Alarm 1

April 1998

GE Power Systems
Gas Turbine

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

This alarm list doesnt purport to cover all details, nor to provide for every possible
contingency to be met during operation

Customer Specific Alarms in <C> and <RST>


DROP

SIGNAL NAME

Description

L30DIAG_C

Diagnostic Alarm <C>

001

L30FORCED

Forced Logic Signal Detected

002

LWLX4MIN

003

Cause

ACTION

The microprocessor self


checking program has uncovered a control panel
problem.

Call up diagnostic display.

Injection to Fuel Ratio


LowFour Minute Average

Steam (water) injection


flow four minute average
low.

Check steam (water) injection system.

LWLXHR

Injection to Fuel Ratio


LowHourly Average

Steam (water) injection


flow one hour average
low.

Check steam (water) injection system.

004

L30TXA_C

Exhaust Temperature High


<C>

High median exhaust temperature calculated in


<C>.

Lower load to reduce exhaust temperature.


Investigate.

005

L86TXT_C

Exhaust Over temperature


Trip <C>

Turbine has tripped due to


high median exhaust temperature.

Investigate.

064

L30DIAG_Q

Diagnostic Alarm <Q>

The microprocessor self


checking program has uncovered a control panel
problem.

Call up diagnostic display.

065

L43DIAG_ALM

OffLine Diagnostics
Running

Offline diagnostic operation has been selected.

Do not start unit until diagnostics are complete.

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be desired or
should particular problems arise which are not covered sufficiently for the purchasers purposes the matter should be
referred to the GE Company.
1998 GENERAL ELECTRIC COMPANY

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

066

L43MAINT

Maintenance Forcing
Mode Enable

Auto calibrate, memory


changing or logic forcing
mode of operation has
been selected.

When done with the operation, deselect the


operation.

067

L5E_ALM

Manual Trip

The emergency stop push Correct abnormality that caused the operabutton has been pressed.
tor to push the emergency stop pushbutton.

068

L86MP

Master Protective Startup


Lockout

Within the turbine control


panel the three microprocessor controllers R, S and
T are in disagreement for
the proper condition of the
Master Protective logic
4X.

Determine which controller is in disagreement with the other two.

069

L4ETR_FLT

Protective Module ETR


Relay Trouble

Trip due to master protective relay (4s) circuit has


a problem.

Isolate <P> Protective Module and correct


the problem.

070

L12H

Electrical Over speed


Trip HP

The speed control system


has not limited HP turbine
speed within the trip limits.

Isolate problem and correct.

071

L12HFD_C

Control Speed Signal


Trouble HP

HP speed pickup voting


mismatch in <C>.

Check and recalibrate HP speed pickups.

072

L12H_P_ALM

Protective Module Overspeed Trip HP

<P> module HP overspeed Investigate cause of overspeed.


trip.

073

L12HFD_P

Control Speed Signal


Trouble HP

HP speed pickup voting


mismatch in <P>.

Check and recalibrate HP speed pickups.

074

L83HOST

Overspeed Test Mode Selected HP

HP overspeed trip being


tested.

See Overspeed Trip Checks section of


text.

075

L12HBLT_ALM

Overspeed Bolt Trip HP

The speed control system


has not limited turbine
speed within the trip limits.

Isolate problem and correct.

076

L30TNH_DIFF

HP Speed Signal Differential Alarm

One of the HP speed sensors is showing a different


speed than the other two.

Check HP speed pickups.

076

L30TNI_DIFF

IP Speed Signal Differential Alarm

One of the IP speed sensors is showing a different


speed than the others.

Check IP speed pickups.

077

L12L

Electrical Overspeed
Trip LP

The speed control system


has not limited LP turbine
speed within the trip limits.

Isolate problem and correct.

078

L12LFD_C

Control Speed Signal


Trouble IP

079

L12L_P_ALM

Protective Module Overspeed Trip LP

<P> module LP overspeed


trip.

Investigate cause of overspeed.

System Description

Gas Turbine

080

L12LF_P

Protective Speed Signal


Trouble LP

LP speed pickup voting


mismatch in <P>.

Check and recalibrate LP speed pickups.

081

L83LOST

Overspeed Test Mode Selected LP

LP overspeed trip being


checked.

See Overspeed Trip Checks section of


text.

082

L30TNL_DIFF

LP Speed Signal Differential Alarm

One of the LP speed sensors is showing a different


speed than the other two.

Check HP speed pickups.

083

L30TNI_DIFF

IP Speed Signal Differential Alarm

084

L3A

Turbine Underspeed

Turbine has bogged down.

Reduce the load that will be applied to the


generator before reclosing the generator
breaker.

085

L4CT_ALM

Customer Trip

Customer trips input to the Determine which of the customer trip deL4CT logic have caused
vices caused the trip and correct.
an automatic trip of the
unit.

086

L3CP_ALM

Customer Start Inhibit

Customer contact input


not enabled.

Check customers permissive.

087

L48

Turbine Incomplete Sequence

Failure of unit to reach


complete sequence.

Check equipment which is causing the


problem in the normal sequence.

088

L62TT2_ALM

Failure to Start

The master protective logic signal L4 has not


been set within 30 seconds
of the start signal, has
tripped the unit twice or, if
the unit is operating in remote, flame was not established after two tries.

Check all signals making up the L4 logic


signal to determine which caused the problem, or determine cause of lack of flame
establishment.

089

L30FD_ALM

Failure to Ignite

Failure to fire within the


one minute period.

Check that ac power is supplied to the ignition system.

090

L28FD_ALM

Flame Detector Trouble

One of the detectors operating when no flame is


present.

Check for proper operation of the flame


detection system. Check that the flame detector quartz window are clean.

091

L28FDT

Loss of Flame Trip

Failure of one of the detectors to detect flame.

Check for following: fuel being supplied to


the combustors, flame in all chambers, damaged crossfire tubes, or combustors. Check
for proper control valve position and fuel
pressure.

092

L28FD_SD

Chamber Flamed Out During Shutdown

Flame loss during fired


shutdown period.

Investigate cause and remedy before restarting turbine. Monitor vibration on the way
up.

093

L3COM_B_ALM Common IO Communication Loss

<C> processor is no longer communicating.

Check <C> power supply card and cabling.

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

094

L2SFT

Startup Fuel Flow Excessive Trip

Excessive fuel for startup


has been detected. For gas
fuel the gas control valve
is open too far.

Check the servo and feedback signals for


proper operation.

095

L60FSRG

FSR Gag Not at Max Limit

Manual FSR control has


Raise the manual FSR control to maximum.
not been reset to a position
where it will not interfere
with automatic FSR control.

096

L3DWRF

Loss of External Setpoint


Load Signal

097

L3TFLT

Loss of Compressor Discharge Pressure Bias

Bad signal from compressor discharge pressure


transmitter.

Check transmitter and associated connections for proper bias signal.

099

L30TFX

Turbine Air Inlet Trouble

Inlet filter excessive pressure drop or inlet filter


motor overloaded or inlet
compartment bypass door
is not in proper position.

Check the following:

Inlet filter for blockage.

Inlet filter motor for proper operation.


Inlet house bypass door.

100

L63TF1H_ALM

Turbine Air Inlet Differential Pressure Alarm

Clogged filter.

Replace filter.

101

L63TFH_ALM

Turbine Air Inlet Differential Pressure ShutDown

Clogged or iced filter.

