FIRE PREVENTION DEPARTMENT

GENERAL DIRECTORATE OF CIVIL DEFENCE


MINISTRY OF INTERIOR, STATE OF QATAR

APPROVING AUTHORITY

PS NUMBER : -

E.O.L.R E.O.L.R E.O.L.R

21/Z1 s 21/Z2 s 21/Z5 s CONSULTANT'S ENDORSEMENT FOR DETECTION AND ALARM SYSTEM:
E.O.L.R

I ENG'R. SAID ABDEL AZIZ ABDEL WAHED an ELECTRICAL ENGINEER with UPDA Registration No. 3994,
20/Z1 s 20/Z2 s 20/Z5 s 20/Z6 s as Grade A,being the Consultant hereby certify that the fire safety works shown on these plans has been
designed in accordance with the provisions of
NFPA 170 / 72/70/101 AND 5000 (2012 EDITION ) and local fire safety codes or standards being imposed by
19/Z1 s 19/Z2 s 19/Z5 19/Z6 s
E.O.L.R Qatar Civil Defence.
Further, I certify that I am fully aware and commit myself responsible to this project and the conditions
18/Z1 s 18/Z2 s 18/Z4 s 18/Z5 s 18/Z6 s prescribed under the existing Law No. 19 of 2005,The Law Regulating the Practice of Engineering Profession in
the State of Qatar.
Affixed is my signature to attest to the above undertaking.
17/Z1 s 17/Z2 s 17/Z4 s 17/Z5 s 17/Z6 s

16/Z1 s 16/Z2 s 16/Z4 s 16/Z5 s 16/Z6 s

15/Z1 s 15/Z2 s 15/Z4 s 15/Z5 s 15/Z6 s

14/Z1 s 14/Z2 s 14/Z4 s 14/Z5 s 14/Z6 s

13/Z1 s 13/Z2 s 13/Z4 s 13/Z5 s 13/Z6 s ENG. SAID ABDEL AZIZ ABDEL WAHED
AL-KASHAF INTERNATIONAL FOR DESIGN & ENGINEERING CONSULTANTS
P.O.Box : 24693 , DOHA , QATAR.
Tel : 44 14 77 29 Fax : 44 14 77 27
12/Z6 s E-mail : info@alkashafqatar.com
12/Z1 s 12/Z2 12/Z4 s 12/Z5 s

11/Z1 s 11/Z2 s 11/Z4 s 11/Z5 s 11/Z6 s CONSULTANT SIGNATURE

10/Z1 s 10/Z2 s 10/Z4 s 10/Z5 s 10/Z6 s UPDA reg. No./ Grade : 3994/A QATAR ID No. : 25381801945
9/Z1 s 9/Z2 s
E.O.L.R
9/Z4 s 9/Z5 s 9/Z6 s Validity : 04/09/2020 Validity: 09/06/2018
8/Z1 s 8/Z2 s 8/Z3 8/Z4 s 8/Z5 8/Z6 s CONSULTANT:

7/Z1 s 7/Z2 s 7/Z3 s 7/Z4 s 7/Z5 s 7/Z6

6/Z1 6/Z2 s 6/Z3 6/Z4 6/Z5 s 6/Z6 s AL-KASHAF INTERNATIONAL FOR


DESIGN & ENGINEERING CONSULTANCY
5/Z1 s 5/Z2 s 5/Z3 s 5/Z4 s 5/Z5 s 5/Z6 s TEL: +974 44 14 77 29,
FAX: +974 44 14 77 27
P.O.BOX : 24693
4/Z1 s 4/Z2 s 4/Z3 4/Z4 s 4/Z5 s 4/Z6 s
DOHA,QATAR

3/Z1 s 3/Z2 s 3/Z3 s 3/Z4 s 3/Z5 s 3/Z6 s

2/Z1 s 2/Z2 2/Z3 s 2/Z4 s 2/Z5 s 2/Z6 s

1/Z1 s 1/Z2 s 1/Z3 1/Z4 s 1/Z5 s 1/Z6


UPDA reg. No./ Grade : 203/A QATAR ID No. : 13 7662 00
Validity : 12/01/2019 Validity: 20/12/2018
2X1.5mm
FIRE RESISTANT CABLE BUILDING OWNER:
FIRE RESISTANT CABLE
NASSER RASHID S. AL- KAABI
ZONE-1 ZONE-2 ZONE-3 ZONE-4 ZONE-5 ZONE-6 INTERFACING SOUNDER
TENANT:
6 ZONES CONVENTIONAL FIRE ALARM PANEL (FACP) WITH BUILT 14 AH IN BATTERY
& BATTERY CHARGER (SEALED LEAD ACID,MINIMUM 24 HOURS DURATION BATTERY WELLNESS CLINIC
BACKUP,30 MINUTES FOR ALARM
PROJECT TITLE:
3L x 2.5mm2
FIRE RESISTANT CABLE
CAMS 13 AMPS UNSWITCHED SPUR UNIT CONVERTING EXISTING VILLA INTO
WITH 5 AMPS FUSE
CENTRALIZED ALARM MONITORING
SYSTEM
WELLNESS CLINIC
IN GF, 1ST & 2ND FLOOR
GALVANIZED STEEL JUNCTION BOX
GALVANIZED STEEL JUNCTION BOX
AT AL HILAL
FIXED TO CEILING
EXPOSED MOUNTING FIXED TO WALL Ø25mm GI CONDUIT OCTAGONAL JUNCTION BOX Ø25mm GI CONDUIT
OCTAGONAL JUNCTION EXPANSION/ANCHOR BOLT EXPOSED MOUNTING Ø100mmx50 DEEP (TYP.) CONCRETE SLAP
SLAB BOX Ø6mm (TYPICAL) SLAB
100x100x50mm DEEP (TYP.)
LOCATION : AL HILAL PIN : 71400143
25mm CONDUIT (GALY)
GI CONDUIT (Ø25mm)

