Você está na página 1de 29

ValmetDNA Engineering Web Diagnostics

Backup Server Management (BsTool)


Conexão VNC (visualizador)
ValmetDNA Engineering Web Diagnostics
• Verifique a estrutura do ValmetDNA
• Diagnóstico de falha de componentes
• Vista para
capacidade, versão,
backup de dados e
licenças
• Geração de alarme
do sistema

2
Para iniciar o ValmetDNA Engineering Web Diagnostics
Para iniciar o ValmetDNA
Engineering Web
Diagnostics
http://server:7070/

Selecione a atividade (Node)

3
ValmetDNA Engineering Web Diagnostics - Capacidade

4
ValmetDNA Engineering Web Diagnostics - Versão

5
ValmetDNA Engineering Web Diagnostics – Backup de dados

6
Engineering Web Diagnostics – Módulo de geração de alarme

7
Módulos de alarme gerados → ValmetDNA Operate

• Status do grupo de IO
• Tipo de unidades / slots vazios
de IO
• Status da unidade de IO
versão do sw
• Atual e última falha

8
ValmetDNA Engineering Web Diagnostics – Licenças

9
ValmetDNA Engineering Web Diagnostics – Carga do CPU

10
ValmetDNA Engineering Web Diagnostics – Hierarquia

11
ValmetDNA Engineering Web Diagnostics – Informação de I/O

12
ValmetDNA Engineering Web Diagnostics - Informações

13
Backup Server Management (BsTool)
BsTool e Backup Server Management

O programa BsTool é usado no servidor de atividade de


engenharia (EAS) primeiramente para manutenções e
modificações do sistema. O BsTool possui comandos que podem
ser usados para o seguinte:
• Modificar a configuração do sistema
• Modificar a configuração do CPU
• Pacotes de controle de aplicativos
• Executar configuração para operações de backup/restauração
• Falhas de tela/monitor
Backup Server Management (Interface gráfica de usuário). O BsTool é um aplicativo de console que é usado
para trabalhar com o servidor de Backup da ValmetDNA (BU). O objetivo do Backup Server Management é
esconder comandos do BsTool por trás da interface gráfica do usuário , que alivia o usuário de lembrar
comandos longos e de vez enquando complexos. Backup Server Management não suporta todos os
comandos do BsTool mas os mais usados são suportados. Algumas das ações do Backup Server
Management combina dois ou mais comandos do BsTool para realizar ações mais trabalhosas.
15
Backup Server Management – Parâmetros de comunicação

Servidor Backup
Endereço HW

No exemplo o Backup Server Management usa as versões > BsTool_8.8_exe & all_8.5_types

16
Backup Server Management – Configuração do servidor

17
Backup Server Management – Configuração do grupo

18
Backup Server Management – Diagnósticos & Comandos

BOOSER

19
Backup Server Management – Errlog

20
Backup Server Management – Os códigos do Errlog

FIRST FIELD : SECOND FIELD : SECOND FIELD (continues…) :