Determine cause of blockage.

102

L63TFH_SENSR

Turbine Air Inlet Differential Pressure Switch


Trouble

Bad signal from differential pressure switch.

Check switch calibration and switch wiring.

103

L52QA_ALM

Auxiliary Lube Oil Pump


Motor Running

The main accessory gear


Examine main lube pump. Check pump outdriven lube oil pump is
put and main lube filters for leaks or plugsupplying insufficient lube ging.
oil pressure due to pump
failure or leaks

104

L72QEZ_ALM

Emergency Lube Oil Pump


Motor Running

Loss of AC power to main


lube oil pumps.

Determine cause of AC power loss.

105

L63QQ1H_ALM

Main LO Filter Diff Pressure High

Clogged filter.

Loss of fluid pressure and deterioration of


fluid purity may result. Change filter.

106

L63QTX

Low Lube Oil Pressure


Trip

Lube oil pressure has fallen below the trip level.

Determine cause and correct before restarting unit.

107

L63QAL_ALM

Lube Oil Pressure Low

Lube system leaks or


pump trouble.

Repair leaks or pump.

108

L63QT_SENSR

Lube Oil Pressure Switch


Trouble

Bad signal from lube oil


pressure switch.

Check switches and switch wiring.

109

L71QH_ALM

Lube Oil Level High

Lube oil tank level high.

Investigate cause of high level alarm and


restore normal level.

110

L71QL_ALM

Lube Oil Level Low

Lube oil tank level low.

Check for leaks, restore normal level.

System Description

Gas Turbine

111

L26QN_ALM

Lube Oil Tank Temperature Lube tank temperature beLow


low recommended limits
(see piping schematic).

Check for proper operation of the lube oil


tank heaters. Starting is inhibited if the tank
temperature is low.

112

L26QA_ALM

Lube Oil Header Temp


High

Lube header temperature


above recommended limits.

Check for proper operation of the lube oil


heat exchangers, cooling water fans (proper
rotation) and temperature regulating valve.

113

L26QT_ALM

Lube Oil Header Temp


High Trip

Lube header temperature


above recommended limits.

Check for proper operation of the lube oil


heat exchangers, cooling water fans (proper
rotation) and temperature regulating valve.

114

L26QT_SENSR

Lube Oil Temperature


Switch Trouble

Bad signal from lube oil


temperature switch.

Check switches and switch wiring.

115

L63HQ1L_ALM

Hydraulic Supply
Pressure Low

Hydraulic supply pressure


is low.

Check hydraulic supply pressure filter and


differential pressure gauge, regulating valve
or pump.

116

L63HF1H_ALM

Hydraulic Filter Differential Pressure High

Clogged filter.

Loss of fluid pressure and deterioration of


fluid purity may result. Change filter.

117

L86HD

Hydraulic Protective
Trouble

One second after the hydraulic oil trip is initiated


either the liquid fuel stop
valve is not closed or the
hydraulic trip pressure
(63HG, 63HL) has not decreased sufficiently.

Check operation of 20FL and 20HD servos.

118

L52HQ_ALM

Auxiliary Hydraulic Oil


Pump Motor Running

Accessory geardriven
hydraulic pump has not
supplied sufficient pressure because of leaks or
failure of pump.

Check hydraulic system.

119

L63HL_SENSR

Liquid Fuel Hydraulic


Pressure Switch Trouble

Bad signal from hydraulic


pressure switch.

Check switch and switch wiring.

120

L63HLL_ALM

Liquid Fuel Hydraulic Trip


Pressure Low

Low oil pressure in liquid


fuel hydraulic oil trip circuit.

Check the control oil filter and control oil


piping. This alarm will actuate if the turbine
is tripped with the manual emergency trip
valve on the turbine or a large leak were to
occur in the hydraulic trip circuit piping.

121

L63HGL_ALM

Gas Fuel Hydraulic Trip


Pressure Low

Low oil pressure in gas


fuel hydraulic oil trip circuit.

Check the control oil filter and control oil


piping. This alarm will actuate if the turbine
is tripped with the manual emergency trip
valve on the turbine or a large leak were to
occur in the hydraulic trip circuit piping.

122

L63HGL_SENSR Gas Fuel Hydraulic Pressure Switch Trouble

Bad signal from hydraulic


pressure switch.

Check switch and switch wiring.

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

123

L3SMT

Starting Device Trip

The turbine has been


tripped because the starting device has failed to
start the turbine.

Note where in the start sequence the turbine


tripped to aid in determining cause of trip.
Check the suspect system.

124

L83DT1

Diesel Test Mode


Selected

Indication that diesel test


pushbutton permissive has
been activated.

Test mode should be deselected once the


test is complete.

125

L48DSX

Diesel Failure to Start

Diesel has failure to start.

Check diesel fuel tank.

126

L2DWZ2

Diesel Failure to Break


Turbine Away

Diesel was unable to accelerate to maximum rpm.

Check diesel. Check diesel maximum


torque solenoid.

127

L4DT

Starting Device Lockout

128

L4DEY_ALM

Diesel Failure to Stop

Diesel should stop automatically after a 5 minute


cooldown period.

Check diesel stop solenoid 20DV.

129

L63QDN_ALM

Diesel Lube Oil


Pressure Low

Diesel lube oil pressure is


low.

Check diesel lube oil system.

130

L26DWH_ALM

Diesel Engine Cooling Water Temp High

Diesel cooling water temperature is high.

Check diesel cooling water system.

131

L86CRTX

Starting Motor Protective


Lockout

Cranking motor circuit


electrical fault.

Clear fault and reset 88CR.

132

L49CR_ALM

Starting Motor Overload

Starting motor is showing


an overload.

Investigate starting motor circuits.

133

L4CRT

Starting Motor Breaker Did Starting motor did not


Not Pick Up
start.

134

L30HRX1

Ratchet Trouble

Ratchet did not complete a Check for proper operation of ratchet mechprescribed motion in noranism.
mal time.

135

L30HRX2

Ratchet Did Not Start

Ratchet did not initiate a


ratchet stroke in the prescribed time.

Check ratchet permissives.

136

L49HR1A_ALM

Ratchet Motor Overload

Ratchet motor overload.

Check ratchet motor overload (MCC).


Check for proper operation of ratchet mechanism.

137

L30CD

Cooldown Trouble

Unit failed to go on cooldown, or the cooldown


cycle was aborted prior to
cooldown timer timeout.

Check ratchet system. Monitor vibration


when cooldown cycle is reinitiated.

138

L30WC_LAG

Standby Cooling Water


Pump Running

Either low cooling water


pressure, or a problem
with the main cooling water pump.

Investigate problem with cooling water system or main cooling water pump.

139

L71WL_ALM

Cooling Water Level Low

Cooling water tank level


low.

Check cooling water system for leaks.

Checking starting motor module in PECC.

System Description

Gas Turbine

140

L52FC_ALM

Cooling Fan Motor Breaker Cooling fan motor did not


Open
start.

Check cooling fan motor module in PECC.

141

L4IGVT

Inlet Guide Vane Control


Trouble Trip

IGV control system problem.

Check IGV control system.

142

L86GVA

Inlet Guide Vane Control


Trouble Alarm

IGV control system problem.

Check IGV control system.

143

L3IGVFLT

Inlet Guide Vane Position


Servo Trouble

Incorrect servo operation.

