Escolar Documentos
Profissional Documentos
Cultura Documentos
NS 1123603288
REVISÕES
(A) PRELIMINAR (D) PARA COTAÇÃO (G) CONFORME CONSTRUÍDO
TIPO DE
(B) PARA APROVAÇÃO (E) PARA CONSTRUÇÃO (H) CANCELADO
EMISSÃO
(C) PARA CONHECIMENTO (F) CONFORME COMPRADO (J) APROVADO
ÁREA:
USINA FOTOVOLTAICA
ESPECIALIDADE:
ELETRICA
PACOTE:
Observar proteção DIN 34.
EXECUTADO:
PHELIPPE R. 18/10/19 N.º SNEF: FOLHA: FORMATO:
VERIFICADO: 1244-G057-01-EST-00904 1 A4
R. GASPAR 18/10/19
N.º CLIENTE: DE: REVISÃO:
APROVADO:
SERGIO R. 18/10/19 - 46 02
/
SUMÁRIO
1 INTRODUÇÃO .............................................................................................4
9 COORDENOGRAMAS............................................................................... 24
Página 2 de 43
/
10 CONCLUSÃO ............................................................................................ 28
11 ANEXOS .................................................................................................... 28
Página 3 de 43
/
1 INTRODUÇÃO
Página 4 de 43
/
3 CONSIDERAÇÕES INICIAIS
4 DADOS DO SISTEMA
Página 5 de 43
/
Condutor Alumínio
Encordoamento Classe 2
Isolação XPLE – 90oC
Classe de Tensão 8,7/15 kV
Tensão de Operação 13,8 kV
Instalação Cabos em trifólio, cabos
diretamente enterrados
Tipo de cabo 3 x 1 x 35 mm2
Comprimento (m) 78 (T1) - 161 (T2) - 344 (T3)
- 400 (T4) - 479 (T5)
Impedância Positiva (Ω/Km) 0,1130 + j0,1627
Impedância Zero (Ω/Km) 0,1796 + j0,4139
Página 6 de 43
/
Página 7 de 43
/
Página 8 de 43
/
Descrição Z (Ω)
Impedância de sequência positiva do primário para o
secundário (Zps) 11,426
4.6 Inversores
Conforme manual do inversor PVS-120-TL, a especificação técnica da saída CA
dos inversores é:
Página 9 de 43
/
Página 10 de 43
/
Página 11 de 43
/
Página 12 de 43
/
Página 13 de 43
/
Página 14 de 43
/
Página 15 de 43
/
Página 16 de 43
/
6 DADOS DE CURTO-CIRCUITO
BARRA_13,8KV
Icc3Ø 3352A Icc1Ø 2319A
CEMIG 3155A CEMIG 2017A
UFV1 40A UFV1 61A
UFV2 40A UFV2 61A
UFV3 40A UFV3 61A
UFV4 40A UFV4 61A
UFV5 40A UFV5 61A
Página 17 de 43
/
Este item tem como objetivo apresentar os critérios para determinação dos
transformadores de corrente da planta solar.
Página 18 de 43
/
*01.4235
*+-./ = 8+-3/
6777
L (m): comprimento total dos condutores que ligam os relés de
proteção ao TC
Observação → Comprimento Total (L) = 2 x Distância Relé Proteção-
TC
RM (Ω/km): Resistência máxima do condutor.
;<>?4@AB C,C:C(
*9: -./ = 8+-3/ = 867 =0,06 Ω
:''' :'''
Página 19 de 43
/
Por norma, a classe de exatidão do TC deve ser maior que a tensão de saturação
encontrada nos cálculos anteriores. De posse das justificativas apresentadas
acima, a classe de exatidão para o enrolamento da proteção dos TC’s deste
empreendimento é 10B100.
6
!VKWXEYMWLFZ = M
6 6
T!
!II&[ VKWXEY
Onde:
· Icc3F é a corrente de curto-circuito trifásico do ponto de instalação do
transformador (3292 A);
· Iinrush é a corrente de Inrush do transformador, sem correção (13,73 x In =
574,42 A, conforme informado pelo fabricante).
