Dados Técnicos para Aplicações

1
Índice

1 Aplicações típicas e métodos de instalação 04


Capacidade de corrente 05
Fator de correção para agrupamento 06
2 Notas sobre fator de correção de agrupamentos 07
Outros fatores de correção 07

3 Seções mínimas 08
Queda de tensão 09
Queda de tensão (Volt / Ampere x km) 10
Parâmetros elétricos 11
Comprimento máximo para cabo multipolar - 220 V Monofásico 12
4
Comprimento máximo para cabo multipolar - 220 V Trifásico 13
Comprimento máximo para cabo multipolar - 380 V 14
Comprimento máximo para cabo multipolar - 440 V 15
Capacidade de curto circuito 16

5 Curva de curto circuito - Cabos com isolantes termofixos (90 °C) 17


Curva de curto circuito - Cabos com isolantes termoplásticos (70 °C) 18

6 Novo conceito para definição da seção econômica de cabos 19

7 Exemplo prático de utilização 20

8 Dimensionamento de cabos para solda 21

Certificações Condumax
Sistema da Garantia da Qualidade ISO 9002 / 94
Todos os produtos Condumax são fabricados rigorosamente de acordo com as
especificações NBR e controlados por um Sistema da Garantia da Qualidade conforme
NBR ISO 9002 / 94

Produtos com Certificados de Conformidade NBR


Maxvinil Flex 0,6 / 1,0 kV • Maxvinil Flex Multipolar • Maxvinil 0,6 / 1,0 kV
• Fio Sólido Antichama 750 V • Cabo Antichama Flexível 750 V • Cabo Flexível PP 750 V
• Cordão Flexível 300 V • Cabo Antichama 750 V

Certificados de Conformidade QS 9000


O Sistema da Garantia da Qualidade dos produtos da linha automotiva é certificado
conforme QS 9000 - 3a. Edição
Cabo de Bateria • Cabo de Ignição • Cabo Auto 300 V
DadosTécnicos

Aplicações típicas e métodos de instalação


NBR 6148 NBR 7288
Antichama Maxvinil 0,6 / 1,0 kV
Fio Cabo Cabo Flexível Cabo Cabo Flexível Multipolar
Residência Circuito de Distribuição OK
Circuito Terminal OK
Indústria / Circuito de Distribuição OK
Comércio Circuito Terminal OK OK

Circuito de distribuição: Ligação do medidor ou transformador ao quadro de distribuição.


Circuito Terminal: Ligação do quadro de distribuição à tomada de força ou direto ao equipamento.

Cabo Unipolar Métodos de Instalação, Classificação NBR 5410 Cabo Multipolar


Eletroduto direto em caixilho de porta ou janela
A1 Eletroduto embutido em parede isolante A1
Moldura
Forro falso ou piso elevado 5 De < v > 50 De B1
Canaleta ventilada no piso ou solo
Eletrocalha
Canaleta fechada no piso, solo ou parede B2
B1 Eletroduto aparente
Eletroduto embutido em alvenaria
Eletroduto em canaleta ventilada no piso ou solo
Eletroduto em espaço de construção v > 20 De
Eletroduto em canaleta fechada v > 20 De
Eletroduto não circular embutido em alvenaria 5 De < v > 50 De
Eletroduto em canaleta fechada 1,5 De < v > 20 De
B2 Eletroduto em espaço de construção 1,5 De < v > 20 De
Eletroduto não circular embutido em alvenaria 1,5 De < v > 5 De
Forro falso ou piso elevado 1,5 De < v > 5 De B2
Bandejas não perfuradas ou prateleiras
C Embutimento direto em alvenaria C
Fixação direta à parede ou teto
D Diretamente enterrado D
Eletroduto enterrado ou canaleta no solo
Leitos, suportes horizontais ou telas
F Bandeja perfurada (Horizontal ou Vertical) E
Afastado da parede ou suspenso por cabo de suporte
G Sobre isoladores

Não aplicável

Desenho esquemático da instalação


E F G
Tripolar 2 cabos 3 cabos 3 cabos 3 cabos espaçados 3 cabos espaçados
Bipolar e tetrapolar unipolares isolados contíguos horizontalmente ver ticalmente