Check servos.

144

L86TCI

Compressor Inlet Thermocouples Disagree

Bad thermocouple signal. Check thermocouples and wiring and reThermocouples in the inlet place faulty thermocouple(s).
have failed, shorted or
open.

145

L86CB1

Compressor Bleed Valve


Position Trouble

Compressor bleed valves


have not operated properly. They are in the wrong
position or required an excessive amount of time to
move from one position to
the other.

Investigate problem. The problem should be


corrected before restarting. The Master Reset switch must be pressed before restarting.

146

L83KU_ALM

Turbine Compressor Abrasive Cleaning Selected

Compressor being
cleaned.

Turn function off when cleaning is complete.

147

L3WCTIM_ALM On Line Water Wash Inhib- Ambient temperature is


ited
below 50 deg F.

Wait to water wash until ambient temperature is higher.

148

L30TWW

Water Wash Inhibit Wheelspace Temp High

Turbine not sufficiently


cooled before attempting
water wash.

Allow turbine to cool to specification prior


to selection.

149

L26CTH_ALM

Control Panel Temp High

Air conditions not maintaining proper temperature.

Check air conditioners.

150

L26BT1H_ALM

Turbine Compartment
Temp High

Compartment temperature
excessive.

Check cooling air fan for proper operation.

151

L63TK_ALM

Exhaust Frame Cooling Air Exhaust frame blower moPressure Low


tor not operating. Air passages blocked.

Check motor operation. Inspect cooling air


flow passages.

152

L63ETH

Exhaust Pressure High Trip

Exhaust pressure has risen


above the trip level.

Inspect exhaust filter and ducting for blockage.

153

L63ETHX_ALM

Exhaust Pressure Switch


Trouble

Bad signal from exhaust


pressure switch.

Check switches and switch wiring.

154

L63EAH_ALM

Exhaust Pressure High


Alarm

Exhaust pressure has risen


above recommended levels.

Inspect exhaust filter and ducting for blockage.

155

L30TXA

Exhaust Temperature High

The exhaust gas temperature is excessive.

Check all thermocouples. Replace any bad


thermocouples. If problem is not thermocouples, isolate portion of Control System
causing the problem.

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

156

L86TXT

Exhaust Overtemperature
Trip

The temperature control


system has not limited exhaust temperature within
the trip limits.

Isolate problem and correct.

157

L86TFB

Exhaust Thermocouples
Open Trip

Excessive number of thermocouples not connected.

Check and reconnect thermocouples.

158

L30SPTA

Exhaust Thermocouple
Trouble

Faulty thermocouple.

Check thermocouples.

159

L30SPA

Combustion Trouble

Faulty thermocouples, gas


path hardware or uneven
distribution of fuel to the
fuel nozzles.

Analyze data for trends. At earliest shutdown check thermocouples. Perform borescope or combustion inspection. Check flow
divider fuel pressures. Check for plugged
nozzles.

160

L30SPT

High Exhaust Temp.


Spread Trip

Faulty thermocouples, gas


path parts or uneven distribution of fuel to the fuel
nozzles.

Analyze data for trends. Perform borescope


or combustion inspection. Check flow divider, fuel pressures. Check for plugged
nozzles.

161

L39VD3_ALM

Vibration Start Inhibit

Vibration protection system problem.

Check vibration protection system.

162

L39VTX_ALM

High Vibration Trip or


Shutdown

High vibration due to


Check that the hydraulic ratchet is operating
bowed rotor, mechanical
properly. Check for mechanical failures, obimbalance, bearing failure, serve vibration level on the next startup.
etc.

163

L39VD1

Vibration Sensor Disabled

Signal from vibration sensor is faulty.

Check vibration sensors and wiring.

164

L39VF

Vibration Transducer Fault

Vibration detector impedance is not within normal


bounds.

Check impedance of each vibration detector.

165

L39VA

High Vibration Alarm

High vibration at one or


more bearings.

Monitor vibration readings.

166

L39VDIFF

Vibration Differential
Trouble

Vibration protection system problem.

Check vibration protection system.

167

L3GRVFLT

Gas Ratio Valve Position


Servo Trouble

The gas ratio valve feedback signal is abnormal.

Check LVDT.

168

L3GCVFLT

Gas Control Valve Servo


Trouble

The gas control valve


feedback signal is abnormal.

Check LVDT.

169

L3GFIVP

Gas Fuel Intervalve Pressure Trouble

Pressure sensed between


the gas control valve and
the speed ratio valve is abnormal.

Check GRV control system, intervalve vent,


and pressure transducer.

170

L63FGL_ALM

Gas Fuel Pressure Low

Gas fuel pressure to turbine has been sensed as


low.

Check cause of low supply pressure.

System Description

Gas Turbine

171

L3LFLT

Liquid Fuel Control Fault

Liquid fuel checking sysDetermine abnormal condition by reading


tem has detected an abnor- signals (L3LFLT1 to L3LFLT5).
mal servo or LVDT position or signal.

172

L33FL_ALM

Liquid Fuel Stop Valve


Failure to Open

Valve or control failure.

173

L63LF1H_ALM

Liquid Fuel Filter Differen- Clogged filter.


tial Pressure High

Loss of fluid pressure and deterioration of


fluid purity may result. Change filter.

174

L30FQL_DIFF

Liquid Fuel Flow Differential Alarm

Check and recalibrate speed pickups.

175

L63LF2H_ALM

Distillate Fuel Filter Differ- Clogged filter.


ential Pressure
High

Replace filter.

176

L26FD1H_ALM

Distillate Fuel Temperature


High

Possible cooling system


problem.

Check temperature sensor and cooling system.

177

L30FD_LAG

Standby Dist Fuel Fwd


Pump Running

Low distillate fuel pressure or problem with main


dist fuel fwd pump.

Investigate fuel forwarding system and


main pump.

178

L63ADL_ALM

Atomizing Air Diff.


Pressure Low

Atomizing air compressor


not providing adequate
pressure.

Check atomizing air system.

179

L26AAH_ALM

Atomizing Air Temp. High

Failure of atomizing precooler louvers to open and


close.

Check water supply to the atomizing air


precooler, isolating valve position flow restrictions.

180

L3FUZ

Heavy Fuel Transfer Permissive Trouble

Turbine unable to transfer


to heavy fuel.

Check heavy fuel system. Be sure fuel is


warm and freeflowing.

181

L63FU2LA

Heavy Fuel Pressure Low,


Auto Xfer to Dist

Problem with heavy fuel


system.

Investigate heavy fuel system.

182

L26FU2LA

Heavy Fuel Temp Low,


Auto Xfer to Dist

Problem with heavy fuel


system.

Investigate heavy fuel system.

183

L63ADLA

A.A. Diff. Press Low, Auto


Xfer to Dist

Problem with atomizing


air system.

Investigate atomizing air system.

184

L26FL2LA

Liquid Fuel Temp Low,


Auto Xfer to Dist

Heavy fuel temperature is


low. Unit has been automatically transferred to
distillate fuel operation.

Check heavy fuel supply heating equipment.

185

L83COMF

Auto Xfer to Dist.


Communicator Failure

Communication link with


auto transfer to distillate
system failed.

Check auto transfer to distillate components


and communication system.

186

L86MAN_SYNC

Manual Synchronizing
Lockout

Manual synch lockout has


been selected on <I> CRT.
Breaker will not close.