A partir da formulação anterior, é possível definir que a corrente de In-rush real dos
transformadores é 489 A.
Página 20 de 43
/
* Curtos-circuitos na UFV
Tendo em vista que a carga demandada é muito pequena (0,85 A) e a
resolução mínima do relé (0,05 x In) é inferior a 10% da corrente nominal dos
TC’s (10 A), adotou-se um ajuste de pick-up igual a 10% da corrente nominal
dos TC’s, garantindo assim a precisão dos mesmos.
Pick-up: 7,6 × 677 = 67i
Curva: IEC Extremamente Inversa
Dial: 0,1
Multiplicador: 0,25
Limite de tensão: 70% Vnom = 9,66 kV (Segundo o manual do relé a tensão
monitorada é L-L)
Página 21 de 43
/
* Curtos-circuitos na UFV
O anexo 10 da ND 5.31 indica que deve ser adotado um valor de pick-up
igual a 30% do ajuste da unidade de fase. Tendo em vista que o valor de
30% da unidade de fase (3 A) é inferior à resolução mínima do relé (0,05 x
In), foi adotado o ajuste mínimo do relé.
Pick-up: = 5% x 100 A = 5 A
Curva: Tempo Definido
Tempo: 1 segundo
Direcionalidade: Direta (sentido Cemig Central Geradora)
Ângulo Característico: 90o
Página 22 de 43
/
A seguir é apresentada uma tabela resumo dos ajustes das funções de proteção:
Página 23 de 43
/
9 COORDENOGRAMAS
9.1 COORDENOGRAMA DE FASE (CURTOS-CIRCUITOS NA REDE DA
CEMIG)
CURRENT IN AMPERES
1000
A C B A - Corrente de partida da proteção
51V para a condição de tensão de
falta inferior à tensão de controle
(0,25 x Ip = 11,45 A)
10
TIME IN SECONDS
51V 67(1)
0.10
0.01
0.5 1 10 100 1K 10K
Página 24 de 43
/
CURRENT IN AMPERES
1000
B D A F E
A - Corrente de partida da
proteção 51V para a
condição de tensão de
falta superior à tensão
de controle
100 (1,0 x Ip = 45,8 A)
B - Corrente de partida
da proteção 67F (10 A)
C - Corrente de In-Rush
T1 do transformador (489 A)
D - Corrente nominal de
10 geração com fator de
TIME IN SECONDS
potência de 0,92
(43,65 A)
51V.
TX Inrush
0.10 C NOTA: A curva inversa da função
67F está abaixo do ponto referente
à corrente de magnetização do
transformador, no entanto, não
haverá atuação destas funções,
pois ela será bloqueada através
da detecção de corrente de
segundo harmônico durante a
energização do transformador.
0.01
0.5 1 10 100 1K 10K 100K
Página 25 de 43
/
CURRENT IN AMPERES
1000
A B A - Corrente de partida da proteção
67N (13,75 A)
100
67N(1)
10
TIME IN SECONDS
1
0.10
0.01
0.5 1 10 100 1K 10K
Página 26 de 43
/
CURRENT IN AMPERES
1000
A D C B
100
67N(2)
10
TIME IN SECONDS
1
0.01
0.5 1 10 100 1K 10K
Página 27 de 43
/
10 CONCLUSÃO
11 ANEXOS
Página 28 de 43
/
Página 29 de 43
/
Página 30 de 43
/
Página 31 de 43
/
Página 32 de 43
/
Página 33 de 43
/
Página 34 de 43
/
Página 35 de 43
/
Página 36 de 43
/
Página 37 de 43
/
Página 38 de 43
/
