QUADRO DE DISTRIBUIÇÃO

TOTAL
POT.(W) 128000
In. (A) 211.39
FP 0.92
FASE A FASE B FASE C

CORRENTE Nº FASE CIR. POTÊNCIA


581.82 3 1 128000 42666.66667
581.82 3 3 128000 42666.66667
581.82 3 5 128000 42666.6666667
0.00 1 7 0 0
0.00 1 9 0 0
0.00 1 11 0 0
0.00 1 13 0 0
0.00 1 15 0 0
0.00 1 17 0 0
0.00 1 19 0 0
0.00 1 21 0 0
0.00 1 23 0 0
0.00 1 25 0 0
0.00 1 27 0 0
0.00 1 29 0 0
0.00 1 31 0 0
0.00 1 33 0 0
0.00 1 35 0 0
0.00 1 37 0 0
0.00 1 39 0 0
0.00 1 41 0 0

42666.66667 42666.66667 42666.6666667


PROIBIDO
42666.67
42666.67
ÃO

BALANÇO 100% - CARREGAMENTO DO CABO EM %


CABO (mm²) 185 68.19%
DISJ. (A) 300
Icc. (KA) 10 OBS: Utilizar secção de cabo e disjuntor mínimo recomendado

POTÊNCIA CIR. Nº FASE CORRENTE


0 2 1 0.00
0 4 1 0.00
0 6 1 0.00
0 8 1 0.00
0 10 1 0.00
0 12 1 0.00
0 14 1 0.00
0 16 1 0.00
0 18 1 0.00
0 20 1 0.00
0 22 1 0.00
0 24 1 0.00
0 26 1 0.00
0 28 1 0.00
0 30 1 0.00
0 32 1 0.00
0 34 1 0.00
0 36 1 0.00
0 38 1 0.00
0 40 1 0.00
0 42 1 0.00
mínimo recomendado
CALCULO DA SECÇÃO PELA
QUEDA DE TENSÃO
MONOFÁSICA TRIFÁSICA
K= 200.0 173.2
Dist.(m) = 0 70
Corren.(A) = 0 21
Q.T.(%) = 4 2
Permis. = 56 56
Tensão (V) = 220 380
S (mm²) = 0.00 5.98

OBS: Queda de tensão máxima permitida apartir do ponto de alimentação é d

CABOS ELÉTRICOS CORRENTE (A) DISJUNTOR (A) Icc. (KA)


1.50 15.5 13 3
2.50 21 20 3
4.00 28 25 3
6.00 36 32 3
10 50 50 3
16 68 63 3
25 89 80 6
35 111 100 6
50 134 125 6
70 171 160 6
95 207 200 10
120 239 225 10
150 272 250 10
185 310 300 10
240 364 350 10
300 419 400 10
400 502 500 10
500 578 CONSULTAR 10

O NIVÉL DE CURTO-CIRCUITO PODE SER DIFERENTE


DEPENDENDO DA APLICAÇÃO, ESTE É PARA APLICAÇÕES PREDIAIS.
CALCULO DE QUEDA DE TENSÃO
QUADROS TÉRREO CARGA (W)
PELA DISTÂNCIA
MONOFÁSICA TRIFÁSICA QDLT.TER(01) 28011
K= 200.0 173.2 QDLT.TER(02) 32980
Dist.(m) = 0 0 QDLT.TER(03) 22172
Corren.(A) = 0 0 QDLT.TER(04) 33105
Secção (mm²) = 2.5 0 QDLT.TER(05) 25902
Permis. = 56 56 QDLT ESCADA 1068
Tensão (V) = 220 380 QF.ARC-TER(01) 3200
Q. T. = 0.000% #DIV/0! QF.ARC-TER(02) 7200
QF.ARC-TER(03) 11746
artir do ponto de alimentação é de 7% QF.CENTRAL DE RESIDUOS 89510
QF.LAVANDERIA 44051
QF.AUTOCLAVE 128000
QF.CHILLER 895200
QB.RECAL 5520
ILUM.EXTERNA 01 5620
ILUM.EXTERNA 02 4594
ILUM.EXTERNA 03 2709