Determine why manual synch has been


locked out. Reset using Master Reset pushbutton on <I> CRT.

Speed pickups on flow divider disagree.

Check operation of VSI and controls.

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

10

187

L86S

Auto Synchronizing
Lockout

Auto synchronizing self


checking system has detected a synchronizing
equipment abnormality.

Investigate synchronization system to determine exact cause of problem.

188

L27BN_ALM

Bus Undervoltage
No Auto Synch

Bus synchronizing potential not available.

Check bus PT fuses and wiring. Do not use


auto synchronizing or manual synchronizing until problem is resolved.

189

L3Z

Failure to Synchronize

Unit did not synchronize


and close generator breaker within the normal expected time (15 seconds).

Check all signals going making up the L4


logic signal to determine which caused the
problem or determine the cause of lack of
flame establishment.

190

L94EK

Exciter Rect Cooling


Trouble Trip 52G

Breaker has tripped and


machine is at FSNL because of problem with exciter rectifier cooling.

Investigate exciter rectifier cooling system.

191

L30EK

Prim Exciter Rect Cooling


Fan Trouble

Problem with primary exciter rectifier cooling fan.

Determine and correct problem with primary exciter rectifier cooling fan.

192

L30EKR

Stby Exciter Rect Cooling


Fan Running

Problem with primary exciter rectifier cooling fan.

Determine and correct problem with primary exciter rectifier cooling fan.

193

L26SFH_ALM

Exciter Rectifier Bridge


Temp High

Possible cooling system


problem.

Check exciter rectifier cooling system.

194

L59E_ALM

Exciter Overvoltage

Excessive field volts have


been detected.

Check exciter.

195

L49GH_ALM

Generator Stator Temp


High

Generator stator temperature is excessive caused by


lack of cooling or overload.

The generator should not be operated when


the stator temperature is excessive. Check
cooling system, reduce overload on generator.

196

L86TGT_ALM

Generator Differential Trip

A generator panel protective device has tripped the


86G lockout relay.

Determine which protective device tripped


the 86G and correct the abnormality that
precipitated the trip.

197

L52G_ALM

Generator Breaker Tripped

Generator breaker has


been tripped by an automatic protective device or
manually.

Determine device that tripped the breaker.

198

L64F_ALM

Generator Field Ground

A ground on the generator


field has been detected.

Operation of the generator with the field


grounded is not recommended as a second
ground could result in excessive damage to
the generator field.

199

L71WG_ALM

Liquid Detected in Generator

Excessive liquid in bottom


of generator.

Remove liquid and take corrective action to


prevent recurrence of problem.

200

L63BQL_ALM

Generator Bearing Vacuum


Low

Generator bearings are


sealed by vacuum. This
alarm indicates a potential
problem with the sealing
system.

Investigate generator bearing sealing system.

System Description

Gas Turbine

201

L63CA3L_ALM

Gen Air Filter Cleaner


Pressure Low

Generator air inlet filter


cleaning system problems.

Check air inlet filter cleaning components.

202

L63GFH_ALM

Generator Air Filter High


Pressure Drop

High pressure differential


across generator air inlet
filters.

Inspect and clean/change filter elements, as


required.

203

L33GCC_ALM

Generator CO2 Door


Trouble

Generator CO2 door is


closed.

Door must be opened and the latch reset.

204

L94GEN

Generator Ventilation
Trouble Shutdown

Temperature in generator
Check generator ventilation system for
compartment exceeds lim- proper fan/motor operation. Check ventilaits. Vent fans inoperable or tion dampers for proper operation/position.
insufficient to handle ventilation requirements.

205

L63CTSL_ALM

(Not Used)

206

L72ES_ALM

Emergency Seal Oil


Pump Running

Generator seal oil pressure


is low.

Check main and auxiliary seal oil supply


system components.

207

L52QS_ALM

Auxiliary Seal Oil Pump


Running

Insufficient pressure from


main seal oil supply pump.

Check seal oil supply system components.

208

L63SAL_ALM

Seal Oil Diff. Pressure Low Low seal oil pressure


across bearings.

Check seal oil system.

209

L63ST

Seal Oil Diff. Pressure Low Seal oil pressure across


Shutdown
bearings has reached shutdown setpoint.

Correct seal oil system problem before restarting.

210

L63STX_ALM

Seal Oil Press. Shutdown


Switch Trouble

Bad signal from seal oil


pressure switch.

Check switches and switch wiring.

211

L71SDH_ALM

Seal Oil Drain Liquid Level High

Seal oil drain system prob- Check generator seal oil drain system.
lem.

212

L71WGH_ALM

Generator Casing Liquid


Level High

Liquids have accumulated


in bottom of generator.

Remove liquids, check for leaks and take


action to prevent recurrence of problem.

213

L43HPA_ALM

Gen Purge System on


Manual Control

Operator has selected


manual control.

Change to automatic control.

214

L27GHN_ALM

Hydrogen Control Panel


Undervoltage

Ac power supply voltage


low.

Check power supply for proper operations.


Check wiring.

215

L63GKL_ALM

Generator Casing Hydrogen Press. Low

Low hydrogen pressure in


generator.

Check hydrogen supply system.

216

L63GL_GH_AL

Hydrogen Pressure High or


Low (Gen)

High machine gas pressure Check generator hydrogen system.


or low manifold gas pressure.

217

L63HHL_ALM

Hydrogen Pressure Low


(Skid)

Hydrogen supply skid


pressure low.

Check skid components for proper operation.

218

L30HP

Hydrogen Purity Trouble

Bad generator hydrogen


purity or purity pressure.

Check generator hydrogen system.

11

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

12

219

L94H_ALM

Generator Hydrogen Purge


Shutdown

Shutdown initiated due to


one or more hydrogen system problems, e.g., hydrogen purity has fallen to
shutdown level.

Check hydrogen cabinet for undervoltage.


Check hydrogen control switch in maintenance/auto. Check and restore hydrogen purity. Check seal unit. If purity continues to
deteriorate, a possible hazard condition may
develop.

220

L33BS_ALM

No. 3 Drain Valve Position


Trouble

Valve incorrectly positioned.

Check drain valve operations.

221

L30LTA

No. 3 Bearing Temperature


High

High number 3 bearing


temperature.

Check lube oil feed and drain piping.

222

L30LOA

Bearing Drain Temperature


High

High bearing drain temperature.

Check lube oil feed and drain piping.

223

L30BTA

Bearing Metal Temperature


High

Bearing or lube oil problem.

Check bearings and lube oil system.

223

L30BTA

Bearing Metal Temp. High

224

L30WSA1

Wheelspace Temp Differential High

Excessive differential between wheelspace thermocouples.

Check thermocouples for shorts, grounds or


opens. Replace failures. If condition persists
investigate for seal failure.

225

L30WSA2

Wheelspace Temperature
High

High wheelspace temperature.

CO2 pressure or control


problem.

Check fire protection system.

Check thermocouples, investigate for seal failure.

226

L45FAX_ALM

Fire Protection System Inoperative

227

L45FTX2_ALM

Fire In Zone #1

228

L45FTX1_ALM

Fire In Zone #2

229

L27MC1N_ALM

MCC Undervoltage

Motor control center undervoltage.

Check that power is supplied to the motor


control center.

230

L49X_ALM

Auxiliary Motor Overload

One of the auxiliary motors is overloaded.

