LEGENDA DETECÇÃO E ALARME DE INCÊNDIO
FIRE ALARM LEGEND
DETECÇÃO E ALARME DE INCÊNDIO - CORES
FIRE ALARM COLORS

A DETECÇÃO - LAÇO / EQUIPAMENTOS | FIRE ALARM - LOOP/EQUIPMENTS A

INFRAESTRUTURA - FONTE AUXILIAR | POWER SUPPLY INFRASTRUCTURE

INFRAESTRUTURA PREVISTA PARA O SISTEMA DE DETECÇÃO POR ASPIRAÇÃO


INFRASTRUCTURE PROVIDED FOR ASPIRATION DETECTION SYSTEM

SIMBOLOGIA DETECÇÃO E ALARME DE INCÊNDIO


FIRE ALARM SIMBOLOGY
CENTRAL DE DETECÇÃO E ALARME DE INCÊNDIO
FIRE ALARM CONTROL PANEL
FONTE AUXÍLIAR
POWER SUPPLY
CENTRAL DE DETECÇÃO DE FUMAÇA POR ASPIRAÇÃO | VESDA - h= 1,5 metros
VERY EARLY SMOKE DETECTION APPARATUS | VESDA - h= 1,5 meters
DETECTOR DE FUMAÇA ENDEREÇÁVEL
ADDRESSABLE SMOKE DETECTOR
DETECTOR DE FUMAÇA ENDEREÇÁVEL INSTALADO NO ENTREFORRO
B ADDRESSABLE SKOME DETECTOR BETWEEN LINING
B
DETECTOR TERMOVELOCIMÉTRICO ENDEREÇÁVEL
ADDRESSABLE THERMAL HEAT DETECTOR
DETECTOR TÉRMICO ENDEREÇÁVEL
ADDRESSABLE HEAT DETECTOR
DETECTOR MULTICRITÉRIO ENDEREÇÁVEL
ADDRESSABLE MULTI-CRITERIA DETECTOR | SMOKE + THERMAL HEAT
DETECTOR DE FUMAÇA PARA DUTOS DE HVAC ENDEREÇÁVEL
DFD
AV
ADDRESSABLE DUCT SMOKE DETECTOR
ACIONADOR MANUAL
MANUAL PULL STATION
AVISADOR AUDIO-VISUAL
AV
HORN AND STROBE
PAINEL ELÉTRICO PARA INSTALAÇÃO DE MÓDULOS
MM | MC CONFORME INDICADO EM PROJETO (MC E/OU MM) - h=1,5 METROS
PANEL ELECTRIC PANEL FOR MODULE INSTALLATION AS INDICATED IN THE PROJECT (MC
AND/OR MM) - h=1.5 METERS
C MÓDULO MONITOR C
MM
MONITOR MODULE
MÓDULO COMANDO
MC
CONTROL MODULE

MÓDULO RELÉ
MR
RELAY MODULE

MÓDULO ZONA
MZ
ZONE MODULE

AVISADOR AUDIOVISUAL DE CHAMADA DE EMERGÊNCIA PARA BANHEIRO PNE.

MCAV
h=ACIMA DA PORTA DE ENTRADA DO BANHEIRO
M-01
M-06
EMERGENCY HORN STROBE FOR W.C. DDA
h=ABOVE THE W.C. ENTRANCE DOOR

Bending Marks
MM
BOTÃO DE CHAMADA DE EMERGÊNCIA PARA BANHEIRO PNE - h=0,4 METROS

MR
GERÊNCIA
M-05 (CLIENTE) SALA DE REUNIÃO (CLIENTE)
EMERGENCY BUTTON FOR W.C. DDA - h=0.40 METERS

MM PANEL PAINEL DE MÓDULOS MONITORES PARA O VESDA + FONTE DE ALIMENTAÇÃO DEDICADA AO VESDA +
D CENTRAL DE DETECÇÃO DE FUMAÇA POR ASPIRAÇÃO D
MODULE PANEL FOR VESDA + VESDA POWER SUPPLY + VERY EARLY SMOKE DETECTION
CORREDOR TÉCNICO MECÂNICA 01

