LT 230 kV SERRA DA MESA - NIQUELÂNDIA C2 e

LT 230 kV NIQUELÂNDIA - BARRO ALTO C2

PROJETO BÁSICO

DETERMINAÇÃO DO FEIXE DE CABOS CONDUTORES

TTER-GO
ER GO LT 230 kV SERRA DA MESA-NIQUELÂNDIA C2 e
LT 230 kV NIQUELÂNDIA-BARRO ALTO C2

ESCALA

DETERMINAÇÃO DO FEIXE DE CABOS


CONDUTORES

Atendimento aos BRUNO PERRO 08/01/10


19/11/10
1 BP BP AUTOR/DESENHO DATA
Execução Comentários da
NS BRUNO PERRO 08/01/10
ANEEL AUTOR / PROJETO DATA
08/01/10 N.SANTIAGO 27.298-D 08/01/10
ORIG Execução BP BP VISTO / RESP / CREA DATA
NS Nº.: 3.67.02-A4-004
FEITO VISTO POR ORG FEITO VISTO APROV
REV. PARA DESCRIÇÃO
FURNAS PROJETISTA
SUMÁRIO

1 OBJETIVO 3

2 PERDAS JOULE NOS CABOS CONDUTORES 3


2.1 LT 230 kV Serra da Mesa – Niquelândia C2 3
2.2 LT 230 kV Niquelândia – Barro Alto C2 3

3 REATÂNCIA LONGITUDINAL DE SEQÜÊNCIA POSITIVA 3


3.1 LT 230 kV Serra da Mesa – Niquelândia C2 4
3.2 LT 230 kV Niquelândia – Barro Alto C2 5

4 CAPACIDADE TÉRMICA DO CABO CONDUTOR 6


4.1 LT 230 kV Serra da Mesa – Niquelândia C2 6
4.2 LT 230 kV Niquelândia – Barro Alto C2 6

5 CORONA VISUAL 7
5.1 LT 230 kV Serra da Mesa – Niquelândia C2 8
5.2 LT 230 kV Niquelândia – Barro Alto C2 8

6 TRANSPOSIÇÃO 9

7 CONCLUSÃO 9

8 REFERÊNCIAS 9

ANEXO I PARÂMETROS ELÉTRICOS DAS LT´S

ANEXO II CAPACIDADE TÉRMICA DO CABO CONDUTOR

ANEXO III CAMPO ELÉTRICO SUPERFICIAL DOS CONDUTORES

2
1 OBJETIVO

O presente relatório tem por objetivo determinar o feixe de cabos condutores das LT 230
kV Serra da Mesa - Niquelândia C2 e LT 230 kV Niquelândia – Barro Alto C2, com
extensões aproximadas de 100 km e 88 km, respectivamente, tomando-se por base os
critérios especificados no Edital do Leilão nº 001/2009 da ANEEL, no que se refere a:

- Perdas Joule
- Reatância Longitudinal de Seqüência Positiva
- Capacidade Térmica
- Corona Visual

2 PERDAS JOULE NOS CABOS CONDUTORES

2.1 LT 230 kV Serra da Mesa – Niquelândia C2

O Anexo 6K do Edital da ANEEL especifica que a resistência de seqüência positiva por


unidade de comprimento da linha de transmissão, para freqüência nominal de 60 Hz e para
a temperatura de 50ºC, deve ser igual ou inferior a da configuração básica: 0,0348 Ω/km.

Considerando-se o feixe com dois subcondutores, o cabo tipo CAA 954 kCM - 45/7,
RAIL, atende ao especificado no Edital.

2.2 LT 230 kV Niquelândia – Barro Alto C2

O Anexo 6K do Edital da ANEEL especifica que a resistência de seqüência positiva por


unidade de comprimento da linha de transmissão, para freqüência nominal de 60 Hz e para
a temperatura de 50ºC, deve ser igual ou inferior a da configuração básica: 0,0697 Ω/km.

O cabo tipo CAA 954 kCM - 45/7, RAIL, atende ao especificado no Edital.

3 REATÂNCIA LONGITUDINAL DE SEQÜÊNCIA POSITIVA

O Anexo 6K do Edital especifica que a reatância longitudinal de seqüência positiva da


linha deverá possibilitar a distribuição de fluxos de potência nesta linha, similares aos da
alternativa de referência apresentada nos estudos.

Os estudos apresentados no relatório R2, "Detalhamento da Alternativa de Referência",


que utilizaram o cabo condutor RAIL nas LT´s, mostram que, tanto em regime normal de
operação quanto em condições de emergência, todas as LT's e equipamentos representados
nos estudos estão com os seus níveis de tensão e corrente dentro dos limites operacionais
aceitáveis.

3
3.1 LT 230 kV Serra da Mesa – Niquelândia C2

Para o feixe de 2 x RAIL, com espaçamento convencional de 0,457 m, e


considerando-se a silhueta da estrutura típica da Figura 1, foram os seguintes os parâmetros
elétricos de seqüência positiva da LT, conforme o Anexo I, obtidos pelo programa
computacional PALT-FE, desenvolvido pela Fluxo Engenharia, com base na metodologia
descrita na referência [1]:

- Resistência : 0,0344 Ω/km


- Reatância : 0,3453 Ω/km
- Susceptância : 4,7645 µS/km

Figura 1

Considerando-se o vão médio desta LT, de 470 m, têm-se as seguintes flechas dos cabos:

- Condutor: 20,18 m;
- Pára-raios: 16,28 m.

Foram incluídos os resultados computacionais com os parâmetros elétricos da LT 230 kV


Serra da Mesa – Niquelândia C2 considerando a LT 230 kV Serra da Mesa – Niquelândia
C1 de FURNAS em paralelo, com distância entre eixos de 30 m.

4
3.2 LT 230 kV Niquelândia – Barro Alto C2

Para o cabo condutor RAIL, considerando-se a silhueta da estrutura típica da Figura 2,


foram os seguintes os parâmetros elétricos de seqüência positiva da LT, conforme o Anexo
I, obtidos pelo programa computacional PALT-FE, desenvolvido pela Fluxo Engenharia,
com base na metodologia descrita na referência [1]:

- Resistência : 0,0685 Ω/km


- Reatância : 0,4810 Ω/km
- Susceptância : 3,4404 µS/km

Figura 2

Considerando-se o vão médio desta LT, de 470 m, têm-se as seguintes flechas dos cabos:

- Condutor: 20,18 m;
- Pára-raios: 16,28 m.