Página 39 de 43
/
Página 40 de 43
/
Página 41 de 43
/
Página 42 de 43
/
Página 43 de 43
Settings Editor 7SR10 - 7SR1004-3[JKL]xx0-2CA0.rsf2 Page 1 of 3
SYSTEM CONFIG
System Frequency (50..60) 60Hz
Setting Dependencies (Disabled..Enabled) Enabled
Favourite Meters Timer (Off..60) 60min
Backlight timer (Off..60) 5min
Curr Set Display (xNom..Secondary) xNom
E/F Curr Set Display (xNom..Secondary) xNom
Export Power/Lag VAr (+ve/+ve..-ve/-ve) -ve/-ve
Select Grp Mode (Edge triggered..Level triggered)
Edge triggered
Clock Sync. From BI (Disabled..Minutes) Disabled
Operating Mode (Out Of Service..Local Or Remote)
Local Or Remote
Disk Activity Symbol (Disabled..Enabled) Disabled
Unexpected Restart Blocking (Disabled..Enabled) Disabled
Setting Password (Password) NONE
Control Password (Password) 340701675
Trip Alert (Disabled..Enabled) Enabled
General Alarm Alert (Disabled..Enabled) Enabled
Relay Identifier (16 Character String) 7SR10···········
Circuit Identifier (16 Character String) ················
CT/VT CONFIG
Phase Nom Voltage (40..160) 66.4V
Phase Voltage Trim Magnitude (0..20) 0V
Phase Voltage Trim Angle (-45..45) 0deg
Phase Voltage Config (Van,Vbn,Vcn..Va,Vb,Vc) Van,Vbn,Vcn
Phase VT Ratio Prim ( 6 Character String) 13800·
Phase VT Ratio Sec (40..160) 115
Phase Current Input (1..5) 5A
Phase CT Ratio Prim ( 6 Character String) 100···
Phase CT Ratio Sec (0.2..7) 5
Earth Current Input (1..5) 5A
Earth CT Ratio Prim ( 6 Character String) 100···
Earth CT Ratio Sec (0.2..7) 5
Phase Rotation (A,B,C..A,C,B) A,B,C
FUNCTION CONFIG
Gn Phase Overcurrent (Enabled..Disabled) Enabled
Gn Voltage Cont O/C (Enabled..Disabled) Enabled
Gn Cold Load (Enabled..Disabled) Disabled
Gn Derived E/F (Enabled..Disabled) Enabled
Gn Measured E/F (Enabled..Disabled) Disabled
Gn Restricted E/F (Enabled..Disabled) Disabled
Gn NPS Overcurrent (Enabled..Disabled) Disabled
Gn Under Current (Enabled..Disabled) Disabled
Gn Thermal (Enabled..Disabled) Disabled
Gn Line Check (Enabled..Disabled) Disabled
Gn Phase U/O Voltage (Enabled..Disabled) Disabled
Gn NPS Overvoltage (Enabled..Disabled) Disabled
Gn Neutral Overvoltage (Enabled..Disabled) Disabled
Gn U/O Frequency (Enabled..Disabled) Disabled
Gn Power (Enabled..Disabled) Enabled
Gn Power Factor (Enabled..Disabled) Disabled
Gn CB Fail (Enabled..Disabled) Disabled
Gn VT Supervision (Enabled..Disabled) Enabled
Gn CT Supervision (Enabled..Disabled) Disabled
Gn Broken Conductor (Enabled..Disabled) Disabled
Gn Trip Cct Supervision (Enabled..Disabled) Disabled
Gn Close Cct Supervis'n (Enabled..Disabled) Disabled
Gn Inrush Detector (Enabled..Disabled) Enabled
Gn THD Supervision (Enabled..Disabled) Disabled
Gn CB Counters (Enabled..Disabled) Disabled