4
Capacidade de corrente em função do tipo de instalação 1
• Base de dados NBR 5410

• Temperatura máxima: 70 °C • Valores em Amperes


• Isolante: Termoplástico • Temperatura ambiente: 30 °C
• Temperatura de solo: 20 °C
• Cabo Condumax indicado: Maxvinil ou Antichama
• Resistividade térmica do solo 2,5 km/W
Seção A1 A2 B1 B2 C D E F G
mm2 2 3 2 3 2 3 2 3 2 3 2 3 2 3
CC CC CC CC CC CC CC CC CC CC CC CC CC CC A B C D E
1,5 14,5 13,5 14 13 17,5 15,5 16,5 15 19,5 17,5 22 18 22 18,5 22 17 18 24 21
2,5 19,5 18 18,5 17,5 24 21 23 20 27 24 29 24 30 25 31 24 25 34 29 2
4,0 26 24 25 23 32 28 30 27 36 32 38 31 40 34 41 33 34 45 39
6,0 34 21 32 29 41 36 38 34 46 41 47 39 51 43 53 43 45 59 51
10,0 46 42 43 39 57 50 52 46 63 57 63 52 70 60 73 60 63 81 71
16,0 61 56 57 52 76 68 69 62 85 76 81 67 94 80 99 82 85 110 97
25,0 80 73 75 68 101 89 90 80 112 96 104 86 119 101 131 110 114 146 130
35,0 99 89 92 83 125 110 111 99 138 119 125 103 148 126 162 137 143 181 162
50,0 119 108 110 99 151 134 133 113 168 144 148 122 180 153 196 167 174 219 197
70,0 151 136 139 125 192 171 168 149 213 184 183 151 232 196 251 216 225 281 254
95,0 182 167 168 150 232 207 201 179 258 223 216 179 282 238 304 264 275 341 311
120 210 188 192 172 269 239 232 206 299 259 246 203 328 276 352 308 321 396 362
150 240 216 219 196 309 275 269 236 344 299 278 230 379 319 406 356 372 456 419
185 273 245 248 223 353 314 309 268 392 341 312 258 434 364 463 409 427 521 480
240 321 286 291 261 415 370 353 313 461 403 361 297 514 430 546 485 507 615 569

• Temperatura máxima: 90 °C • Valores em Amperes


• Isolante: Termofixo • Temperatura ambiente: 30 °C
• Temperatura de solo: 20 °C
• Cabo Condumax indicado: Maxlink, Maxlink G Flex
• Resistividade térmica do solo 2,5 km/W

Seção A1 A2 B1 B2 C D E F G
mm2 2 3 2 3 2 3 2 3 2 3 2 3 2 3
CC CC CC CC CC CC CC CC CC CC CC CC CC CC A B C D E
1,5 19 17 18,5 16,5 23 20 22 19,5 24 22 26 22 26 23 27 21 22 30 25
2,5 26 23 25 22 31 27 30 26 33 30 34 299 36 32 37 29 30 41 35
4,0 35 31 33 30 42 37 40 35 45 40 44 37 49 42 50 40 42 56 48
6,0 45 40 42 38 54 48 51 44 58 52 56 46 63 54 65 53 55 73 63
10,0 61 54 57 51 75 66 69 60 80 71 73 67 86 75 90 74 77 101 88
16,0 81 73 76 68 100 88 91 80 107 96 95 79 115 100 121 101 105 137 120
25,0 106 95 99 89 133 117 119 105 138 119 121 101 149 127 161 135 141 182 161
35,0 131 117 121 109 164 144 246 128 171 147 146 122 185 158 200 169 176 226 201
50,0 158 141 145 130 198 275 175 154 209 179 173 144 225 192 242 297 216 275 246
70,0 200 179 183 164 253 222 222 194 269 229 213 178 289 246 310 268 279 353 318
95,0 241 216 220 197 306 269 269 233 328 278 252 211 352 298 377 328 342 430 389
120 278 249 253 227 354 312 312 268 382 322 287 240 410 346 437 383 400 500 454
150 318 285 290 259 407 358 358 307 441 371 324 271 473 399 504 444 464 577 527
185 362 324 329 238 464 408 408 348 506 424 363 304 542 456 575 510 533 661 605
240 424 380 386 346 546 481 481 407 599 500 419 351 641 538 679 607 634 781 719

Base de dados

2CC = 02 condutores carregados


3CC = 03 condutores carregados
A = 02 condutores contíguos (horizontal ou vertical)
B = 03 condutores contíguos (sobrepostos) trifólio
C = 03 condutores contíguos (horizontal ou vertical)
D = 03 condutores espaçados horizontalmente
E = 03 condutores espaçados verticalmente