Foram incluídos os resultados computacionais com os parâmetros elétricos da LT 230 kV


Niquelândia - Barro Alto C2 considerando a LT 230 kV Niquelândia - Barro Alto C1 de
FURNAS em paralelo, com distância entre eixos de 26 m.

5
4 CAPACIDADE TÉRMICA DO CABO CONDUTOR

4.1 LT 230 kV Serra da Mesa – Niquelândia C2

O Anexo 6K do Edital especifica que a linha de transmissão deverá ter capacidade


operativa de longa duração de 1550 A e capacidade operativa de curta duração de 1960 A,
sem que haja violação de qualquer critério de desempenho, inerente à linha de transmissão.

A capacidade térmica do cabo CAA RAIL, em regime permanente, foi processada pelo
programa computacional CATA-FE, desenvolvido pela Fluxo Engenharia, para a LT em
estudo:

Parâmetros adotados nesta LT:

- Temperatura máxima média da região: 30ºC;


- Radiação solar máxima;
- Brisa: 1 m/s (3,6 km/h);
- Coeficiente de absorção: 0,6;
- Coeficiente de emissividade: 0,6;
- Pressão atmosférica: 709 mmHg (altitude de 600m).

Para a corrente máxima de 1550 A por fase, ou seja, 775 A por subcondutor, a temperatura
máxima do cabo será da ordem de 58ºC, conforme pode ser observado no Anexo II.

Para a corrente máxima de 1960 A por fase, ou seja, 980 A por subcondutor, a temperatura
máxima do cabo será de ordem de 70ºC, conforme também observado no Anexo II.

Com base na norma NBR-5422, a condição governante para distância mínima


condutor-solo será a de operação de longa duração. Desta forma, é recomendável adotar a
temperatura máxima de 60ºC para cálculo da flecha máxima dos cabos condutores,
temperatura esta que deve ser considerada para a plotação das estruturas no perfil.

Cumpre ressaltar que a locação das estruturas também será verificada para a temperatura
do cabo condutor na condição de operação de curta duração, ou seja, de 70ºC.

Como na faixa de vãos de 200m a 1000m a diferença da flecha do cabo condutor nas
temperaturas de 60ºC e 70ºC varia de 0,28m a 0,43m, observa-se que, em função da
diferença entre as distâncias mínimas necessárias e as distâncias adotadas de isolamento a
obstáculo em regime de longa duração, conforme especificado no Relatório 3.67.02-A4-
010, “Distâncias de Segurança”, o cabo, mesmo a 70ºC, também atenderá as distâncias
mínimas especificadas para o regime de longa duração.

4.2 LT 230 kV Niquelândia – Barro Alto C2

O Anexo 6K do Edital especifica que a linha de transmissão deverá ter capacidade


operativa de longa duração de 775 A e capacidade operativa de curta duração de 980 A,
sem que haja violação de qualquer critério de desempenho, inerente à linha de transmissão.
6
A capacidade térmica do cabo CAA RAIL, em regime permanente, foi processada pelo
programa computacional CATA-FE, desenvolvido pela Fluxo Engenharia, para a LT em
estudo:

Parâmetros adotados neste trecho:

- Temperatura máxima média da região: 30ºC;


- Radiação solar máxima;
- Brisa: 1 m/s (3,6 km/h);
- Coeficiente de absorção: 0,6;
- Coeficiente de emissividade: 0,6;
- Pressão atmosférica: 709 mmHg (altitude de 600m).

Para a corrente máxima de 775 A, a temperatura máxima do cabo será da ordem de 58ºC,
conforme pode ser observado no Anexo II.

Para a corrente máxima de 980 A, a temperatura máxima do cabo será de ordem de 70ºC,
conforme também observado no Anexo II.

Com base na norma NBR-5422, a condição governante para distância mínima


condutor-solo será a de operação de longa duração. Desta forma, é recomendável adotar a
temperatura máxima de 60ºC para cálculo da flecha máxima dos cabos condutores,
temperatura esta que deve ser considerada para a plotação das estruturas no perfil.

5 CORONA VISUAL

O Anexo 6K do Edital especifica que à tensão máxima de operação da linha, qual seja,
242kV, a mesma não deverá apresentar corona visual, nos cabos condutores e ferragens,
para 90% da condição de tempo bom.

O cálculo do campo elétrico foi elaborado pelo programa computacional CAMPO-FE,


desenvolvido pela Fluxo Engenharia, com base na metodologia descrita na referência [1].

As silhuetas das estruturas típicas consideradas são as da Figura 1 e 2, os resultados são


apresentados no Anexo III, considerando-se o campo elétrico de corona visual de acordo
com a fórmula de Peek [2]

 0,3 
E c = 30 m δ 1 + , kVP/cm
 δ . r 

onde:
m - fator de superfície
δ - densidade relativa do ar
r - raio do condutor, cm

7
5.1 LT 230 kV Serra da Mesa – Niquelândia C2

Neste trecho os valores adotados para cálculo foram:

- m = 0,82

Este valor é representativo para um condutor normalmente envelhecido, em tempo bom.

Considerando-se os cuidados de lançamento e grampeamento dos cabos condutores em


LT's de alta tensão, é usual, nos projetos atuais, se utilizar o valor típico de fator de
superfície de 0,82.

- δ = 0,91

Este valor corresponde ao valor que é excedido em 90% do tempo para a região de maior
altitude onde a LT poderá passar. Cumpre ressaltar que o valor médio na rota é de 0,93,
conforme o relatório 3.67.02-A4-002, “Dados Meteorológicos Aplicáveis ao Projeto”.

- r = 1,4795 cm.

O maior valor de campo elétrico na superfície dos subcondutores, conforme o Anexo III,
foi de 16,93 kVp/cm, inferior ao campo elétrico de corona visual de 28,17 kVp/cm,
atendendo, portanto, o Edital.

Entende-se que um feixe com um desempenho adequado, no que se refere ao efeito corona,
ou seja, com intensidades de campo elétrico, na superfície dos cabos condutores, inferiores
ao campo elétrico crítico de Peek (corona visível generalizado), irá ter também um
desempenho adequado no que se refere a níveis de rádio-interferência e ruído-audível,
necessitando de faixas de passagens com larguras típicas das utilizadas em LT's de 230 kV.

5.2 LT 230 kV Niquelândia – Barro Alto C2

Neste trecho os valores adotados para cálculo foram:

- m = 0,82

Este valor é representativo para um condutor normalmente envelhecido, em tempo bom.