Gn I^2t CB Wear (Enabled..Disabled) Disabled
Gn Arc Flash Detector (Enabled..Disabled) Disabled
CURRENT PROT'N
PHASE OVERCURRENT
Gn 67 Char Angle (-95..95) 40deg
Gn 67 Minimum Voltage (1..20) 1V
Gn 67 2-out-of-3 Logic (Enabled..Disabled) Enabled
Gn 50 Measurement (RMS..Fundamental) RMS
Gn 51 Measurement (RMS..Fundamental) RMS
51-1
Gn 51-1 Element (Disabled..Enabled) Enabled
Gn 51-1 Dir. Control (Non-Dir..Reverse) Reverse
Gn 51-1 Setting (0.05..4) 0.45xIn
Gn 51-1 Char (DTL..ANSI-EI) IEC-EI
Gn 51-1 Time Mult (IEC/ANSI)
(0.01..100) 0.2
Gn 51-1 Min Operate Time (0..20) 0s
Gn 51-1 Follower DTL (0..20) 0s
Gn 51-1 Reset ((IEC/ANSI) Decaying..60) 0s
Gn 51-1 VTS Action (Off..Non-Dir) Non-Dir
Gn 51-1 Inrush Action (Off..Inhibit) Off
51-2
Gn 51-2 Element (Disabled..Enabled) Enabled
Gn 51-2 Dir. Control (Non-Dir..Reverse) Forward
Gn 51-2 Setting (0.05..4) 0.1xIn
Gn 51-2 Char (DTL..ANSI-EI) IEC-EI
Gn 51-2 Time Mult (IEC/ANSI)
(0.01..100) 0.1
Gn 51-2 Min Operate Time (0..20) 0s
Gn 51-2 Follower DTL (0..20) 0s
Gn 51-2 Reset ((IEC/ANSI) Decaying..60) 0s
Gn 51-2 VTS Action (Off..Non-Dir) Inhibit
Gn 51-2 Inrush Action (Off..Inhibit) Inhibit
51-3
Gn 51-3 Element (Disabled..Enabled) Enabled
Gn 51-3 Dir. Control (Non-Dir..Reverse) Non-Dir
Gn 51-3 Setting (0.05..4) 0.45xIn
Gn 51-3 Char (DTL..ANSI-EI) IEC-EI
Gn 51-3 Time Mult (IEC/ANSI)
(0.01..100) 0.2
Gn 51-3 Min Operate Time (0..20) 0s
Gn 51-3 Follower DTL (0..20) 0s
Gn 51-3 Reset ((IEC/ANSI) Decaying..60) 0s
Gn 51-3 VTS Action (Off..Non-Dir) Off
Gn 51-3 Inrush Action (Off..Inhibit) Inhibit
51-4
Gn 51-4 Element (Disabled..Enabled) Disabled
50-1
Gn 50-1 Element (Disabled..Enabled) Disabled
50-2
Gn 50-2 Element (Disabled..Enabled) Disabled
50-3
Gn 50-3 Element (Disabled..Enabled) Disabled
50-4
Gn 50-4 Element (Disabled..Enabled) Disabled
VOLTAGE CONT O/C
Gn 51V Element (Ph-Ph) (Disabled..Enabled) Enabled
Gn 51V Setting (5..200) 80.5V
Gn 51V VTS Action (Off..Inhibit) Inhibit
Gn 51-1 Multiplier (0.25..1) 1
Gn 51-2 Multiplier (0.25..1) 1
Gn 51-3 Multiplier (0.25..1) 0.25
DERIVED E/F
Gn 67N Polarizing Quantity (ZPS..NPS) ZPS
Gn 67N Char Angle (-95..95) 90deg
Gn 67N Minimum Voltage (0.33..3) 0.33V
51N-1
Gn 51N-1 Element (Disabled..Enabled) Enabled
Gn 51N-1 Dir. Control (Non-Dir..Reverse) Reverse
Gn 51N-1 Setting (0.05..4) 0.13xIn
Gn 51N-1 Char (DTL..ANSI-EI) DTL
Gn 51N-1 Delay (DTL) (0..20) 5s
Gn 51N-1 Min Operate Time (0..20) 0s
Gn 51N-1 Follower DTL (0..20) 0s
Gn 51N-1 Reset ((IEC/ANSI) Decaying..60) 0s
Gn 51N-1 VTS Action (Off..Non-Dir) Non-Dir
Gn 51N-1 Inrush Action (Off..Inhibit) Off
Settings Editor 7SR10 - 7SR1004-3[JKL]xx0-2CA0.rsf2 Page 2 of 3
51N-2
Gn 51N-2 Element (Disabled..Enabled) Enabled