Check auxiliary motors to determine which


motor is overloaded and the cause of the
overloading.

231

L27QEL_ALM

DC Motor Undervoltage
(Lube Oil)

DC power not supplied to Check power to DC lube pump (MCC


emergency DC lube pump. breaker on). The gas turbine should not be
operated unless DC power is available to
the emergency DC lube pump.

232

L27ESL_ALM

DC Motor UnderVoltage
(Seal Oil )

233

L27BLN_ALM

Battery Charger AC Under- Battery charger AC undervoltage


voltage.

Check battery charger AC breaker. Check


voltage magnitude.

234

L27VVN_ALM

Black Start Inverter


Trouble

Troubleshoot black start inverter.

The black start inverter


output voltage has gone
low, ignition power has
been transferred to the
MCC 12 VAC.

System Description

Gas Turbine

235

L30RHFLTX

Relative Humidity Sensor


Fault

Humidity sensor failure.

Check sensor and wiring.

236

L26JS2H_ALM

Water Skid Enclosure Temperature High

Failure of exhaust fan.

Check exhaust fan/motor components for


proper operation.

237

L26WR2L_ALM

Water Skid Enclosure Temperature Low

Failure of heaters.

Check heater and blower for proper operation.

238

L30WN

Water Injection Not Selected

NOx control water injection system inoperative.

Select Water Injection on <I> CRT.

239

L86WN1

Water Inj Suction Pressure


High Lockout

High supply pressure.

Check water supply system.

240

L86WN2

Water Injection Discharge


Pressure Low Lockout

Low supply pressure.

Check water supply system.

241

L86WN3

Water Flow High Lockout

Water injection system


Investigate water injection system.
locked out due to excessive water flow. This is
dangerous because it could
extinguish flame.

242

L86WN4

Water System Trouble


Lockout

Water injection system not


ready for use.

Check water injection system components.

243

L3WFLT_ALM

Water Flow Sensor Trouble

Water flow sensors disagree.

Recalibrate or replace faulty flow sensor.

244

L3WSFLT_ALM

Water Valve LVDT Trouble Water valve LVDTs disagree.

Recalibrate or replace faulty LVDT.

245

L3WFD_ALM

Water Flow Feedback


Trouble

A disagreement between
the water flow sensors has
been detected.

Determine failed sensor and replace.

246

L30SJ

Steam Injection Not Selected

NOx control steam injection system inoperative.

Select Steam Injection on <I> CRT.

247

L60STLA_ALM

Steam Temperature Low

Low steam temperature.

Increase steam temperature.

248

L60STLT_ALM

Steam Temperature Low


Lockout

Low steam temperature.

Correct steam temperature before restarting.

249

L60STHA_ALM

Steam Temperature High

High steam temperature.

Reduce steam temperature.

250

L60STHT_ALM

Steam Temperature High


Lockout

High steam temperature.

Correct steam temperature before restarting.

251

L60SPLA_ALM

Steam Pressure Low

Low steam pressure.

Increase steam pressure.

252

L60SPLT_ALM

Steam Pressure Low Lockout

Low steam pressure.

Correct steam pressure before restarting.

253

L60SPHA_ALM

Steam Pressure High

High steam pressure.

Reduce steam pressure.

254

L60SPHT_ALM

Steam Pressure High Lockout

High steam pressure.

Correct steam pressure before restarting.

255

L60WL1_ALM

Steam Flow High

Excessive steam flow.

Check steam system.

256

L60WQPL_ALM

Steam Flow High Lockout

Excessive steam flow.

Correct problem before restarting.

257

L60ATLA_ALM

Steam Augmentation
Low Temperature

Low steam temperature.

Increase steam temperature.

13

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

14

258

L60ATHA

Steam Augmentation
High Temperature

High steam temperature.

Reduce steam temperature.

259

L60ATLT_ALM

Steam Augmentation
Low Temp. Trip

Steam augmentation system tripped due to low


temperature.

Correct problem before restarting steam


augmentation.

260

L60ATHT_ALM

Steam Augmentation
High Temp. Trip

Steam augmentation system tripped due to high


temperature.

Correct problem before restarting steam


augmentation.

261

L60APLA_ALM

Steam Augmentation
Low Pressure

Low steam pressure.

Increase steam pressure.

262

L60APHA

Steam Augmentation
High Pressure

High steam pressure.

Reduce steam pressure.

263

L60APLT_ALM

Steam Augmentation
Low Pressure Trip

Steam augmentation system tripped due to low


pressure.

Correct problem before restarting steam


augmentation.

264

L60APHT_ALM

Steam Augmentation
High Pressure Trip

Steam augmentation system tripped due to high


pressure.

Correct problem before restarting steam


augmentation.

265

L3NZFLT

Nozzle Control Servo


Trouble

Problem with second stage Check servo wiring and hydraulic oil sysnozzle servo.
tem.

266

L3LFP_FLT

Liquid Fuel Pump Control


Trouble

Problem with one or more


control devices.

267

L63QQ2H_ALM

Trip Oil Filter Diff Pressure Clogged filter.


High

Replace filter.

268

L63QQ3H_ALM

Coupling Oil Filter Diff


Pressure High

Clogged filter.

Replace filter.

269

L63FLZ_ALM

Failure to Establish
Liquid Fuel Press.

Liquid fuel forwarding


system problem.

Check that power is being supplied to liquid


fuel forwarding pump/motor. Troubleshoot
per system components per instructions.

270

L63FLZ_FLT

Failure to Establish
Liquid Fuel Press.

Liquid fuel forwarding


system problem.

Check that power is being supplied to liquid


fuel forwarding pump/motor. Troubleshoot
per system components per instructions.

271

L94PGT

Gas Fuel Nozzle Purge


System Trouble Trip

Either VA131 or 2 or
20VG2 are stuck open
and machine has tripped.
Gas may be backing
through the system.

Check valves for cause. Correct positioning


prior to refire.

272

L63PGFT

Gas Fuel Nozzle Purge


System Pressure High

Problem with valves.

Determine cause of incorrect valve positioning.

273

L33PGFT

Gas Fuel Nozzle Purge


Valve Fail to Close

VA131 or 2 are obstructed.

Check valves to remove obstruction to resume purge.

274

L33PGO_ALM

Gas Fuel Nozzle Purge


Valve Fail to Open

No atomizing air flow;


VPR441 stuck.

Check valve.

275

L30HRX3

Troubleshoot liquid fuel pump control components to determine problem and correct.

System Description

Gas Turbine

276

R5E_ALM

Remote Emergency Trip

Unit was tripped with the


remote emergency trip
pushbutton.

Investigate and correct cause of trip. Manually reset pushbutton.

277

L90TKL

Exhaust Frame Cooling


System Trouble Unload

Exhaust frame cooling


fans 88TK1,2 problem
or system problem.

Investigate exhaust frame cooling system.

278

L30AC_ALM

279

L30AF_ALM

280

L52GA_ALM

Gen. Inlet Air Dirt Separator Not Running

Generator inlet air dirt


separator malfunction.

Check separator motor for proper operation.


Check supply system wiring.

281

L12HF

Control Speed Signal


Loss HP

Machine tripped due to


loss of speed signal.

Check wiring to speed pickups.

Battery DC Undervoltage

Battery system voltage is


low. Battery charger is not
functioning properly, excessive drain on the batteries, or bad cells in battery.