Obs.: para temperaturas diferentes, utilizar a tabela de correção na página 8

5
DadosTécnicos

Fator de correção para agrupamento


Número de circuitos
Método 01 02 03 04 05 06 07 08 09 12 16 20
Feixe de cabos ao ar livre sobre A
superfície, cabos condutos fechados F 1,00 0,80 0,70 0,65 0,60 0,57 0,54 0,52 0,50 0,45 0,41 0,38
Camada única sobre parede, piso
bandeja não ventilada ou prateleira C 1,00 0,85 0,79 0,75 0,73 0,72 0,72 0,70 0,70
Camada única no teto 0,95 0,81 0,72 0,68 0,66 0,64 0,63 0,62 0,60
Camada única em bandeja perfurada E 1,00 0,88 0,82 0,77 0,75 0,73 0,73 0,7 0,72
horizontal ou vertical F
Camada única em leito suporte 1,00 0,87 0,82 0,80 0,80 0,79 0,79 0,79 0,78
Cabos unipolares Distância zero 1,00 0,75 0,65 0,60 0,55 0,50
ou multipolares Distância 1 dia 1,00 0,80 0,70 0,60 0,55
diretamente Distância 0,125 m D 1,00 0,85 0,75 0,70 0,65 0,60
enterrados Distância 0,250 m 1,00 0,90 0,80 0,75 0,70
Distância 0,50 m 1,00 0,90 0,85 0,80
Ao ar livre cabos contíguos Vertical C 1,00 0,85 0,78 0,75 0,75 0,72 0,70
Multipolar Contíguos
em camadas horizontais em Horizontal E
bandeja, prateleira ou suporte F 1,00 0,80 0,73 0,70 0,70 0,68
Multipolar em Distância Zero 1,00 0,85 0,75 0,70 0,65 0,60
eletroduto Distância 0,25 m 1,00 0,90 0,85 0,80
diretamente Distância 0,50 m 1,00 0,95 0,90 0,85 0,85 0,80
enterrado Distância 1,00 m 1,00 0,95 0,95 0,90 0,90 0,80
Unipolar em Distância Zero D 1,00 0,80 0,70 0,65 0,60
eletroduto Distância 0,25 m 1,00 0,90 0,85 0,80
diretamente Distância 0,50 m 1,00 0,90 0,85 0,80
enterrado Distância 1,00 m 1,00 0,90
Bandeja horizontal 1 Bandeja 1,00 0,88 0,82 0,79 0,76 0,73
perfurada 2 Bandejas 1,00 0,87 0,80 0,77 0,73 0,68
Cabos contíguos 3 Bandejas 1,00 0,86 0,79 0,76 0,71 0,66
Bandeja horizontal 1 Bandeja 1,00 1,00 0,98 0,95 0,91 0,91 Multipolar Espaçados
perfurada 2 Bandejas 1,00 0,99 0,96 0,92 0,87 0,87
Cabo espaçado 3 Bandejas 1,00 0,98 0,95 0,91 0,85
Cabo Bandeja ver tical 1 Bandeja 1,00 0,88 0,82 0,78 0,73 0,72
Multipolar perfurada, contíguos 2 Bandejas 1,00 0,88 0,81 0,76 0,71 0,70
ao ar Bandeja ver tical 1 Bandeja 1,00 0,91 0,89 0,88 0,87 0,87
livre perfurada espaçado 2 Bandejas 1,00 0,91 0,88 0,87 0,85 0,85
Leitos e suporte 1 Bandeja 1,00 0,87 0,82 0,80 0,79 0,78
horizontais 2 Bandejas 1,00 0,86 0,80 0,78 0,76 0,73
Cabos contíguos 3 Bandejas 1,00 0,85 0,79 0,76 0,73 0,70
Leitos e suportes 1 Bandeja 1,00 1,00 1,00 1,00 1,00 1,00
horizontais 2 Bandejas 1,00 0,99 0,98 0,97 0,96 0,96
Cabo espaçado 3 Bandejas 1,00 0,98 0,97 0,96 0,93 0,93
Bandeja 1 Bandeja 0,98 0,91 0,87 Unipolar Contíguos
horizontal 2 Bandejas 0,96 0,87 0,81
perfurada, contíguos 3 Bandejas 0,95 0,85 0,78
Bandeja ver tical 1 Bandeja 0,96 0,86 0,86
Cabo perfurada, contíguos 2 Bandejas 0,96 0,84 0,84
Unipolar Leito e 1 Bandeja 1,00 0,97 0,96
ao supote 2 Bandejas 0,98 0,93 0,89 Unipolar Espaçados
ar horizontais, contíguos 3 Bandejas 0,97 0,90 0,86
livre Bandeja 1 Bandeja 1,00 0,98 0,96
horizontal 2 Bandejas 0,97 0,93 0,89
Circuito perfurada, espaçados 3 Bandejas 0,96 0,92 0,86
3F Bandeja ver tical 1 Bandeja 1,00 0,91 0,89
perfurada, espaçados 2 Bandejas 1,00 0,90 0,86
Leitos, suportes 2 Bandejas 0,97 0,95 0,93
horizontais, espaçados 3 Bandejas 0,96 0,94 0,90