Gn 51N-2 Dir. Control (Non-Dir..Reverse) Forward
Gn 51N-2 Setting (0.05..4) 0.05xIn
Gn 51N-2 Char (DTL..ANSI-EI) DTL
Gn 51N-2 Delay (DTL) (0..20) 1s
Gn 51N-2 Min Operate Time (0..20) 0s
Gn 51N-2 Follower DTL (0..20) 0s
Gn 51N-2 Reset ((IEC/ANSI) Decaying..60) 0s
Gn 51N-2 VTS Action (Off..Non-Dir) Inhibit
Gn 51N-2 Inrush Action (Off..Inhibit) Inhibit
51N-3
Gn 51N-3 Element (Disabled..Enabled) Disabled
51N-4
Gn 51N-4 Element (Disabled..Enabled) Disabled
50N-1
Gn 50N-1 Element (Disabled..Enabled) Disabled
50N-2
Gn 50N-2 Element (Disabled..Enabled) Disabled
50N-3
Gn 50N-3 Element (Disabled..Enabled) Disabled
50N-4
Gn 50N-4 Element (Disabled..Enabled) Disabled
POWER PROT'N
POWER
32-1
Gn 32-1 Element (Disabled..Enabled) Enabled
Gn 32-1 Operation (Under..Over) Over
Gn 32-1 1Ph/3Ph Power (3Ph..1Ph) 3Ph
Gn 32-1 Power (Real..Apparent) Real
Gn 32-1 Dir. Control (Non-Dir..Reverse) Reverse
Gn 32-1 Setting (0.05..2) 0.42xSn
Gn 32-1 Delay (0..14400) 15s
Gn 32-1 U/C Guard (Disabled..Enabled) Disabled
Gn 32-1 VTS Action (Off..Inhibit) Off
32-2
Gn 32-2 Element (Disabled..Enabled) Enabled
Gn 32-2 Operation (Under..Over) Over
Gn 32-2 1Ph/3Ph Power (3Ph..1Ph) 3Ph
Gn 32-2 Power (Real..Apparent) Real
Gn 32-2 Dir. Control (Non-Dir..Reverse) Forward
Gn 32-2 Setting (0.05..2) 0.1xSn
Gn 32-2 Delay (0..14400) 15s
Gn 32-2 U/C Guard (Disabled..Enabled) Disabled
Gn 32-2 VTS Action (Off..Inhibit) Off
SUPERVISION
VT SUPERVISION
Gn 60VTS Element (Disabled..Enabled) Enabled
Gn 60VTS Component (NPS..ZPS) NPS
Gn 60VTS V (7..110) 7V
Gn 60VTS I (0.05..1) 0.1xIn
Gn 60VTS Vpps (1..110) 15V
Gn 60VTS Ipps Load (0.05..1) 0.1xIn
Gn 60VTS Ipps Fault (0.05..20) 10xIn
Gn 60VTS Delay (0.03..14400) 10s
INRUSH DETECTOR
Gn 81HBL2 Element (Disabled..Enabled) Enabled
Gn 81HBL2 Bias (Phase..Sum) Cross
Gn 81HBL2 Setting (0.1..0.5) 0.2xI
CONTROL & LOGIC
MANUAL CB CONTROL
Gn Close CB Delay (0..900) 10s
Gn Blocked Close Delay (0..600) 5s
Gn Open CB Delay (0..900) 10s
Gn CB Controls Latched (Latch..Reset) Latch
CIRCUIT BREAKER
Gn Close CB Pulse (0..20) 2s
Gn Reclaim Timer (0..600) 2s
Gn CB Control Trip Time (Disabled..Enabled) Enabled
Gn Trip Time Alarm (0..2) 0.2s
Gn Trip Time Adjust (0..2) 0.015s
Gn CB Travel Alarm (0.01..2) 1s
Gn Open CB Pulse (0.1..2) 1s
Gn CB DBI Delay (0..2) 0s
QUICK LOGIC
Quick Logic (Disabled..Enabled) Disabled
INPUT CONFIG
INPUT MATRIX
Inhibit 81HBL2 (17 Bit Binary) -----------------
Inhibit 51-1 (17 Bit Binary) -----------------
Inhibit 51-2 (17 Bit Binary) -----------------
Inhibit 51-3 (17 Bit Binary) -----------------
Inhibit 51N-1 (17 Bit Binary) -----------------
Inhibit 51N-2 (17 Bit Binary) -----------------
Inhibit 32-1 (17 Bit Binary) -----------------