QUADROS 1°PAVIMENTO CARGA (W)

QDLT-1PAV(Á.TÉCNICA) 7424
QDLT-1PAV(01) 31153
QDLT-1PAV(02) 26308
QDLT-1PAV(03) 10656
QF.ARC-1PAV(01) 3200
QF.ARC-1PAV(02) 3050
QF.ARC-1PAV(03) 4400
QF.ARC-1PAV(04) 4400
QF.ARC-1PAV(05) 5500
QF.ARC-1PAV(06) 3700
QF.ARC-1PAV(07) 27100
QF.ARC-1PAV(08) 21500
QF.IT.MÉDICO 79500
QUADROS 2°PAVIMENTO CARGA (W)

QDLT-2PAV(01) 32896
QDLT-2PAV(02) 28749
QF.ARC-2PAV(01) 3200
QF.ARC-2PAV(02) 3050

QUADROS 2°PAVIMENTO CARGA (W)

QD.BARRILETE 740
ELEVADOR 1
ELEVADOR 2
FIAÇÃO ELÉTRICA OCUPAÇÃO
CORRENTE (A) DISTÂNCIA(m) Q.T -DISTÂNCIA
(fase-mm²) CABO
46.26 35 64.72 0.70
54.47 25 120.17 2.13
36.62 35 120.65 1.03
54.67 25 103.27 1.84
42.78 25 119.33 1.66
1.76 2.5 102.5 0.59
5.28 4 102.76 1.10
11.69 4 119.2 2.84
19.4 6 119.69 3.15
147.82 70 0.00
72.75 50 0.00
211.39 185 43.73 0.41
0 0 40.86 #DIV/0!
9.13 4 63.35 1.18
9.28 6 136.9 1.72
7.59 6 12.69 0.13
6.85 6 12.69 0.12

FIAÇÃO ELÉTRICA
CORRENTE (A) DISTÂNCIA(m) Q.T -DISTÂNCIA Q.T-SEÇÃO
(fase-mm²)
12.27 6 131.94 2.20
53.1 35 118.55 1.46
43.45 25 102.94 1.46
17.6 10 141.84 2.03
5.28 6 117.75 0.84
5.04 6 100.94 0.69
7.28 6 135.88 1.34
7.28 6 139.68 1.38
9.09 6 122.79 1.51
6.11 6 123.64 1.02
44.75 25 129.99 1.89
35.51 16 130.72 2.36
131.4 120 142.9 1.27
FIAÇÃO ELÉTRICA
CORRENTE (A) DISTÂNCIA(m) Q.T -DISTÂNCIA Q.T-SEÇÃO
(fase-mm²)
54.33 35 124.85 1.58
47.48 25 107.55 1.66
5.28 4 126.59 1.36
5.04 4 108.55 1.11

FIAÇÃO ELÉTRICA
CORRENTE (A) DISTÂNCIA(m) Q.T -DISTÂNCIA Q.T-SEÇÃO
(fase-mm²)
1.22 4 140.91 0.15
TRANSFORMAÇÃO
DE COORDENADAS
GRAUS MINUTOS SEGUNDOS
42 13 1.23
RESUL. GRAUS 42.21700833
RESUL. MINUTOS 2533.02050000
RESUL. SEGUNDOS 151981.23000000
CABOS ELÉTRICOS CORRENTE (A) DISJUNTOR (A) Icc. (KA) CÁLCULO
1.5 15.5 13 3
2.5 21 20 3
4 28 25 3
6 36 32 3
10 50 50 3
16 68 63 3
25 89 80 6
35 111 100 6
50 134 125 6
70 171 160 6
95 207 200 10
120 239 225 10
150 272 250 10
185 310 300 10 310 300 10
240 364 350 10
300 419 400 10
400 502 500 10
500 578 CONSULTAR 10
310 300 10
LO

0.68

0.6819