6
Notas sobre fator de correção para agrupamento
1) Os fatores são aplicados à grupos de cabos uniformemente carregados
2) Quando a distância horizontal entre cabos adjacentes for o dobro do seu diâmetro externo, não é necessário aplicar nenhum
fator de correção
3) Os valores indicados são médios para a faixa de seções nominais, com precisão de 5%
4) Os fatores são aplicáveis à cabos em uma única camada (exceto quando mencionado disposição em camadas)
5) Para os cabos dispostos em camadas, o fator total é obtido multiplicando os fatores referentes à disposição horizontal pelos
fatores referentes à disposição vertical
6) Distância mínima entre bandejas ou leitos na vertical 300 mm 2
7) Distância mínima entre bandejas ou leitos na horizontal 225 mm
8) Se um agrupamento é constituído de cabos bipolares e tripolares, o número total de cabos é considerado igual ao número de
circuitos e aplica-se à tabela de 03 condutores carregados

Fatores de correção para temperaturas


Isolação
Temperatura PVC EPR / XLPE PVC EPR / XLPE
C Ambiente Solo
10 1,22 1,15 1,10 1,07
15 1,17 1,12 1,05 1,04
20 1,12 1,08 1,00 1,00
25 1,06 1,04 0,95 0,96
30 1,00 1,00 0,89 0,93
35 0,94 0,96 0,84 0,89
40 0,87 0,91 0,77 0,85
45 0,79 0,87 0,71 0,80
50 0,71 0,82 0,63 0,76
55 0,61 0,76 0,55 0,71
60 0,50 0,71 0,45 0,65
65 0,65 0,60
70 0,58 0,53
75 0,50 0,46
80 0,41 0,38

Fator de conversão: Resistividade do solo


Fator de conversão para cabos contidos em eletrodutos enterrados no solo com resistividade térmica diferente de
2,5 km/W

Resistividade térmica (km/W) 1 1,5 2,0 3,0


Fator de conversão 1,18 1,10 1,05 0,96

7
DadosTécnicos

Seções mínimas de condutores isolados

Tipo de Instalação Utilização do circuito Seção mínima (mm²)

Instalações fixas Circuitos de Iluminação 1,5

Circuitos de força (tomadas) 2,5

Circuitos de sinalização e / ou controle 0,5

Instalações flexíveis Equipamentos específicos Conforme instrução da fábrica

Equipamentos em geral 0,75

Seções mínimas de condutores neutro e de proteção


Seção do condutor fase Condutor de proteção Condutor neutro

1,5 1,5 1,5

2,5 2,5 2,5

4,0 4,0 4,0

6,0 6,0 6,0

10,0 10,0 10,0

16,0 16,0 16,0

25,0 16,0 25,0

35,0 16,0 25,0

50,0 25,0 25,0

70,0 35,0 35,0

95,0 50,0 50,0

20,0 70,0 70,0

150,0 95,0 70,0

185,0 95,0 95,0

240,0 120,0 120,0

8
Queda de tensão
Limite de queda de tensão
Instalações Iluminação Outros usos
A Alimentados diretamente por um ramal de baixa tensão,
a partir de uma rede de distribuição pública em baixa tensão 4% 4%
B Alimentados diretamente por subestação de transformação ou
transformador, a partir de uma instalação de média / alta tensão 7% 7%
C Instalações que possuam fonte própria geradora de energia 7% 7%

Nas páginas seguintes você vai encontrar tabelas que fornecem:

1) Volt / Ampere x km
(pág. 10)

No caso de utilização, a queda de tensão deve ser calculada conforme abaixo:


Queda de Tensão (V) = Corrente de Projeto (A) x Comprimento do cabo (km) x Tabela V/A km

2) Tabelas simplificadas de comprimentos máximos para cabos multipolares para determinação direta do lance máximo
permissível, nas condições estabelecidas.
(págs. 12, 13, 14 e 15)
3