Inhibit 32-2 (17 Bit Binary) -----------------
Trig Trip Contacts (17 Bit Binary) -----------------
Inhibit 60VTS (17 Bit Binary) -----------------
Ext Trig 60VTS (17 Bit Binary) -----------------
Ext Reset 60VTS (17 Bit Binary) -----------------
Reset Trip Time (17 Bit Binary) -----------------
Reset Energy Meters (17 Bit Binary) -----------------
General Alarm 1 (17 Bit Binary) BI5
General Alarm 2 (17 Bit Binary) -----------------
General Alarm 3 (17 Bit Binary) -----------------
General Alarm 4 (17 Bit Binary) -----------------
General Alarm 5 (17 Bit Binary) -----------------
General Alarm 6 (17 Bit Binary) -----------------
CB Open (17 Bit Binary) BI2
CB Closed (17 Bit Binary) BI1
Reset Demand (17 Bit Binary) -----------------
Reset Start Count (17 Bit Binary) -----------------
Close CB (17 Bit Binary) -----------------
Block Close CB (17 Bit Binary) -----------------
Open CB (17 Bit Binary) -----------------
Line Check (17 Bit Binary) -----------------
E/F Out (17 Bit Binary) -----------------
E/F In (17 Bit Binary) -----------------
Trigger Wave Rec (17 Bit Binary) BI6
Trigger Fault Rec (17 Bit Binary) BI6
Select Group 1 (17 Bit Binary) -----------------
Select Group 2 (17 Bit Binary) -----------------
Select Group 3 (17 Bit Binary) -----------------
Select Group 4 (17 Bit Binary) -----------------
Out Of Service Mode (17 Bit Binary) -----------------
Local Mode (17 Bit Binary) -----------------
Remote Mode (17 Bit Binary) -----------------
Local Or Remote Mode (17 Bit Binary) -----------------
Clock Sync. (17 Bit Binary) -----------------
Reset LEDs & O/Ps (17 Bit Binary) -----------------
BINARY INPUT CONFIG
Inverted Inputs ( 9 Bit Binary) ---------
BI 1 Pickup Delay (0..14400) 0.02s
BI 1 Dropoff Delay (0..14400) 0s
BI 2 Pickup Delay (0..14400) 0.02s
BI 2 Dropoff Delay (0..14400) 0s
BI 3 Pickup Delay (0..14400) 0.02s
BI 3 Dropoff Delay (0..14400) 0s
BI 4 Pickup Delay (0..14400) 0.02s
BI 4 Dropoff Delay (0..14400) 0s
BI 5 Pickup Delay (0..14400) 0.02s
BI 5 Dropoff Delay (0..14400) 0s
BI 6 Pickup Delay (0..14400) 0.02s
BI 6 Dropoff Delay (0..14400) 0s
BI 7 Pickup Delay (0..14400) 0.02s
BI 7 Dropoff Delay (0..14400) 0s
BI 8 Pickup Delay (0..14400) 0.02s
BI 8 Dropoff Delay (0..14400) 0s
BI 9 Pickup Delay (0..14400) 0.02s
BI 9 Dropoff Delay (0..14400) 0s
Enabled In Local ( 9 Bit Binary) 1, 2, 3, 4, 5, 6, 7, 8, 9
Enabled In Remote ( 9 Bit Binary) 1, 2, 3, 4, 5, 6, 7, 8, 9
GENERAL ALARMS
General Alarm-1 (16 Character String) TRAFO·-·49·ALARM
General Alarm-2 (16 Character String) ALARM·2·········
General Alarm-3 (16 Character String) ALARM·3·········
Settings Editor 7SR10 - 7SR1004-3[JKL]xx0-2CA0.rsf2 Page 3 of 3