FROM OTHER TO OTHER


GI CONDUIT
FALSE CEILING
EXIT 25mm CONDUIT
FIXED BY 2No. 1 1/2"x8"
R/HD SCREWS AND PLASTIC PLUGS
LUMINAIRE LUMINAIRE
ROOF SCREED
Ø 25 mm PVC CONDUIT PVC ADAPTOR AND BUSHING
THROUGH BOX WITH
FIRE RESISTANCE CABLE
FP 200
AREA : 71 STREET : XX PLOT : XX
EMBEDDED IN WALL
BACK OUTLET
WALL OR CEILING MOUNTED EXIT SIGN, DOUBLE
SOFITOF THE CEILING Ø25mm EMBEDED PVC CONDUIT
SIDED, WITH 2*8W FLUORESCENT LAMPS,
25mm CONDUIT (GALY) FIRE RESISTANCE CABLE
GALVANIZED STEEL
FALSE CEILING TILES
100x100x50mm
100x100x50mm
JUNCTION BOX FOR COMPRESSION GLAND DRAWING TITLE:
FP 200
THREADED ROD
BACK BOX FOR
EXIT EMERGENCY LIGHTING
MAINTAINED TYPE, (IP 20).
FLEXIBLE METAL CONDUIT
FALSE CEILING EMERGENCY CIRCUIT ABOVE
LIGHTING IN DOOR FALSE CEILING CONSTRUCTION :
SMOKE OR HEAT DETECTOR FLUSH MOUNTED 2300
LIQUID TIGHT BODY MADE OF WHITE EPOXY POWDER
ON FALSE CEILING

COMPRESSION GLAND
25mm CONDUIT
THROUGH BOX WITH
BACK OUTLET FLEXIBLE METAL CONDUIT
FLEXIBLE (PVC)
CONDUIT (Ø25mm)

SOUNDER FIXED ON WALL


FRONT VIEW
COATED SHEET STEEL WITH TWO OPAL
FACES, COMPLETE WITH CONTROL GEAR.
RGS SHROUD FIRE ALARM SYSTEM SCHEMATIC
RECESSED TYPE AT 2300MM FROM F.F.L
CONDUIT BOX DETECTOR BASE

AS BUILT
LIGHTING FIXTURE
EXTENSION RING
CONCRETE SLAB

EXPANSION/ANCHOR BOLT 1200 ABOVE CEILING


Ø6mm PULL DOWN
DOOR JAMB SMOKE OR HEAT DETECTOR
RGS SHROUD (SECTION) FIRE

CEILING TILE FRONT VIEW


GALVANIZED STEEL
THREADED ROD BREAK GLASS FIXED ON WALL
DETECTOR BASE Ø6mm AT 1200MM FROM F.F.L

EXPANSION/ANCHOR BOLT DETAIL CEILING TILE

SMOKE OR HEAT DETECTOR


F.F.L
BELLOW CEILING
LED INDICATOR LAMP REV. PROJECT NO.: DWG. NO.
SMOKE OR HEAT DETECTOR
00 C356-P4896 D-E-FA-0501

DETAIL NO SCALE : DETAIL NAME : TYPICAL ARRANGEMENT OF SMOKE AND DETAIL NO SCALE DETAIL NAME INSTALLATION RECESSED TYPE EMERGENCY LIGHTING FIXTURE DETAIL NO SCALE : DETAIL NAME : DETAIL NO SCALE DETAIL NAME DETAIL NO : SCALE: DETAIL NAME : DETAIL NO SCALE : DETAIL NAME : TYPICAL ARRANGEMENT OF SMOKE DATE : SCALE : SIZE: SHEET NO.:
(1) N.T.S. HEAT DETECTOR RECESSED (2) N.T.S. WITH EMBEDDED CONDUIT (3) N.T.S. DETAILS FOR CONNECTION OF SOUNDER AND BREAK GLASS STATIONS (4) N.T.S. EMERGENCY LIGHTING (EXIT) ABOVE DOOR. (5) N.T.S. DETAILS FOR EXIT SIGN (6) N.T.S. DETECTOR ABOVE CEILING WITH INDICATOR LAMP
25-03-2018 N.T.S A2 6/6