Considerando-se os cuidados de lançamento e grampeamento dos cabos condutores em


LT's de alta tensão, é usual, nos projetos atuais, se utilizar o valor típico de fator de
superfície de 0,82.

- δ = 0,91

Este valor corresponde ao valor que é excedido em 90% do tempo para a região de maior
altitude onde a LT poderá passar. Cumpre ressaltar que o valor médio na rota é de 0,93,
conforme o relatório 3.67.02-A4-002, “Dados Meteorológicos Aplicáveis ao Projeto”.
8
- r = 1,4795 cm.

O maior valor de campo elétrico na superfície dos subcondutores, conforme o Anexo III,
foi de 22,50 kVp/cm, inferior ao campo elétrico de corona visual de 28,17 kVp/cm,
atendendo, portanto, o Edital.

6 TRANSPOSIÇÃO

Caso as LT´s não fossem transpostas, as mesmas apresentariam os seguintes


desequilíbrios:

- LT 230 kV Serra da Mesa - Niquelândia C2: a plena carga o desequilíbrio de tensão de


sequência zero é de 0,84% e o de sequência negativa é de 2,93%.

- LT 230 kV Niquelândia - Barro Alto C2: a plena carga o desequilíbrio de tensão de


sequência zero é de 1,07% e o de sequência negativa é de 2,00%.

Como no caso das duas LT´s há valores de desequilíbrio superiores ao limite estabelecido
no Edital da ANEEL, de 1,5%, cada uma das LT´s terá um ciclo completo de transposição,
com trechos de 1/6, 1/3, 1/3 e 1/6 do comprimento total, a partir das SE’s.

7 CONCLUSÃO

O feixe de 2 x CAA 954 kCM – 45/7, RAIL, da LT 230 kV Serra da Mesa – Niquelândia
C2 e o cabo condutor CAA 954 kCM – 45/7, RAIL, da LT 230 kV Niquelândia - Barro
Alto C2, conforme apresentado neste Relatório, atendem a todas as especificações do
Anexo 6K do Edital 001/2009 da ANEEL, além de se apresentarem como uma escolha
adequada tanto do ponto de vista técnico como econômico.

As principais características do cabo CAA 954 kCM – 45/7 são apresentadas a seguir:

- Diâmetro ........................................ 29,59 mm


- Peso próprio ................................... 1,6 kgf/m
- Área total ....................................... 516,75 mm2
- Carga de ruptura ............................. 11.764 kgf
- Resistência elétrica.......................... 0,0683 Ω/km, CA, a 50ºC
- Reatância indutiva .......................... 0,2455 Ω/km, até 1 pé

8 REFERÊNCIAS

[1] Transmission Line Reference Book 345 kV and Above, EPRI, 1975.

[2] Peek Jr., F. W., "Law of Corona and the Dielectric Strength of Air", AIEE
Transactions, Vol. 30, Pt. III, pp. 1889 - 1965, 1911.

9
ANEXO I

PARÂMETROS ELÉTRICOS DAS LT´S


LT´S 230 kV EM PROJETO ISOLADAMENTE
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO

CABO CONDUTOR:

CIRCUITO 1

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 20.18

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (1)

- Tipo ..................................................... OPGW


- Bitola ................................................... 55mm2
- Formação ................................................. 24FO
- Diâmetro (mm) ............................................ 11.00
- Resistência (Ohms/km) .................................... 1.4610 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .3258
- Flecha média (m) ......................................... 16.28
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (2)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 16.28

RESISTIVIDADE MÉDIA DO SOLO (Ohms.m) ....................... 1000


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DISPOSIÇÃO GEOMÉTRICA DOS CABOS CONDUTORES NO(s) CIRCUITO(s)

CIRCUITO 1

- Número de sub-condutores por fase ........................ 2


- Espaçamento entre subcondutores (m) ...................... .457
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -3.70 28.60


FASE B.......... 3.70 28.60
FASE C.......... 3.70 34.00

- Abscissa (x) e ordenada (y) dos cabos pára-raios em relação a um sistema de


eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

CABO PÁRA-RAIOS (1)......... -3.70 39.55


CABO PÁRA-RAIOS (2)......... 3.70 39.55
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS:

R (Ohms/km)
jX

.0927 .0585 .0584 .0582 .0582


.7932 .4453 .4293 .4000 .3901

.0585 .0927 .0584 .0582 .0582


.4453 .7932 .4690 .3901 .4000

.0584 .0584 .0924 .0581 .0581


.4293 .4690 .7935 .4158 .4384

.0582 .0582 .0581 1.5189 .0579


.4000 .3901 .4158 1.0122 .4459

.0582 .0582 .0581 .0579 3.6779


.3901 .4000 .4384 .4459 1.2044

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

R (Ohms/km)
jX

.1648 .1298 .1360


.6993 .3524 .3305

.1298 .1633 .1354


.3524 .7012 .3712

.1360 .1354 .1763


.3305 .3712 .6894
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE SEQUÊNCIA

R (Ohms/km)
jX

.4356 .0072 -.0122


1.3994 -.0031 -.0141

-.0122 .0344 -.0093


-.0141 .3453 .0213

.0072 .0092 .0344


-.0031 .0210 .3453

R0/R1 (1)= 12.676 X0/X1 (1)= 4.053

MATRIZ TRANSVERSAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

B (Sx1E-6/km)
jY

.0000 .0000 .0000


3.9349 -.6975 -.5380

.0000 .0000 .0000


-.6975 4.1057 -.9896

.0000 .0000 .0000


-.5380 -.9896 4.0279
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 06/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 6 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE SEQUÊNCIA

B (Sx1E-6/km)
jY

.0000 -.0236 .0236


2.5395 .0800 .0800

.0236 .0000 .1145


.0800 4.7645 -.2919

-.0236 -.1145 .0000


.0800 -.2919 4.7645

Y0/Y1 (1)= .533


1
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO

CABO CONDUTOR:

CIRCUITO 1

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 20.18

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (1)

- Tipo ..................................................... OPGW


- Bitola ................................................... 55mm2
- Formação ................................................. 24FO
- Diâmetro (mm) ............................................ 11.00
- Resistência (Ohms/km) .................................... 1.4610 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .3258
- Flecha média (m) ......................................... 16.28
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (2)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 16.28

RESISTIVIDADE MÉDIA DO SOLO (Ohms.m) ....................... 1000


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DISPOSIÇÃO GEOMÉTRICA DOS CABOS CONDUTORES NO(s) CIRCUITO(s)

CIRCUITO 1

- Número de sub-condutores por fase ........................ 1


- Espaçamento entre subcondutores (m) ...................... .000
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -3.50 28.60


