116 114
STRING 08 4 693 122 48,9
STRING 09 5 643 115 107
STRING 10 5 646 49,9 54
STRING 11 6 691 184 191
STRING 12 6 694 128 126
STRING 13 7 644 100 70,5
STRING 14 7 643 155 65,9
STRING 15 8 689 57,6 61,6
STRING 16 8 689 114 42,5
STRING 17 9 688 60,9 195
STRING 18 9 691 118 112
TESTES INICIAIS
ITEM OBSERVAÇÃO
POLARIDADE OK
CONTINUIDADE DO CONDUTOR DE EQUIPOTENCIALIZAÇÃO OK
APERTO DOS TERMINAIS DOS DISJUNTORES OK
FUNCIONAMENTO DOS DISJUNTORES OK
PENDENTE
CONTINUIDADE DE TODAS AS PARTES METÁLICAS
ELETROCALHA
CONTINUIDADE ATERRAMENTO DAS MESAS OK

TENSÕES C.A.
MEDIÇÃO VALORES
R-N 223,2
S-N 222,3
T-N 222,2
R-S 385,8
R-T 384,7
S-T 383,7

TESTES OPERACIONAIS
ITEM OBSERVAÇÃO
SECCIONADORES OK
TESTES DE FUCIONAMENTO DOS
INVERSORES
OK
TESTES DE DESCONEXÃO E RECONEXÃO
À REDE
OK
TESTE DE MONITORAMENTO SEM INTERNET
INSPEÇÃO GERAL
ITEM OBSERVAÇÃO
PLACA “GERAÇÃO PRÓPRIA” OK
CERCAS OK
PORTÃO OK
FECHADURA NSA
POSTE PE OK
MÓDULOS +/- SUJOS
CONEXÕES OK
FIXAÇÃO DOS MÓDULOS OK
ESTRUTURA OK
CABOS - INTEGRIDADE OK
CABOS IDENTIFICAÇÃO FITAS
CAIXAS DE PASSAGEM OK
CAIXAS DE ATERRAMENTO OK
HASTES, CONECTORES E CABOS DE
OK
ATERRAMENTO
SOLO E DRENAGEM NSA
QUADRO ELÉTRICO OK
QUADRO DE TELECOM NSA
CONEXÃO COM A INTERNET PENDENTE
CASA/ABRIGO DO INVERSOR OK
ILUMINAÇÃO OK
INSTALAÇÃO DOS MC4 OK
ANEXO VI
MANUAL DE OPERAÇÃO E
MANUNTEÇÃO
1. Programa de manutenção preventiva e preditiva
Será oferecido um guia com o objetivo de orientar as práticas de
operação e manutenção do sistema fotovoltaico instalado, a fim de que
seja preservada a integridade do sistema, avaliando periodicamente o
funcionamento dos seus componentes.

2. Informações de operação e manutenção


a. Checklist dos procedimentos a serem seguidos em
caso de falha do GFV
 Verificar no display do Inversor se ele está desligado ou
está indicando algum erro. Caso haja um erro no inversor,
identifique-o, utilizando o código de erros do manual do
inversor, caso possua essa informação.
 Desligar a chave seccionadora de corrente contínua e o
disjuntor de corrente alternada.
 Verificar as conexões dentro dos quadros: se há cabos
soltos, etc. Prestar atenção se há cheiro de queimado
vindo dos quadros elétricos ou próximo ao inversor.
Verificar se há indícios de fogo ou faísca elétrica (ex.:
marcas carbonizadas). Verificar se há alguma ligação de
cabeamento solta, tanto C.C. quanto C.A.
 Verificar a tensão do arranjo fotovoltaico. Considerar a
Temperatura de operação dos módulos. Se não há tensão,
há um problema com a ligação dos cabos no arranjo
fotovoltaico.
 Comparar a tensão dos módulos com a tensão mínima de
entrada do inversor interativo. Caso a tensão dos módulos
esteja fora da faixa de tensão do inversor, o
dimensionamento entre módulos fotovoltaicos e inversor
interativo não foi o adequado.
 Ligar o disjuntor de corrente alternada e verificar se a
tensão da rede é igual à tensão nominal do inversor
interativo. Verificar no ponto de ligação do inversor
interativo.
 Ligar o disjuntor de corrente contínua e verificar se a
chave seccionadora no inversor está ligada e verificar se
o inversor inicia.
 Caso não haja falha, tanto no lado de corrente contínua
(tensão dos módulos normal) quanto no lado da rede
(tensão nominal da rede), é necessário contatar um
técnico ou entrar em contato com fabricante/fornecedor
do inversor interativo.