INFRAESTRUTURA

AVMC
M-01
INFRASCTRUCTURE
COPA (CLIENTE)
MM | MC MM | MC ELETRODUTO DE AÇO GALVANIZADO ELETROLITICAMENTE
PANEL M-02 PANEL M-02
ELECTROLYTICALLY GALVANIZED STEEL ELECTRODUCT

PLENUM DE VENTILAÇÃO ELETRODUTO DE PVC ENTERRADO NO SOLO


PVC ELECTRODUCT BURIED IN THE GROUND
M-05 M-06
M-05
M-05 M-01
TUBO FLEXÍVEL CORRUGADO EM PEAD (POLIETILENO DE ALTA DENSIDADE)
M-06 M-05 M-06 M-05 M-06 M-06 M-05
M-06 M-06 PEAD CORRUGATED FLEXIBLE TUBE (HIGH DENSITY POLYETHYLENE)
MR MM MR MM MR MM MR MM MR MM MR MM MR MM
M-05 AVMC
NOTAS
NOTES
1 - ELETRODUTO SEM INDICAÇÃO CONSIDERAR Ø1";
E 2 - ATERRAR TODAS AS INFRAESTRUTURAS METÁLICAS;
E
ESCRITÓRIO (CLIENTE)
M-07 3 - A FIXAÇÃO DE ELETRODUTOS DEVEM SER A CADA 2 METROS;
W.C. PCD
M-08 4 - NA REALIZAÇÃO DE PERFURAÇÃO EM PAREDES E/OU LAJES, É OBRIGATÓRIA A SUBSTITUIÇÃO DA PROTEÇÃO
PASSIVA CONTRA INCÊNDIO;
5 - O INSTALADOR DA INFRAESTRUTURA DEVE FORNECER ARAME GUIA PARA TODA A INFRAESTRUTURA SECA,

MM
MC
DESTINA A INSTALAÇÃO DO SISTEMA;
6 - O PROJETO ESTÁ DE ACORDO COM A NFPA 72 E NFPA 76;
7 - TODOS OS CIRCUITOS SÃO NAC (CIRCUITO DE APARELHO DE NOTIFICAÇÃO) E DEVEM SER SUPERVISIONADOS POR
RESISTORES EOL (END OF LINE);
W.C. FEM. 8 - DEVE SER CONSIDERADO UM MÓDULO ISOLADOR A CADA 20 DISPOSITIVOS ENDEREÇÁVEIS CONFORME INDICADO
PELO FABRICANTE;
M-14 9- TODOS OS DIPOSITIVOS EM ÁREAS EXTERNAS DEVEM TER GRAU PROTEÇÃO IP 56.
MM

CIRCULAÇÃO 10 - AS CENTRAIS DE ASPIRAÇÃO SÃO DESTINADAS A DETECÇÃO NO RETORNO DAS MÁQUINAS DE AR CONDICIONADO
ESPECIFICADAS PELOS PROJETOS DE AR CONDICIONADO.
11 - A CONTRATADA DEVERÁ FORNECER PROJETOS, DIAGRAMAS COM AS DISTRIBUIÇÕES FINAIS DE LAÇO, DETALHES
CONSTRUTIVOS E CÁLCULO/DIMENSIONAMENTO DE CADA CENTRAL DE ASPIRAÇÃO PARA APROVAÇÃO DA SCALA.
12 - PARA CADA FUNÇÃO DOS MÓDULOS ALOCADOS EM PROJETO, VER TABELA "TAG'S"
MCAV
13 - DEVERÁ SER CONSIDERADO MÓDULO RELÉ E MONITOR PARA TODOS OS DAMPERS CORTA-FOGO ALOCADOS EM
MR