FASE B.......... 3.50 28.60
FASE C.......... 3.50 34.00

- Abscissa (x) e ordenada (y) dos cabos pára-raios em relação a um sistema de


eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

CABO PÁRA-RAIOS (1)......... -3.50 39.15


CABO PÁRA-RAIOS (2)......... 3.50 39.15
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS:

R (Ohms/km)
jX

.1268 .0585 .0584 .0582 .0582


.9313 .4495 .4320 .4022 .3928

.0585 .1268 .0584 .0582 .0582


.4495 .9313 .4692 .3928 .4022

.0584 .0584 .1265 .0581 .0581


.4320 .4692 .9315 .4197 .4422

.0582 .0582 .0581 1.5189 .0579


.4022 .3928 .4197 1.0122 .4501

.0582 .0582 .0581 .0579 3.6779


.3928 .4022 .4422 .4501 1.2044

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

R (Ohms/km)
jX

.1998 .1307 .1373


.8364 .3555 .3318

.1307 .1984 .1366


.3555 .8382 .3700

.1373 .1366 .2120


.3318 .3700 .8258
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE SEQUÊNCIA

R (Ohms/km)
jX

.4731 .0078 -.0131


1.5383 -.0015 -.0131

-.0131 .0685 -.0102


-.0131 .4810 .0192

.0078 .0100 .0685


-.0015 .0188 .4810

R0/R1 (1)= 6.905 X0/X1 (1)= 3.198

MATRIZ TRANSVERSAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

B (Sx1E-6/km)
jY

.0000 .0000 .0000


2.9581 -.4348 -.3392

.0000 .0000 .0000


-.4348 3.0275 -.5686

.0000 .0000 .0000


-.3392 -.5686 2.9929
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 07/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 6 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE SEQUÊNCIA

B (Sx1E-6/km)
jY

.0000 -.0176 .0176


2.0977 .0432 .0432

.0176 .0000 .0652


.0432 3.4404 -.1384

-.0176 -.0652 .0000


.0432 -.1384 3.4404

Y0/Y1 (1)= .610


1
LT´S 230 kV EM PROJETO EM PARALELO COM AS LT´s 230 kV DE FURNAS
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO

CABO CONDUTOR:

CIRCUITO 1

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 20.18

CABO CONDUTOR:

CIRCUITO 2

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 16.89
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (1)

- Tipo ..................................................... OPGW


- Bitola ................................................... 55mm2
- Formação ................................................. 24FO
- Diâmetro (mm) ............................................ 11.00
- Resistência (Ohms/km) .................................... 1.4610 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .3258
- Flecha média (m) ......................................... 16.28

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (2)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 16.28
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (3)


CABO PÁRA-RAIOS (4)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 13.63

RESISTIVIDADE MÉDIA DO SOLO (Ohms.m) ....................... 1000


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DISPOSIÇÃO GEOMÉTRICA DOS CABOS CONDUTORES NO(s) CIRCUITO(s)

CIRCUITO 1

- Número de sub-condutores por fase ........................ 2


- Espaçamento entre subcondutores (m) ...................... .457
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -3.70 28.60


FASE B.......... 3.70 28.60
FASE C.......... 3.70 34.00

CIRCUITO 2

- Número de sub-condutores por fase ........................ 2


- Espaçamento entre subcondutores (m) ...................... .457
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -37.00 25.30


FASE B.......... -30.00 25.30
FASE C.......... -23.00 25.30
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

- Abscissa (x) e ordenada (y) dos cabos pára-raios em relação a um sistema de


eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

CABO PÁRA-RAIOS (1)......... -3.70 39.55


CABO PÁRA-RAIOS (2)......... 3.70 39.55
CABO PÁRA-RAIOS (3)......... -35.50 29.50
CABO PÁRA-RAIOS (4)......... -24.50 29.50
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 6 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS:

R (Ohms/km)
jX

.0927 .0585 .0584 .0585 .0585 .0585 .0582 .0582 .0584 .0584
.7932 .4453 .4293 .3318 .3496 .3728 .3999 .3901 .3344 .3651

.0585 .0927 .0584 .0585 .0585 .0585 .0582 .0582 .0583 .0584
.4453 .7932 .4690 .3167 .3309 .3484 .3901 .4000 .3190 .3432

.0584 .0584 .0924 .0584 .0584 .0584 .0581 .0581 .0582 .0582
.4293 .4690 .7935 .3159 .3297 .3464 .4158 .4384 .3198 .3447

.0585 .0585 .0584 .0927 .0586 .0585 .0582 .0582 .0584 .0584
.3318 .3167 .3159 .7931 .4495 .3972 .3255 .3125 .4545 .3971

.0585 .0585 .0584 .0586 .0927 .0586 .0582 .0582 .0584 .0584
.3496 .3309 .3297 .4495 .7931 .4495 .3398 .3247 .4356 .4356

.0585 .0585 .0584 .0585 .0586 .0927 .0582 .0582 .0584 .0584
.3728 .3484 .3464 .3972 .4495 .7931 .3561 .3389 .3971 .4545

.0582 .0582 .0581 .0582 .0582 .0582 1.5189 .0579 .0581 .0581
.3999 .3901 .4158 .3255 .3398 .3561 1.0122 .4459 .3333 .3622

.0582 .0582 .0581 .0582 .0582 .0582 .0579 3.6779 .0580 .0581
.3901 .4000 .4384 .3125 .3247 .3389 .4459 1.2044 .3184 .3417

.0584 .0583 .0582 .0584 .0584 .0584 .0581 .0580 3.6783 .0583
.3344 .3190 .3198 .4545 .4356 .3971 .3333 .3184 1.2040 .4156

.0584 .0584 .0582 .0584 .0584 .0584 .0581 .0581 .0583 3.6783
.3651 .3432 .3447 .3971 .4356 .4545 .3622 .3417 .4156 1.2040
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 7 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

R (Ohms/km)
jX

.1797 .1431 .1483 .1397 .1432 .1452


.6604 .3154 .2934 .2070 .2209 .2418

.1431 .1750 .1461 .1366 .1401 .1420


.3154 .6660 .3359 .1947 .2052 .2204

.1483 .1461 .1861 .1403 .1440 .1462


.2934 .3359 .6541 .1887 .1985 .2128

.1397 .1366 .1403 .1764 .1448 .1448


.2070 .1947 .1887 .6732 .3261 .2722

.1432 .1401 .1440 .1448 .1821 .1485


.2209 .2052 .1985 .3261 .6661 .3206

.1452 .1420 .1462 .1448 .1485 .1838


.2418 .2204 .2128 .2722 .3206 .6623
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 8 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE SEQUÊNCIA