b. Procedimentos para desligamento de emergência


No caso de uma emergência, basta desativar o disjuntor de
corrente alternada e/ou o a chave seccionadora de corrente
contínua. O inversor interativo vai desligar e a corrente para de
circular no arranjo fotovoltaico. Nunca puxe os cabos que conduzem
corrente, sempre utilize os dispositivos de seccionamento, chave e/ou
disjuntor. Quando os módulos estão iluminados, sempre há uma
tensão entre as extremidades (polos positivos e negativos) do arranjo
fotovoltaico.

c. Recomendações de limpeza e manutenção dos


equipamentos da GFV
Com o tempo, sujeira e poeira podem se acumular na superfície
dos módulos, o que causa uma redução da potência. Para manter o
máximo da capacidade do sistema, é recomendável uma limpeza
periódica dos módulos fotovoltaicos, especialmente em regiões com
pouca chuva, ou excesso de partícula suspensas (poluição, poeira,
queimadas, etc.).
Para diminuir o risco para choques térmicos, é recomendado
limpar os módulos de manhã, cedo; ou no final da tarde quando a
irradiância solar é baixa, e os módulos estão mais frios. Nunca tente
limpar módulos com vidro quebrado, ou indicações de cabeamento
danificado, pois existe o risco de choque elétrico.
Limpe a superfície dos módulos com uma escova macia, água
limpa. Água que contém uma alta quantidade de minerais não é
recomendado porque deixa um acúmulo desses na superfície do vidro.
ANEXO VII
TERMO DE GARANTIA DOS
EQUIPAMENTOS
SUMÁRIO

1. Termo de Garantia Módulo

2. Termo de Garantia Inversor


ANEXO VIII
RELATÓRIO FOTOGRÁFICO
Figura 1 – Foto Usina
Figura 2 – Casa dos Inversores
ANEXO IX
TERMO DE RECEBIMENTO
TERMO DE RECEBIMENTO
ADQUIRINTE: Nelson Galvão Filho / 083.524.024-04

ENDEREÇO: Rodovia Lajedo, n° 1000, 55370-000, Zona Rural, São Bento do Una,
Pernambuco

USINA GFV: Gerador Fotovoltaico composto por 260 módulos, modelo CS6W –
550WMS, do fabricante Canadian, totalizando uma potência de 143 kWp, conectado em
01 inversor, modelo SG110CX, do fabricante Sungrow, totalizando uma potência
nominal de 110 kW.

DECLARAÇÃO: Pelo presente instrumento, o ADQUIRINTE acima qualificado,


após vistorias realizadas, declara, neste ato, ter recebido os anexos citados e que a Usina
de Geração Fotovoltaica supracitada, encontra-se em pleno funcionamento, razão pela
qual afirma estar satisfeito o objeto do instrumento contratual de compra e venda do
gerador fotovoltaico firmado entre as Partes, no que diz respeito à venda do bem.

ANEXOS:
 MEMORIAL DESCRITIVO;
 PROJETO AS BUILT;
 ART;
 DATASHEET DOS MÓDULOS E INVERSORES;
 RELATÓRIO DE COMISSIONAMENTO;
 TERMOS DE GARANTIAS DOS EQUIPAMENTOS;
 RELATÓRIO FOTOGRÁFIO;
Logo, assinam este “Termo de Recebimento”, para que surtam seus efeitos jurídicos e
legais.

RECIFE, 01 de setembro de 2023.

__________________________ __________________________
NELSON GALVÃO FILHO TR Energia Solar LTDA
CPF: 083.524.024-04 CNPJ: 46.840.210/0001-99