M-05
M-01 PROJETO.
MM

W.C. MASC.
MM | MC
PANEL

M-06 14 - OS ACIONADORES PNE SÃO DE RESPONSABILIDADE DO PROJETO DE ARQUITETURA, ESTÁ APENAS DESTACADO
EM PROJETO, O INSTALADOR DEVERÁ COMPATILIBILIZAR A ALOCAÇÃO DELES COM A INFRAESTRUTURA DESTINADA A
F SHAFT ELE./SIST. INTEGRAÇÃO COM O MÓDULO MONITOR E O MÓDULO DE COMANDO. F
ESCADA DH
M-03
1 - CONDUITS WITHOUT INDICATION SHALL BE CONSIDER Ø1";
SHAFT ELE.SIST. 2 - GROUND ALL METAL PATHWAYS;
3 - FIXING FOR CONDUITS AND CABLE TRAY SHOULD BE EVERY 2 METERS MAXIMUM;
DATA HALL 4 - IN THE PERFORMANCE OF PERFURATION IN WALLS AND SLABS, THE REPLACEMENT OF PASSIVE PROTECTION
M-06 WITH FIRE STOP IS MANDATORY;
MM
MR

SHAFT HVACM-05 5 - THE INFRASTRUCTURE INSTALLER SHOULD PROVIDE GUIDE WIRE FOR ALL DRY INFRASTRUCTURE, INTENDED FOR
M-12 SYSTEM INSTALLATIONS;
6 - THE PROJECT IS IN ACCORDANCE WITH NFPA 72 AND NFPA 76;
MM

M-06
MR

7 - ALL CIRCUITS ARE NAC (NOTIFICATION APPLIANCE CIRCUIT) AND MUST BE SUPERVISED BY EAL RESISTORS (END

MC

MRMM
M-05
M-05 OF LINE);
DSB-AC-3.1 M-06 8 - MUST BE CONSIDER A ISOLATOR MODULE TO EACH 20 ADDRESSABLE DEVICES AS INDICATED IN STANDARDS;
CIRCULAÇÃO SHAFT
SHAFTHVAC
HVAC 9 - ALL EXTERNAL DEVICES SHALL BE IP 56.

MR
M-05 10 - THE ASPIRATION DETECTION CENTRALS ARE INTENDED FOR DETECTION IN THE RETURN OF THE AIR

MM
ELEVADOR SOCIAL 01 M-06 CONDITIONING MACHINES SPECIFIED BY THE AIR CONDITIONING PROJECTS..
11 - THE CONTRACTOR MUST PROVIDE THE CALCULATION/DIMENSIONING OF EACH ASPIRATION DETECTION CENTRAL,
PROJECTS, LOOPS DISTRIBUTION DIAGRAMS AND CONSTRUTIVE DETAIS FOR SCALA'S APPROVAL.
MM PAINEL

12 - FOR EACH FUNCTION OF THE MODULES ALLOCATED IN THE PROJECT, SEE TABLE "TAG'S"
M-02
13 - RELAY AND MONITOR MODULE MUST BE CONSIDERED FOR ALL FIRE DAMPERS ALLOCATED IN THE PROJECT
14 - THE ADA PANIC BUTTON ARE THE RESPONSIBILITY OF THE ARCHITECTURE PROJECT, IT IS ONLY HIGHLIGHTED IN
ELEVADOR SOCIAL
ELEVADOR SOCIAL 02
02
G THE PROJECT, THE INSTALLER MUST MAKE THE ALLOCATION OF THEM COMPATIBLE WITH THE INFRASTRUCTURE G
M-06 INTENDED FOR INTEGRATION WITH THE MONITOR MODULE AND THE COMMAND MODULE.

MM
W.C.