R (Ohms/km)
jX

.4719 .0094 -.0102 .4258 -.0191 .0100


1.2900 -.0056 -.0151 .6299 -.0180 -.0216

-.0102 .0344 -.0093 -.0047 -.0014 .0020


-.0151 .3453 .0213 .0164 -.0025 -.0019

.0094 .0093 .0344 .0070 -.0021 .0016


-.0056 .0209 .3453 .0232 -.0022 -.0026

.4258 .0070 -.0047 .4728 .0133 -.0201


.6299 .0232 .0164 1.2798 -.0037 -.0046

.0100 .0016 .0020 -.0201 .0347 -.0298


-.0216 -.0026 -.0019 -.0046 .3609 .0178

-.0191 -.0021 -.0014 .0133 .0303 .0347


-.0180 -.0022 -.0025 -.0037 .0168 .3609

R0/R1 (1)= 13.707 X0/X1 (1)= 3.736

R0/R1 (2)= 13.609 X0/X1 (2)= 3.546


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 9 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

B (Sx1E-6/km)
jY

.0000 .0000 .0000 .0000 .0000 .0000


3.9654 -.6865 -.5231 -.0396 -.0742 -.2056

.0000 .0000 .0000 .0000 .0000 .0000


-.6865 4.1096 -.9841 -.0176 -.0276 -.0670

.0000 .0000 .0000 .0000 .0000 .0000


-.5231 -.9841 4.0355 -.0274 -.0382 -.0812

.0000 .0000 .0000 .0000 .0000 .0000


-.0396 -.0176 -.0274 3.9985 -.7305 -.2193

.0000 .0000 .0000 .0000 .0000 .0000


-.0742 -.0276 -.0382 -.7305 4.1439 -.7197

.0000 .0000 .0000 .0000 .0000 .0000


-.2056 -.0670 -.0812 -.2193 -.7197 4.0305
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ ----------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 10 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE SEQUÊNCIA

B (Sx1E-6/km)
jY

.0000 -.0258 .0258 .0000 .0617 -.0617


2.5744 .0907 .0907 -.1928 .0541 .0541

.0258 .0000 .1158 -.0100 .0267 -.0253


.0907 4.7681 -.2886 -.0633 .0222 .0240

-.0258 -.1158 .0000 .0100 .0253 -.0267


.0907 -.2886 4.7681 -.0633 .0240 .0222

.0000 .0100 -.0100 .0000 -.1148 .1148


-.1928 -.0633 -.0633 2.9446 .0520 .0520

-.0617 -.0267 -.0253 .1148 .0000 .3279


.0541 .0222 .0240 .0520 4.6142 -.1928

.0617 .0253 .0267 -.1148 -.3279 .0000


.0541 .0240 .0222 .0520 -.1928 4.6142

Y0/Y1 (1)= .540

Y0/Y1 (2)= .638


1
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO

CABO CONDUTOR:

CIRCUITO 1

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 20.18

CABO CONDUTOR:

CIRCUITO 2

- Tipo ..................................................... CAA


- Bitola ................................................... 954 kCM
- Formação ................................................. 45/7
- Diâmetro (mm) ............................................ 29.59
- Resistência (Ohms/km) .................................... .0683 a 50.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .2455
- Flecha média (m) ......................................... 16.89
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (1)

- Tipo ..................................................... OPGW


- Bitola ................................................... 55mm2
- Formação ................................................. 24FO
- Diâmetro (mm) ............................................ 11.00
- Resistência (Ohms/km) .................................... 1.4610 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .3258
- Flecha média (m) ......................................... 16.28

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (2)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 16.28
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

CABO PÁRA-RAIOS:

CABO PÁRA-RAIOS (3)


CABO PÁRA-RAIOS (4)

- Tipo ..................................................... ACO GALV.EAR


- Bitola ................................................... 3/8"
- Formação ................................................. 7
- Diâmetro (mm) ............................................ 9.14
- Resistência (Ohms/km) .................................... 3.6200 a 30.0 (°C)
- Reatância indutiva interna - 1 ft - (Ohms/km) ............ .5180
- Flecha média (m) ......................................... 13.63

RESISTIVIDADE MÉDIA DO SOLO (Ohms.m) ....................... 1000


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DISPOSIÇÃO GEOMÉTRICA DOS CABOS CONDUTORES NO(s) CIRCUITO(s)

CIRCUITO 1

- Número de sub-condutores por fase ........................ 1


- Espaçamento entre subcondutores (m) ...................... .000
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -3.50 28.60


FASE B.......... 3.50 28.60
FASE C.......... 3.50 34.00

CIRCUITO 2

- Número de sub-condutores por fase ........................ 1


- Espaçamento entre subcondutores (m) ...................... .000
- Abscissas (x) e ordenadas (y) dos centros dos feixes de sub-condutores em relação a um sistema de
eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

FASE A.......... -33.00 25.30


FASE B.......... -26.00 25.30
FASE C.......... -19.00 25.30
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

- Abscissa (x) e ordenada (y) dos cabos pára-raios em relação a um sistema de


eixos ortogonais arbitrado:

Eixos .......... EIXO DA ESTRUTURA / SOLO

x(m) y(m)

CABO PÁRA-RAIOS (1)......... -3.50 39.15


CABO PÁRA-RAIOS (2)......... 3.50 39.15
CABO PÁRA-RAIOS (3)......... -31.50 29.50
CABO PÁRA-RAIOS (4)......... -20.50 29.50
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 6 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS:

R (Ohms/km)
jX

.1268 .0585 .0584 .0585 .0585 .0585 .0582 .0582 .0584 .0584
.9313 .4495 .4320 .3409 .3613 .3893 .4022 .3928 .3438 .3792

.0585 .1268 .0584 .0585 .0585 .0585 .0582 .0582 .0584 .0584
.4495 .9313 .4692 .3249 .3409 .3613 .3928 .4022 .3274 .3549

.0584 .0584 .1265 .0584 .0584 .0584 .0581 .0581 .0582 .0582
.4320 .4692 .9315 .3239 .3393 .3585 .4197 .4422 .3284 .3568

.0585 .0585 .0584 .1268 .0585 .0585 .0582 .0582 .0584 .0584
.3409 .3249 .3239 .9312 .4494 .3971 .3334 .3199 .4546 .3971