0 Notice 0 Command handled 63 Connection to external data with name ... was cut off...
1 Module error 1 Station started 64 Lack of memory
2 Type error 7 Cannot find port with type ktstat (MODSTAT ) from module 65 Control task is overloaded ...
3 Resource error interface 66 Lack of execution capacity
4 Usage error 8 Name is already in system 72 Backup station .. disk ... is duplicated
5 Other Error 9 Module execution interval is not suitable. 73 Station ... is starting
6 Warning 10 Externals transfer mode in unknown 74 In backup station ... disk... is formatted
7 BU-notice 11 There is no FBC/DCU in card slot , specified in I/O-module. 75 In backup station ... disk... is emptied
8 BU-error 12 Channel address specified in I/O-module is in use 76 In backup station ... disk... is copied
18 Unknown type in module 77 In backup station ... disk... is restored
19 Unknown version of the type in module 78 In backup station ... disk... is master copied from...
20 Unknown type for unit FBC/DCU 79 In backup station ... status of disk... is ...
26 Out of memory 80 In backup station ... is disk... active
27 Name server has no more names (first number in names... 91 In backup station... peripheral device error in disk...
28 Name server has no more directory nodes (second number...) 92 In backup station... on disk...file system is faulty
29 Out of execution capacity of the station 93 In backup station... configuration... is faulty
30 Out of control tasks, maximum is ... 94 In backup station... there is internal error ...
31 Too many modules in control task, maximum is... 95 In backup station... duplication of disk... is not identical...
32 Out of memory in plug-in unit FBC/DCU 96 Station... cannot load.... Check cpu-configuration file.
33 Too many connections to the plug-in unit FBC/DCU 97 Cannot send to station...
39 Module reserved 98 Station... has a member..., that cannot be send to
40 There has not been time to delete I/O-module from... 99 Cannot copy file... to file...
41 Unknown command 100 Cannot find module... from system
42 User has no authorization to configure station 101 Syntax error in station... cpu-configuration file
43 Control task has 2 outputs connected to the same I/O channel 102 In backup station... primary and secondary partition...
44 Inconsistent command: no such module in station
45 Cannot read file from backup station
50 System error THIRD FIELD :
56 Cannot find external data with name... 0 No comments
57 External data with name ... has wrong type... 1 Command not handled
58 External data with name ... has wrong version of type... 2 Handling of module interrupted
59 Module’s destination differs from station name 3 External data connection not made
60 Cannot get connection to I/O card... 4 Some connections failed
61 I(O-module uses wrong card type. Type of I/O-card... 5 Cannot start station
62 External data with name ... connects to I/O module... 6 Cannot transmit command

→ Aviso!!!! Módulo pr:123FI-002 tem entrada externa pr:123FI-002.I:m, que não se encontra no GP01

21
Backup Server Management – Modificações do arquivo

• Selecione o arquivo no BU Explorer


• "Arraste e solte“ o aquivo no PC Explorer
• Modifique o arquivo no PC Explorer com o Notepad ou
Wordpad
• "Arraste e solte“ o aquivo de volta para o BU Explorer

22
Conexão VNC (visualizador)
ValmetDNA Program Starters –> Slot Controller
• ValmetDNAProgram Starter é um programa usado para controlar a operação de programas do
ValmetDNA sob o Windows. Ele Inicia todos os programas que são especificados para ser iniciado
automaticamente ao iniciar do sistema, sem a necessidade do usuário fazer log-in.
• ValmetDNAProgram Starter é usado com o ValmetDNA PCS/LIS/EDR-NT/ACN, BU-NT/ACN e ALP-
NT/ACN.
• Ele não é usado com NT-OPS, o NT-OPS é iniciado com o seu próprio arquivo xxx.bat.
• As operações do ValmetDNAProgram Starter são baseadas nas definições do arquivo de
configuração.
• O arquivo de configuração tem todas as configurações para variáveis comuns do ambiente e dos
slots individuais.
• Geralmente ele é colocado para o diretório D:/dna e ele é nomeado como <endereço_hw>.sys (por
exemplo D:/dna/261.sys).

• stop, para um servidor de cada vez


• start, inicia um servidor de cada vez
• all slots para/inicia todos os servidores de uma vez.
Ele é usado especialmente antes que o PC é
reiniciado
• Show log mostra o log de eventos
• Edit sysfile, o arquivo do sistema pode ser editado

24
Conexões VNC no servidor ACN
Do desktop do EAS No Backup Server Management (Misc → VNC Viewer…)
Endereço IP do ValmetACN

pw4ruser

Endereço HW e Nó
25
Conexões VNC para o ACN – xslot (Slot Controller)

26
Conexões VNC para o ACN – errlogs

27
Conexões VNC para o ACN – xterm

28

Você também pode gostar