MR
M-05

MR
M-05

MM
M-11 MM
SHAFT HID. M-01 M-06 SHAFT HID. ESCADA 02

MM
AVMC

MR
FUNÇÃO DOS MÓDULOS - MODULES FUNCTION
M-05
MR

MANTRAP
MM

M-06 M-05
ESCADA 01 ANTE-CÂMARA TAG FUNÇÃO DO EQUIPAMENTO
M-06 ANTE-CÂMARA
M-01 M-01 MÓDULO DE COMANDO PARA O ACIONAMENTO DO AVISADOR AUDIOVISUAL. CONTROL MODULE FOR HORN/STROBE.
M-02 PAINEL DE MÓDULOS MONITORES DAS CENTRAIS DE ASPIRAÇÃO: 1-SUPERVISÃO DA FONTE DE BATERIAS, 2-FALHA, 3-ALARME E 4-PRÉ-ALARME, O
MC MCAV INSTALADOR DEVERÁ ENVIAR PARA A SCALA APROVAR O DIMENSIONAMENTO/MEMORIAL DE CÁLCULO DE ASPIRAÇÃO DE CADA CENTRAL, E SE
AV MM MR MM MR MM MR MM MR NECESSÁRIO, A ADIÇÃO DE MÓDULOS MONITORES PARA TUBOS ENDEREÇÁVEIS. FIRE ALARM MODULES PANEL FOR INSTALLATION OF ALL MONITORING
MM MR MM MR MM MR
MODULES OF VERY EARLY ASPIRATION PANEL: 1-POWER SUPERVISION, 2-FAIL, 3-ALARM, 4-PRÉ-ALARM.THE INSTALLER MUST SEND TO SCALA TO APPROVE
M-01 THE DIMENSIONING/CALCULATION MEMORIAL OF EACH ASPIRATION SMOKE CENTRAL, AND IF NECESSARY, THE ADDITION OF MONITORING MODULES FOR
M-06 M-05 M-06 M-05 M-06 M-05 M-06 M-05 M-06 M-05 M-06 M-05 M-06 M-05 ADDRESSABLE PIPES.
M-03 PAINEL DE MÓDULOS PARA COMANDO E MONITORAMENTO DA VPA (7 MÓDULOS MONITORES): 1 - STATUS DE OPERAÇÃO, 2 - ALTA PRESSÃO DE AR
COMPRIMIDO, 3 - BAIXA PRESSÃO DE AR COMPRIMIDO, 4 - INTERRUPTOR DE PRESSÃO DE ÁGUA, 5 - PRESSÃO DE AR DA REDE, 6 - VÁLVULA DE
MANUTENÇÃO DE ENTRADA, 7 - VÁLVULA DE TESTE DE SAÍDA) E 1 MÓDULO RELEASE PARA CADA VPA. PANEL OF MODULES FOR MONITORING AND
H H

Bending Marks
PLENUM DE VENTILAÇÃO ACTIVATION OF VPA(7 MONITOR MODULE): 1 - STATUS OPERATION, 2 - HIGH PRESSION OF COMPRESS AIR, 3 - LOW PRESSION OF COMPRESS AIR, 4 - WATER
MCAV PRESSURE SWITCH, 5 - AIR NET PRESSURE, 6 - INLET MAINTENANCE VALVE, 7 - OUTLET TESTE VALVE, AND 1 RELEASE MODULE FOR VALVE COMMANDO
FOR EACH VPA.
M-01 MM | MC MM | MC M-05 MÓDULO RELÉ PARA DAMPER CORTA FOGO. RELAY MODULE FOR FIRE DAMPER
M-02 PANEL PANEL M-02 ELEVADOR DE CARGA 02 M-06 MÓDULO DE MONITORAMENTO PARA O FIM DE CURSO DO DAMPER CORTA FOGO. CONSIDERAR MÓDULO PARA COMPARTIMENTAÇÃO HORIZONTAL E
VERTICAL ONDE NECESSÁRIO. MONITOR MODULE FOR FIRE DAMPER. CONSIDER MODULE FOR HORIZONTAL AND VERTICAL COMPARTMENTATION WHERE
NECESSARY
M-07 MÓDULO DE COMANDO PARA AVISADOR AUDIOVISUAL DO BANHEIRO PNE. CONTROL MODULE FOR THE HORN STROBE OF THE SPECIAL NEEDS TOILET
M-08 MÓDULO DE MONITORAMENTO PARA O BOTÃO DO BANHEIRO PNE. MONITOR MODULE FOR THE BUTTON OF THE SPECIAL NEEDS TOILET
M-09 MÓDULO RELÉ PARA CORTAR A ALIMENTAÇÃO DAS SAÍDAS DAS FONTES DAS FECHADURAS ELETROMAGNÉTICAS. RELAY MODULE TO CUT OFF THE POWER
SUPPLY OUTLETS FOR THE ELECTROMAGNETIC LOCKS
M-06 M-05
M-11 DOIS MÓDULOS DE MONITORAMENTO PARA STATUS DA VÁLVULA SETORIAL E STATUS DA CHAVE DE FLUXO. TWO MONITORING MODULES FOR SECTOR
VALVE STATUS AND WATER FLOW SWITCH.