.0585 .0585 .0584 .0585 .1268 .0585 .0582 .0582 .0584 .0584
.3613 .3409 .3393 .4494 .9312 .4494 .3490 .3334 .4356 .4356

.0585 .0585 .0584 .0585 .0585 .1268 .0582 .0582 .0584 .0584
.3893 .3613 .3585 .3971 .4494 .9312 .3667 .3490 .3971 .4546

.0582 .0582 .0581 .0582 .0582 .0582 1.5189 .0579 .0581 .0581
.4022 .3928 .4197 .3334 .3490 .3667 1.0122 .4501 .3425 .3757

.0582 .0582 .0581 .0582 .0582 .0582 .0579 3.6779 .0581 .0581
.3928 .4022 .4422 .3199 .3334 .3490 .4501 1.2044 .3267 .3531

.0584 .0584 .0582 .0584 .0584 .0584 .0581 .0581 3.6783 .0583
.3438 .3274 .3284 .4546 .4356 .3971 .3425 .3267 1.2040 .4156

.0584 .0584 .0582 .0584 .0584 .0584 .0581 .0581 .0583 3.6783
.3792 .3549 .3568 .3971 .4356 .4546 .3757 .3531 .4156 1.2040
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 7 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

R (Ohms/km)
jX

.2162 .1451 .1506 .1420 .1458 .1480


.7952 .3164 .2926 .2128 .2290 .2544

.1451 .2110 .1482 .1388 .1425 .1447


.3164 .8012 .3328 .1998 .2118 .2296

.1506 .1482 .2227 .1428 .1467 .1492


.2926 .3328 .7885 .1932 .2043 .2207

.1420 .1388 .1428 .2115 .1460 .1462


.2128 .1998 .1932 .8086 .3231 .2688

.1458 .1425 .1467 .1460 .2176 .1501


.2290 .2118 .2043 .3231 .8009 .3169

.1480 .1447 .1492 .1462 .1501 .2199


.2544 .2296 .2207 .2688 .3169 .7964
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 8 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ LONGITUDINAL DE SEQUÊNCIA

R (Ohms/km)
jX

.5126 .0102 -.0109 .4335 -.0222 .0122


1.4228 -.0043 -.0142 .6519 -.0210 -.0250

-.0109 .0686 -.0101 -.0055 -.0018 .0028


-.0142 .4810 .0192 .0185 -.0032 -.0024

.0102 .0101 .0686 .0078 -.0029 .0021


-.0043 .0188 .4810 .0259 -.0028 -.0033

.4335 .0078 -.0055 .5112 .0132 -.0207


.6519 .0259 .0185 1.4079 -.0030 -.0044

.0122 .0021 .0028 -.0207 .0689 -.0297


-.0250 -.0033 -.0024 -.0044 .4990 .0178

-.0222 -.0029 -.0018 .0132 .0303 .0689


-.0210 -.0028 -.0032 -.0030 .0168 .4990

R0/R1 (1)= 7.472 X0/X1 (1)= 2.958

R0/R1 (2)= 7.419 X0/X1 (2)= 2.821


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 9 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE FASE COM PÁRA-RAIOS ELIMINADOS:

B (Sx1E-6/km)
jY

.0000 .0000 .0000 .0000 .0000 .0000


2.9849 -.4237 -.3256 -.0326 -.0634 -.1648

.0000 .0000 .0000 .0000 .0000 .0000


-.4237 3.0321 -.5629 -.0160 -.0268 -.0623

.0000 .0000 .0000 .0000 .0000 .0000


-.3256 -.5629 3.0000 -.0220 -.0327 -.0672

.0000 .0000 .0000 .0000 .0000 .0000


-.0326 -.0160 -.0220 2.9923 -.4169 -.1408

.0000 .0000 .0000 .0000 .0000 .0000


-.0634 -.0268 -.0327 -.4169 3.0588 -.4075

.0000 .0000 .0000 .0000 .0000 .0000


-.1648 -.0623 -.0672 -.1408 -.4075 3.0185
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT's 230 kV NIQUELANDIA - BARRO ALTO C1 E C2 ║
║ PARÂMETROS ELÉTRICOS DE LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 19/11/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 10 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

MATRIZ TRANSVERSAL DE SEQUÊNCIA

B (Sx1E-6/km)
jY

.0000 -.0191 .0191 .0000 .0495 -.0495


2.1309 .0524 .0524 -.1626 .0460 .0460

.0191 .0000 .0659 -.0048 .0190 -.0194


.0524 3.4431 -.1359 -.0491 .0180 .0175

-.0191 -.0659 .0000 .0048 .0194 -.0190


.0524 -.1359 3.4431 -.0491 .0175 .0180

.0000 .0048 -.0048 .0000 -.0681 .0681


-.1626 -.0491 -.0491 2.3797 .0274 .0274

-.0495 -.0190 -.0194 .0681 .0000 .1710


.0460 .0180 .0175 .0274 3.3450 -.1012

.0495 .0194 .0190 -.0681 -.1710 .0000


.0460 .0175 .0180 .0274 -.1012 3.3450

Y0/Y1 (1)= .619

Y0/Y1 (2)= .711


1
ANEXO II

CAPACIDADE TÉRMICA DO CABO CONDUTOR


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ------------------------- ║
║ LT's 230 kV SERRA DA MESA - NIQUELANDIA - BARRO ALTO C2 ║
║ CAPACIDADE TÉRMICA DE CABOS AÉREOS EM REGIME PERMANENTE ║
║ TIPO: CAA BITOLA: 954 kCM FORMAÇÃO: 45/7 ║
║ ║
║ DATA: 04/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

1.- CARACTERÍSTICAS DO AMBIENTE:

Temperatura ambiente (°C) ................. 30.0


Velocidade do vento (km/h) ................ 3.6
Pressão atmosferica (mmHg) ................ 709.0

2.- CARACTERÍSTICAS DO CABO CONDUTOR:

Diâmetro nominal (mm) ..................... 29.59


Resistência linear do condutor (ohms/km) .. 0.0683 ( a 50.0 °C)
Coeficiente de emissividade (0.2 - 0.9) ... 0.60
Coeficiente de absorção (0.1 - 1.0) ....... 0.60

3.- RESULTADOS:

┌─────────────┬─────────────┐ ┌───────────┬───────────┬───────────┬───────────┐
│ TEMPERATURA │ CORRENTE │ │ QC (W/m) │ QR (W/m) │ QS (W/m) │ RI² (W/m) │
│CONDUTOR (°C)│CONDUTOR (A)│ │ │ │ │ │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 45.0 │ 460. │ │ 26.9 │ 5.7 │ 18.4 │ 14.1 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 50.0 │ 608. │ │ 35.9 │ 7.8 │ 18.4 │ 25.3 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 55.0 │ 724. │ │ 45.0 │ 10.0 │ 18.4 │ 36.5 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 60.0 │ 821. │ │ 54.1 │ 12.2 │ 18.4 │ 47.9 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 65.0 │ 906. │ │ 63.2 │ 14.6 │ 18.4 │ 59.4 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 70.0 │ 982. │ │ 72.4 │ 17.1 │ 18.4 │ 71.1 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 75.0 │ 1050. │ │ 81.6 │ 19.7 │ 18.4 │ 82.9 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 80.0 │ 1114. │ │ 90.8 │ 22.5 │ 18.4 │ 94.8 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 85.0 │ 1172. │ │ 100.1 │ 25.3 │ 18.4 │ 107.0 │
├─────────────┼─────────────┤ ├───────────┼───────────┼───────────┼───────────┤
│ 90.0 │ 1227. │ │ 109.4 │ 28.3 │ 18.4 │ 119.3 │
└─────────────┴─────────────┘ └───────────┴───────────┴───────────┴───────────┘

Obs: QC - perda de calor por convecção QR - perda de calor por irradiação


QS - ganho de calor do sol RI² - ganho de calor por efeito Joule
1
ANEXO III

CAMPO ELÉTRICO SUPERFICIAL DOS CABOS CONDUTORES


╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO :

Eixos de referência .................. SOLO/LINHA DE CENTRO DA ESTRUTURA


Densidade relativa do ar ............. 0.91
Indice pluviométrico (mm/h) .......... 10.00
Número de circuitos .................. 1
Número de pára-raios ................. 2

DADOS REFERENTES AO(S) CIRCUITO(S) :

CIRCUITO 1

Cabo condutor :

Tipo ................................. CAA


Bitola ............................... 954 kCM
Formação ............................. 45/7
Diâmetro (mm) ........................ 29.59
Flecha média (m) ..................... 20.18
Fator de superfície .................. 0.82
Número de subcondutores por fase ..... 2
Distância entre subcondutores (m) .... 0.46

Disposição geométrica das fases :

x y
(m) (m)
FASE "A" -3.70 28.60
FASE "B" 3.70 28.60
FASE "C" 3.70 34.00

Tensão nominal do circuito (kV) : 242.0


Perda corona trifásica em tempo bom (kW/km) : 1.50

Ângulo das tensões nas fases :

ÂNGULO
(°)
FASE "A" 0.0
FASE "B" 240.0
FASE "C" 120.0
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS REFERENTES AO(S) PÁRA-RAIOS :

PÁRA-RAIOS TIPO 1

Tipo ................................. ACO GALV.EAR


Bitola ............................... 3/8"
Formação ............................. 7 FIOS
Diâmetro (mm) ........................ 9.14
Flecha média (m) ..................... 16.28

PÁRA-RAIOS TIPO 2

Tipo ................................. OPGW


Bitola ............................... 55 mm²
Formação ............................. 8 FIOS
Diâmetro (mm) ........................ 11.00
Flecha média (m) ..................... 16.28

Disposição geométrica dos pára-raios :

x y TIPO
(m) (m)
Pára-raios 1 -3.70 39.55 1
Pára-raios 2 3.70 39.55 2
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERDA CORONA 3Ø COM CHUVA, CAMPO ELÉTRICO CRÍTICO DE CORONA E SUPERFICIAL MÁXIMO :

┌──────────┬───────────┬───────────────────────────────────┐
│ │ │ CAMPO ELÉTRICO │
│ │ PERDA ├──────────┬────────────────────────┤
│ │ CORONA 3Ø │ CRÍTICO │ SUPERFICIAL MÁXIMO │
│ CIRCUITO │ COM CHUVA │ - Peek - ├─────────────┐ │
│ │ │ │ SUBCONDUTOR │ │
│ │ (kW/km) │ (kVp/cm) ├──────┐ │ (kVp/cm) │
│ │ │ │ FASE │ │ │
├──────────┼───────────┼──────────┼──────┼──────┼──────────┤
│ 1 │ 4.6 │ 28.17 │ A │ 1 │ 15.66 │
│ │ │ │ ├──────┼──────────┤
│ │ │ │ │ 2 │ 15.24 │
│ │ │ ├──────┼──────┼──────────┤
│ │ │ │ B │ 1 │ 16.68 │
│ │ │ │ ├──────┼──────────┤
│ │ │ │ │ 2 │ 16.93 │
│ │ │ ├──────┼──────┼──────────┤
│ │ │ │ C │ 1 │ 16.24 │
│ │ │ │ ├──────┼──────────┤
│ │ │ │ │ 2 │ 16.38 │
└──────────┴───────────┴──────────┴──────┴──────┴──────────┘
CORRENTE MÁXIMA INDUZIDA EM PESSOAS TOCANDO VEÍCULOS :

┌─────────────────────────────────────────────┬──────────┐
│ │ CORRENTE │
│ DIMENSÃO DO V E Í C U L O │ INDUZIDA │
│ │ (mA) │
├─────────────────────────────────────────────┼──────────┤
│ CARROS DE PASSEIO │ 0.9 │
│ (pequeno porte) │ │
├─────────────────────────────────────────────┼──────────┤
│ CAMINHONETAS E VEÍCULOS GRANDES DE FAZENDA │ 1.8 │
│ (médio porte) │ │
├─────────────────────────────────────────────┼──────────┤
│ ONIBUS E GRANDES CAMINHÕES │ 3.1 │
│ (grande porte) │ │
└─────────────────────────────────────────────┴──────────┘
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERFIL DE CAMPO ELETRICO NO SOLO

Coordenada X Inicial (m).................. -20.00


Coordenada X Final (m).................... 20.00
Incremento (m)............................ 1.00
Campo Eletrico Maximo no Solo (kVrms/m)... 3.97

d (m) E (kVrms/m)

-20.00 0.68
-19.00 0.77
-18.00 0.88
-17.00 1.01
-16.00 1.16
-15.00 1.34
-14.00 1.54
-13.00 1.78
-12.00 2.05
-11.00 2.36
-10.00 2.70
-9.00 3.06
-8.00 3.40
-7.00 3.70
-6.00 3.91
-5.00 3.97
-4.00 3.86
-3.00 3.55
-2.00 3.11
-1.00 2.65
0.00 2.37
1.00 2.40
2.00 2.69
3.00 3.03
4.00 3.28
5.00 3.36
6.00 3.28
7.00 3.08
8.00 2.80
9.00 2.50
10.00 2.20
11.00 1.93
12.00 1.69
13.00 1.49
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV SERRA DA MESA - NIQUELANDIA C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERFIL DE CAMPO ELETRICO NO SOLO

d (m) E (kVrms/m)