Check battery charger for proper operation,


correct excessive drain on battery, check for
bad cells. The gas turbine should not be operated unless DC power is available to the
emergency DC lube oil pump.

282

L27DZ_

ALM

283

L64D

Battery 125 VDC Ground

Insulation failure has resulted in a ground on the


125 VDC system.

Isolate and remove ground from the system.

284

L26GGCA

Generator Cold Gas Tempertaure High

Generator cooling air


temp as it leaves the coolers, at cplg or collector
end exceeds 145 F

Check cooling water flow to generator coolers, water pump/motor. Reduce load until
problem resolved, Check sensors.Clean
coolers, air filters.

285

L26GGHA

Generator Hot Gas Temperature High

Generator cooling air


temp as it enters the coolers, at cplg or collector
end exceeds 212 F

Check temp of air leaving the coolers and


stator temps as indication of problem
source. Check cooling water flow to generator coolers, water pump/motor. Reduce
load until problem resolved, Check sensors.Clean coolers, air filters.

286

L26GGF_ALM

Generator RTD Out Of


Limits

RTD sensors measuring


abnormal temperatures.
Sensors located for cold
gas temp, hot gas temp,
stator collector end temp,
coupling end temp

Check temp display to identify failed sensor


and replace at next outage.

287

L12H_ACC_AL
M

Protection Module Acceleration Trip HP

Rotor speed increase was


excessive, probably during startup. Protection
speed sensors triggered
trip.

If during startup, check fuel schedule. (Too


much, too soon). Check IGV operation and
position. Compressor bleed valve position?
If under load, check for load rejection (unlikely). Control speed sensors should have
detected same condition; if not check sensors and probe gaps.

15

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

16

288

L12L_ACC_AL
M

Protection Module Acceleration Trip LP

289

L12LF

Control Speed Signal


Trouble LP

290

L12LBLT_ALM

Overspeed Bolt Trip LP

291

L86LOT

Lube Oil HighTemp. Trip

292

L32DWF

293

LP speed pickup voting


mismatch.

Check and recalibrate LP speed pickups.

Generator Watts Transducer Failure

Transmitter for load feedback has failed.

Check wiring and transmitter.

L32DW_ALM

Generator Breaker Trip Reverse Power

Reverse current flow in


the generator. The generator is motoring. Selecting
STOP will decrease the
load setpoint until this
condition arises and opens
the breaker.

May require no action if stop has been


operatorselected. If not; the turbine is underspeed. Check fuel valves and supply,
IGVs, compressor bleed valves.

294

L30EK_ALM

Exciter Rect Cooling


Trouble

295

L63FLT

LIQ FUELPRESS HIGH


WHEN FIRING ON GAS

297

L48WW

Water Wash Flow Trouble


Trip

System expects flow in


wash lines within 13 sec
of initiating the wash.

Check valves, and pump in wash system.


Supply tank has water? Flow sensor is
functional? Sensor wiring?

298

L30WWX_ALM

Water Wash Compartment


Temp High/Low

Temperature switch in water wash compartment


senses abnormal temperature.

Check compartment. Check semsor /


switch calibration. Too cold: frozen pipes,
too high; possible fire.

299

L86WWX_ALM

Water Wash Skid Control


Lockout

Wash skid onbase controls have a problem.


Probably electrical.

Check skid sensors, switches and alarms.


Auto or Manual setting?

300

L30SPT5

Excessive Combustion
Trouble

301

L30ECH

Eccentricity High Alarm

302

L86GSVA

Gas Splitter Valve Control


Trouble

303

L86GSVT

Gas Splitter Valve Trouble


Trip

304

L3GSVFLT

Gas Splitter Valve Position


Trouble

305

L86GTVA

Gas Transfer Valve Control


Trouble

306

L86GTVT

Gas Transfer Valve Trouble


Trip

System Description

Gas Turbine

307

L3GTVFLT

Gas Transfer Valve Position Trouble

308

L3GCVSFLT

Secondary Gas Control


VLV Servo Trouble

309

L3GPVFLT

Gas Premix/Trim Valve


Servo Trouble

310

L86GPVA

Gas Premix/ Trim Not


TrackingAlarm

311

L86GPVT

Gas Premix/Trim Not


Tracking Trip

312

L3GCVQFLT

Quatenary Gas Control


VLV Servp Trouble

328

L39VTF

Accelerometer Fault

329

L39VTA

Accelerometer Vibration
High

330

L39VTT

Accelerometer Vibration
High Trip

331

L3CPIF

Compressor Inlet Pressure


Low Fault

376

L12H_FLTALM

Loss Of Prot. HP Speed Inputs

Defective Pick Up

Check Voting Screen

377

L3MP_ALM

Master Protective Start


Check ETR Fault

Trip boards in the <P>


core indicate the controllers do not agree about
unit status.

Thorough checkout of diagnostic and prevote data display screens.

378

L3SFLT_ALM

StartUp Shutdown <C>


Comm Failure Trip

<C> core, responsible for


many of the startup
checks, no longer has
communication with either the controllers or its
I/O.

Check communication networks DENET


and IONET. Check <C> power / power supply.

379

L59EX_V_TAL
M

EX2K Gen Voltage Or


Volts/HZ High Trip

Indication That The V/HZ


Has Exceeded The Upper
Limit

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help
Also Check GEH6121 Pg.810

380

381

L24EX_VHAAL
M

L76EX_T_ALM

EX2K Gen Volts/Hertz


High

EX2K Gen Field Over Excitation Trip

Volts To Hertz Ratio Is To


High also indicated Ar
IOS Alarm Status And
The V/HZ Reg Act LED
On

If V/HZ Active LED is Lit, lower The


Excitation Until Clear, Then Reset The
Alarm

OEL Trip Indicatio Of


Over Excitation Limit,
Gen Exceeding The Inverse I2t Fault Level #2

If V/HZ Active LED is Lit, lower The


Excitation Until Clear, Then Reset The
Alarm

If V/HZ Active LED is Clear, Reset


Alarm At IOS

If V/HZ Active LED is Clear, Reset


Alarm At IOS

17

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

382

L40EX_A_ALM

EX2K Loss Of Excitation

Loss Of Current To Field


Automatically Transfer To
The Hot Backup Core

Trouble Shoot Master 1 Core

383

L40EX_Y_ALM

EX2k Loss Of Excitation


Trip

Excitation Exceeded The


Low Level Setpoint. System Switched To Hot
Backup

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help

Bad SCR PackageTrouble


ShootThe PCMProtection
Core Should Transfer To
Hot BackUp

C\heck PCM Module

Trip Due To Current Detected In The Excitation


Module While Operating

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help

384

L30BRGFAIL_A

EX2K One Bridge Failed

385

L30DEEXTRP_A EX2K DEExcitation Trip

Also Check GEH6121 Pg.810

Also Check GEH6121 Pg.810

386

387

L46EX_PPTALM EX2K PPT Phase Unbalance Trip

L30SCRFAIL_A

EX2K SCR Conduction


Failure

Indication Of AC Line
Drop Or Imbalance Between Line To Line Voltage

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help

Problem In PCM Module.