MM
M-12 MÓDULO DE COMANDO PARA PAINEL ELÉTRICO DOS EQUIPAMENTOS DE AR CONDICIONADO(DESLIGAMENTO DOS EQUIPAMENTOS). CONTROL MODULE
HALL ELEVADOR

MR
FOR ELECTRICAL PANEL OF AIR CONDITIONING EQUIPMENT (EQUIPMENT SHUTDOWN).
M-14 MÓDULO MONITOR PARA FALHA DA FONTE DE ALIMENTAÇÃO DO SISTEMA DE DETECÇÃO E ALARME DE INCÊNDIO. MONITOR MODULE FOR FIRE DETECTION
AND ALARM SYSTEM POWER SUPPLY FAILURE.
HALL ELEVADOR CORREDOR TÉCNICO MECÂNICA 02

M-01 ARQUIVO DE REFERÊNCIA DE ARQUITETURA:


MCAV

SGRUTB12-E-SCE-GE01-AR00-TD101.RVT
AVMC

AVMC
M-01
MR M-09
SGRUTB12-E-SCE-DC01-AR10-DE-0001
SGRUTB12-E-SCE-DC01-AR20-DE-0001
M-01
I SGRUTB12-ACP-L03-CL00-1000 SGRUTB12-E-SCE-DC01-AR20-DE-1001 I
SGRUTB12-E-SCE-DC01-AR20-DE-2001
SGRUTB12-E-SCE-DC01-AR20-DE-3001
SGRUTB12-E-SCE-DC01-AR20-DE-4001
SGRUTB12-E-SCE-DC01-AR20-DE-5001
SGRUTB12-E-SCE-DC01-AR20-DE-6001

LEVEL 03-FIRE ALARM SYSTEM


1 : 75

Estado / Status

APROVADO APPROVED

J J

00 APROVADO | APPROVED 18/05/2023 FAD MRM PGR


0A EMISSÃO INICIAL | INITIAL ISSUE 28/02/2023 FAD MRM PGR
Versão / Descrição / Description Data / Date Elaborado / Verificado / Aprovado/
Version Designed by Verified Aproved

Tabela de Revisões / Revision Schedule

K K

Projeto / Project
TAMBORÉ - SGRUTB12
Fase / Phase
PROJETO EXECUTIVO / EXECUTIVE DESIGN
Disciplina / Discipline
ELÉTRICA / ELECTRICAL
Título / Title

SISTEMA DE DETECÇÃO E ALARME DE INCÊNDIO (SDAI)


L L
NÍVEL 03 - SDAI
LEVEL 03 - SDAI
Data / Date Folha/ Sheet Código SCALA / SCALA Code Versão / Version

18/11 04/07 SGRUTB12-E-SCE-DC01-EL33-DE-3001 00


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16