14.00 1.32
15.00 1.18
16.00 1.06
17.00 0.96
18.00 0.87
19.00 0.80
20.00 0.73
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 1 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS GERAIS DE PROJETO :

Eixos de referência .................. SOLO/LINHA DE CENTRO DA ESTRUTURA


Densidade relativa do ar ............. 0.91
Indice pluviométrico (mm/h) .......... 10.00
Número de circuitos .................. 1
Número de pára-raios ................. 2

DADOS REFERENTES AO(S) CIRCUITO(S) :

CIRCUITO 1

Cabo condutor :

Tipo ................................. CAA


Bitola ............................... 954 kCM
Formação ............................. 45/7
Diâmetro (mm) ........................ 29.59
Flecha média (m) ..................... 20.18
Fator de superfície .................. 0.82
Número de subcondutores por fase ..... 1
Distância entre subcondutores (m) .... 0.00

Disposição geométrica das fases :

x y
(m) (m)
FASE "A" -3.50 28.60
FASE "B" 3.50 28.60
FASE "C" 3.50 34.00

Tensão nominal do circuito (kV) : 242.0


Perda corona trifásica em tempo bom (kW/km) : 1.50

Ângulo das tensões nas fases :

ÂNGULO
(°)
FASE "A" 0.0
FASE "B" 240.0
FASE "C" 120.0
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 2 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

DADOS REFERENTES AO(S) PÁRA-RAIOS :

PÁRA-RAIOS TIPO 1

Tipo ................................. ACO GALV.EAR


Bitola ............................... 3/8"
Formação ............................. 7 FIOS
Diâmetro (mm) ........................ 9.14
Flecha média (m) ..................... 16.28

PÁRA-RAIOS TIPO 2

Tipo ................................. OPGW


Bitola ............................... 55 mm²
Formação ............................. 8 FIOS
Diâmetro (mm) ........................ 11.00
Flecha média (m) ..................... 16.28

Disposição geométrica dos pára-raios :

x y TIPO
(m) (m)
Pára-raios 1 -3.50 39.15 1
Pára-raios 2 3.50 39.15 2
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 3 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERDA CORONA 3Ø COM CHUVA, CAMPO ELÉTRICO CRÍTICO DE CORONA E SUPERFICIAL MÁXIMO :

┌──────────┬───────────┬───────────────────────────────────┐
│ │ │ CAMPO ELÉTRICO │
│ │ PERDA ├──────────┬────────────────────────┤
│ │ CORONA 3Ø │ CRÍTICO │ SUPERFICIAL MÁXIMO │
│ CIRCUITO │ COM CHUVA │ - Peek - ├─────────────┐ │
│ │ │ │ SUBCONDUTOR │ │
│ │ (kW/km) │ (kVp/cm) ├──────┐ │ (kVp/cm) │
│ │ │ │ FASE │ │ │
├──────────┼───────────┼──────────┼──────┼──────┼──────────┤
│ 1 │ 11.0 │ 28.17 │ A │ 1 │ 21.32 │
│ │ │ ├──────┼──────┼──────────┤
│ │ │ │ B │ 1 │ 22.50 │
│ │ │ ├──────┼──────┼──────────┤
│ │ │ │ C │ 1 │ 22.00 │
└──────────┴───────────┴──────────┴──────┴──────┴──────────┘
CORRENTE MÁXIMA INDUZIDA EM PESSOAS TOCANDO VEÍCULOS :

┌─────────────────────────────────────────────┬──────────┐
│ │ CORRENTE │
│ DIMENSÃO DO V E Í C U L O │ INDUZIDA │
│ │ (mA) │
├─────────────────────────────────────────────┼──────────┤
│ CARROS DE PASSEIO │ 0.6 │
│ (pequeno porte) │ │
├─────────────────────────────────────────────┼──────────┤
│ CAMINHONETAS E VEÍCULOS GRANDES DE FAZENDA │ 1.3 │
│ (médio porte) │ │
├─────────────────────────────────────────────┼──────────┤
│ ONIBUS E GRANDES CAMINHÕES │ 2.2 │
│ (grande porte) │ │
└─────────────────────────────────────────────┴──────────┘
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 4 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERFIL DE CAMPO ELETRICO NO SOLO

Coordenada X Inicial (m).................. -20.00


Coordenada X Final (m).................... 20.00
Incremento (m)............................ 1.00
Campo Eletrico Maximo no Solo (kVrms/m)... 2.82

d (m) E (kVrms/m)

-20.00 0.46
-19.00 0.53
-18.00 0.60
-17.00 0.69
-16.00 0.79
-15.00 0.91
-14.00 1.06
-13.00 1.22
-12.00 1.41
-11.00 1.63
-10.00 1.87
-9.00 2.12
-8.00 2.37
-7.00 2.60
-6.00 2.76
-5.00 2.82
-4.00 2.76
-3.00 2.56
-2.00 2.27
-1.00 1.95
0.00 1.74
1.00 1.76
2.00 1.94
3.00 2.16
4.00 2.32
5.00 2.36
6.00 2.29
7.00 2.14
8.00 1.95
9.00 1.74
10.00 1.53
11.00 1.35
12.00 1.19
13.00 1.05
╔═════════════════════════════════════════════════════════════════════════════════════════════════════════╗
║ ║
║▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ F L U X O E N G E N H A R I A ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒║
║ ║
║ --------------------- TRANSENERGIA GOIAS ----------------------- ║
║ LT 230 kV NIQUELANDIA - BARRO ALTO C2 ║
║ CAMPO ELÉTRICO E TENSÕES INDUZIDAS EM LINHAS DE TRANSMISSÃO ║
║ ║
║ DATA: 13/01/10 REFERÊNCIA: 3.67.02-A4-004 PÁGINA: 5 ║
║ ║
╚═════════════════════════════════════════════════════════════════════════════════════════════════════════╝

PERFIL DE CAMPO ELETRICO NO SOLO

d (m) E (kVrms/m)

14.00 0.94
15.00 0.84
16.00 0.76
17.00 0.68
18.00 0.62
19.00 0.57
20.00 0.52