Switched To Hot Backup

If V/HZ Active LED is Lit, lower The


Excitation Until Clear, Then Reset The
Alarm

Also Check GEH6121 Pg.810

If V/HZ Active LED is Clear, Reset


Alarm At IOS

388

L30EX_TRIP_A

EX2K Trip

Anything That Trips The


Excitation Listed In
GEH6121 Table B1

If V/HZ Active LED is Lit, lower The


Excitation Until Clear, Then Reset The
Alarm
If V/HZ Active LED is Clear, Reset
Alarm At IOS

389

L30SS_FAIL_A

StatusS Communication
Link Failed

Loss Of Link Presence Be- Check Coaxial Cables To IOS For Problemtween IOS And EX2000
Verify IOS availability At The Exciter And
Cores
Operate The Exciter Until Problem Is CorrectedGo To Gen/EX2K Control Screen,
Check Fault Code , Click On Fault Code
HelpAlso Check GEH6121 Pg.810

390

L74CR

DGP Failure Initiate Shutdown

DGP Self Test Failure To- Check DGP , Fault Report,Event Mestal Loss Of Protective
sages,Error Messages
Functions,Automatic Shutdown

DGP Has Tripped 52G

Loss Of Protective FuncCheck DGP , Fault Report,Event Mestions,Automatic Shutdown sages,Error Messages

ALM

391

18

L74G1_ALM

System Description

Gas Turbine

392

L74A_ALM

Excessive Volts Per Hertz

Ratio Between V/HZ Incorrect

Lower The ExcitationGo To Gen/EX2K


Control Screen, Check Fault Code , Click
On Fault Code HelpAlso Check GEH6121
Pg.810

393

L74B_ALM

Negative Sequencing Current

Unbalance Stator Current.Unbalance


Loads.46T=Trip,
46A=Alarm

Check The MMI Operation

Freq Distrubance , System


Fault,Unconnected Unit
Malfunction Speed Control

Check The MMI Operation

Failed Internal Checks In


The MMI

Check The MMI Operation

394

395

L74D_ALM

DGP_TRB_ALM

System Over frequency

Self Test Failure Or PWR


Supply Trouble

Usr INF KEY, Request Status Inf, Fault Inf.


Check Print Out.

Usr INF KEY, Request Status Inf, Fault Inf.


Check Print Out.

Usr INF KEY, Request Status Inf, Fault Inf.


Check Print Out.

396

LVTFFALM

Voltage XFMR Fuse Fail


Xfer To Man Reg

Lost A Voltage Feedback


Signal Transfered To The
Hot Back Up Core,If Hot
Back Up Has Lost Feedback .Core Will Transfer
To Man Reg.

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help
Also Check GEH6121 Pg.810

397

L4EXOFF_ALM

EX2K Operator Selected


Excitation Off

Normal Operation When


Operator Turns Excitation
Off An Alarm Is Displayed

None

398

L27EX_ALM

EX2K Power Supply


Source Undervoltage

Usually Low AC Voltage


Feeding The Power Supply

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help
Also Check GEH6121 Pg.810

399

L24EX_ALM

EX2K Gen Stator Volts Or


Volts/Hz High

Volts Or V/HZ Is Into A


Upper Limit

Lower Excitation

400

L76EX_ALM

EX2K Gen Field Over Excitation

To HIgh

Lower Excitation,Watch IOE Light On IOS


Panel Reset IOS , When OEL Goes OFF

401

L83EXPCM_AL
M

EX2K Xfer To BackUp


PCM/Bridge

Problem With PCM Module

Go To Gen/EX2K Control Screen, Check


Fault Code , Click On Fault Code Help
Also Check GEH6121 Pg.810

19

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

20

402

L4_FB_ALM

403

TCEA 4 Relay Circuit


FDBK (Extrnl Trip)

External (customer) trip.


A switch input wired to
the control panel trips the
turbine, when activated.

Check switch, wiring and activating parameters of switch.

L33CDMN_ALM At Min TNR Reverse Power Not Detected

Load setpoint (TNR) has


decreased to the point that
generator breaker should
be open on reverse power
protection.

Trip the unit / breaker if unit is actually experiencing reverse power. Check breaker
protection circuit, minimum TNR and reverse power control constants.

404

L86WN7

Water Injection Low Flow


Trip Water

Operation expects water


flow for Low NOx

Check valves, flow transmitter, pump, motor, minimum flow control constant. Unit
shutdown (not trip) if EPA compliance requires. Master Reset necessary to clear
alarm condition.

405

L30WFD

Water Inj. Flow Meter /Pos


FD High Diff

406

L30WQER_ALM Water Inj Servo Not Following Output

407

L27BLNALM

Batt Charger #2 AC Under- Control package is


voltage
equipped with 125 V battery pack. Pack is supplied
with autocharger from AC
supply. This equipment is
not functioning.

Check battery charger circuit. Wiring, power supply, switches. MCC voltage is okay
(sequencing checks for this).

408

LCTDA_ALM

CompDischarge Temp
High Spread

There are three thermocouples (T/C) measuring


this temperature. Minimum and maximum temperatures vary more than
50F.

Check T/Cs (physically and measurements). Vibration indicates rotor condition


(excessive heating, thrown blading). Not a
problem if water washing.

409

L3TCI_ALM

Comp Inlet Temp TC


Trouble

There are three thermocouples (T/C) measuring


this temperature. Minimum and maximum temperatures vary more than
25F.

Check T/Cs (physically and measurements). Weather will affect this. IGV position? Not a problem if water washing.

410

LFTGALM

Gas Fuel Temperature High There are three thermoSpread


couples (T/C) measuring
this temperature. Minimum and maximum temperatures vary more than
25F.

Check T/Cs (physically and measurements). Exhaust spreads may be affected.


Fuel source change / problem?

System Description

Gas Turbine

411

L33GCL_ALM

Load Compartment CO2


Door Closed

Fire protection system activation closes all


compartment ventilation
discharge vents. CO2 discharge pressure releases a
door latch.

Reset vent doors and latches.

412

L33GCG_ALM

Generator CO2 Door


Closed

Fire protection system activation closes all


compartment ventilation
discharge vents. CO2 discharge pressure releases a
door latch.

Reset vent doors and latches.

413

L63WN3H_ALM

Water Filter Diff Press


High

Differential pressure
across injection water filter is excessive.

Check actual pressure on gauge, clean filter


if pressure is high (requires injection shutdown), check switch calibration if not.

414

L86WN5_ALM

Water INJ Hyd Trip Pressure Lockout

415

L86WN6_ALM

Water INJ Stop/Isolation


Valve Lockout

416

L30CC_ALM

Fire Protection System


Trouble

Fire protection system has Check power to control panel, CO2 presa skidmounted control
sure, switches, resets. Consult equipment
panel that has detected this manual for troubleshooting chart.
problem.

417

L27_ALM

Fire Protection Trip Relay


Undervoltage

Fire protection system has Check power to control panel. Check cona skidmounted control
trol panel circuits.
panel that has detected this
problem.

418

L45FTX_ALM

Fire

Fire has been detected by


sensors in turbine
compartments. Sensors are
temperature switches, not
fireeyes.

Ensure unit has tripped. Confirm actual fire


(high compartment temperature can trigger
this response). Ensure fuel systems are
blocked and isolated. Assemble adequate
fire fighting equipment and trained personnel to ensure fire is out. CAUTION:
compartments flooded with CO2 will not
support a flame or respiration. Adequately
ventilate compartment before entering.

419

L94F1B_ALM

Fire In Zone # 1

Fire in accessory and / or


turbine compartment.

See alarm 418

420

L94F2B_ALM

Fire In Zone # 2

Fire in load compartment.

See alarm 418

421

L741_2_ALM

Generator Protection 125


VDC Power Loss

Blown Fuse

Check DC Trippin Bus

422

L86AT_ALM

Aux Transformer Lockout

Lost Power To Running


Relay

Check Power Source

21

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

423

L37GJA

Generator Breaker Cooling


Fan On Backup

Problem With One Of The


Fans

Investigate Fan Control Circuits

424

L37GJF

Generator Breaker Cooling


Failure

Problem with Both Cooling Fans

Reduce Gen enerator Out Put To The Max


Out Put Allowable W/O Cooling Fans See
Control ConstantFor setting

425

L26EX_ALM

EX2K Power Conversion


Module Temp High

A Normally Closed Overtemperature Trip Interlock


Is Open> Temp Has
Reached 170 C. Trip At
190 C

Check Fans, Control And Temp DevicesGo


To Gen/EX2K Control Screen, Check Fault
Code , Click On Fault Code HelpAlso
Check GEH6121 Pg.810Verify Temp.
Switch Circuits

426

L45HH_ALM

HIGHHIGH Gas Level


Detected

Gas Leak Or Defective


Gas Momitor

Consider A Turbine Shut Down.Investigate


Turbine Compartment ,Monitor For Gas

427

L45HL_ALM

High Gas Level Detected

Gas Leak Or Defective


Gas Momitor

Investigate Turbine Compartment ,Monitor


For Gas

428

L45HF_ALM

Gas Detector Monitor Fault Gas Leak Or Faulty Gas


Monitor

Check Gas Monitir

429

L74HT_ALM

Batt Compartment High


Temp

High Temperature Or Defective Temp Probe

Investigate Room & Temp Devices

430

L27CLN_ALM

Compartment Lighting Undervoltage

Low Voltage Or A Dip In


The Supply Course

Check AC Voltage Supply If The Source


AC Is Still Low Investage

431

L14EX_ALM

EX2K PCM/BRIDGE
Coolong Blower Failure

Bridge Temperature High


Also Indicated At IOS
Alarm Status

Check For High Bridge Temp

Check Temp Switches & Blower Motor Circuits

432

L30EX_ALM

EX2K Diagnostic Alarm

Diagnostic Faults, Also In- Attempt To Rest The Alarm At The IOS.If
dicated At IOS Diagnos- The Alarm Does Not Clesr. It Will Return
tic Display and Ex2K
Check The Coe Diagnostic Readout For
Keypad Readout
Fault Messages.Consult The Fault Listings{GEH 6121 )

433

L43_ALM

EX2K Manual (FVR) Regulator Active

Operator Tranfered To
Manual RegularSystem
Transfered From Auto To
Manual

Lost Auto Reg, Operator Must Control Gen


TerminalVolts With The Manual Regulator

434

L60EX_ALM

EX2K PT Failure Detected

PT Failure Detected Also


Indicated At IOS Bad
PT LED On Core Fault
Display,EX2K switched
To Hot BackUp Unit

Press The Ios Reset Button To Cleat.Clear


The Core Fault By Pressing Core Keypad
Rset
If Alarm Does Not Clesr, Check PT Input
At Exciter

Check Fuses, Wiring To PTs And Into Core

435

22

L94ADL

Atomizing Air Diff Press


Low Shutdown

Low Diff Press

Check Atomizing Air Compressor An Press


Switches, Check Logic Voting 2/3

System Description

Gas Turbine

436

L63ADL_SENSR Atomizing Air Diff Press


Switch Trouble

Low Diff Press

Check Atomizing Air Compressor An Press


Switches, Check Logic Voting 2/3

437

L86CBT_ALM

Incorrect Position

Check Position Of Switches

Compressor Bleed Valve


Pos Trouble Trip

Position Switch Problem

438

L20HR_ALM

Hyd Ratchet Forward


Stroke Trouble

Malfunction

Check HYD Ratchet Limit Switches

439

L2SMBA_ALM

Starting Means Failure To


BRK Turb Away

14Hr Not At Zero Speed

Check Torque Convertor & Control Circuits

Torque ConvertorFill Solenoid Logic Incorrect

440

L30HYD_ALM

HYD Supply Press Low


No HYD Ratchet

Low Hydraulic Presure

CheckHyd Pressure Gauges & Devices

441

L33HRF_ALM

Hydrauclic Ratchet Return


Stroke Trouble

Malfunction

Check HYD Ratchet Limit Switches

442

L4CRT_ALM

Start Device Lockout

Master Control Did Not


PickUp

Check Motor Control Circuit

443

L26AAL_ALM

Atomizing Air Temperature Low

Low Temperature Or Defective Device Setting

Investigate

Check Device Setting

444

L63AF_ALM

Atom Air Filter Diff Press


High

Dirty Filter

Change Filter

445

L86WN8

Wtr INJ VFD Controller


FLTTrip Water

Injection VDF Control


Fault

Check Injection Control Crkt For Fault

446

L86WN9

WTR INJ VFD In Local


Mode Trip Water

Switch In Manual Mode

Change Switch Position

447

L30WN1A_ALM

WTR Inj VFD Over Load


Early Warning

448

LNOXLOST

Loss Of NOX Fedback


Signal

Lost NOXPPM Feedback


To Monitor

Check Emission Monitor

449

L52FCX_ALM

Cooling Fans Motor Break- Current Exceeded Limit


er Open
Caused Breaker To Open

Check Out Motor Control Circuits

450

L63VL4L_ALM

Gas Compt Diff Press


Alarm

Door Open Lost Positive


Pressure

Close Door

451

L5051CRA_AL
M

Starting Motor Protection


Alarm

Timed Overcurrent Or Inrush Current To High

Check The Starting Motor Protection


Module Faults Codes Etc.

452

L30BN_F_ALM

Bently Nevada Monitor


Fault

Increased Vibrations

Check Shaft Vibrations

Check Bently Nevada Monitor System


Check GE Vibration Probes

23

Alarm 1

SPEEDTRONIC Mark V Annunciator Troubleshooting Chart

453

L39VS_A_ALM

Bently Nevada Monitor


Alarm

Increased Vibrations

Check Shaft Vibrations

Check Bently Nevada Monitor System


Check GE Vibration Probes

454

L39VS_D_ALM

Bently Nevada Monitor


Danger

Increased Vibrations

Check Shaft Vibrations

Check Bently Nevada Monitor System


Check GE Vibration Probes

455

L4BT_ALM

Standby Turb Compertment Cooling Fan RU

Lead Fan Failed To Operate

Check Lead Fan Control Circuit Thermostat


etc.

456

L4FK_ALM

Lead / Lag Fan Trouble

457

L45FE20A_ALM

WarningSmoke Alarm
GAC!!

Fire Or Electrical Component Failure

Investigate

458

L45FP22A_ALM

Warning Smoke Alarm


PEECC!!!!!

Fire Or Electrical Component Failure

Investigate

459

L45FG24A_ALM Warning Smoke Alarm


Generator !!!!!!

Fire Or Electrical Component Failure In Gen Collector Compartment

Investigate

460

L63AD4L_ALM

APU Low Air Pressure


Alarm

Insufficicent Air Available

Check APU Unit

461

L63CT_ALM

Abnormal Pressure CO2

Pressure Exceeded Device


Setting

Investigate CO2 System

GE Power Systems