Exemplo comparativo

Seleção de cabos, considerando os seguintes parâmetros:


• Corrente de Projeto: 130 A
• Método de Instalação: A1 4
• 3 condutores unipolares carregados
• Eletroduto não magnético
• Fator de Potência: 0,95

Classe térmica do cabo 70 oC 90 oC


Produtos Condumax Cabo Antichama Maxlink
Maxvinil Maxlink G Flex
Cabo selecionado pelo critério da máxima capacidade corrente 70 mm2 50 mm2
Máxima queda de tensão (4% da tensão da rede) 15,2 V
Tabela V / A x km 0,64 0,86
Comprimento máximo do cabo (fórmula acima) 175 metros 123 metros

9
DadosTécnicos

Queda de tensão (Volt / Ampere x km)

Fator de potência = 0,80


Condutor Unipolar Condutor Multipolar
Conduto Conduto Ar livre
magnético não-magnético
Seção Circuitos Circuito Circuito Circuito monofásico Circuito trifásico Circuito Circuito
Nominal monofásico e trifásico monofásico Distância entre condutores monofásico trifásico
mm2 trifásico 10 cm 20 cm 10 cm 20 cm Contíguos
1,5 20,2 23,3 20,2 23,6 23,7 20,5 20,5 20,2 23,3 20,2
2,5 12,4 14,3 12,4 14,6 14,7 12,7 12,7 12,4 14,3 12,4
4,0 7,8 8,96 7,79 9,25 9,35 8,02 8,08 7,79 8,96 7,76
6,0 5,2 6,03 5,25 6,30 6,41 5,47 5,52 5,25 6,03 5,22
10,0 3,1 3,63 3,17 3,88 3,95 3,38 3,44 3,17 3,63 3,14
16,0 2,0 2,32 2,03 2,56 2,64 2,24 2,29 2,03 2,32 2,01
25,0 1,3 1,51 1,33 1,73 1,80 1,52 1,57 1,33 1,51 1,31
35,0 1,0 1,12 0,98 1,33 1,39 1,17 1,22 0,98 1,12 0,97
50,0 0,75 0,85 0,76 1,05 1,12 0,93 0,99 0,76 0,85 0,74
70,0 0,55 0,62 0,55 0,81 0,87 0,72 0,77 0,55 0,62 0,54
95,0 0,43 0,48 0,43 0,65 0,71 0,58 0,64 0,43 0,48 0,42
120 0,35 0,40 0,36 0,57 0,63 0,51 0,56 0,36 0,41 0,35
150 0,31 0,35 0,31 0,50 0,56 0,45 0,51 0,31 0,35 0,30
185 0,26 0,30 0,27 0,44 0,51 0,40 0,46 0,27 0,31 0,26
240 0,23 0,26 0,23 0,39 0,45 0,35 0,41 0,23 0,26 0,22

Fator de potência = 0,95


Condutor Unipolar Condutor Multipolar
Conduto Conduto Ar livre
magnético não-magnético
Seção Circuitos Circuito Circuito Circuito monofásico Circuito trifásico Circuito Circuito
Nominal monofásico e trifásico monofásico Distância entre condutores monofásico trifásico
mm2 trifásico 10 cm 20 cm 10 cm 20 cm Contíguos
1,5 27,4 27,6 23,9 27,8 27,8 24,0 24,1 23,9 27,6 23,9
2,5 16,8 16,9 14,7 17,1 17,1 14,8 14,8 14,7 16,9 14,7
4,0 10,5 10,6 9,15 10,7 10,7 9,27 9,30 9,15 10,6 9,14
6,0 7,00 7,07 6,14 7,18 7,18 6,25 6,28 6,14 7,07 6,12
10,0 4,20 1,23 3,67 4,35 4,36 3,79 3,81 3,67 4,23 3,66
16,0 2,70 2,68 2,33 2,79 2,82 2,44 2,47 2,33 2,68 2,32
25,0 1,72 1,71 1,49 1,83 1,86 1,60 1,62 1,49 1,71 1,48
35,0 1,25 1,25 1,09 1,36 1,39 1,19 1,22 1,09 1,25 1,08
50,0 0,95 0,94 0,82 1,04 1,08 0,91 0,94 0,82 0,94 0,81
70,0 0,67 0,67 0,59 0,76 0,80 0,67 0,70 0,59 0,67 0,58
95,0 0,51 0,50 0,44 0,59 0,62 0,52 0,55 0,44 0,50 0,43
120 0,42 0,41 0,36 0,49 0,52 0,43 0,46 0,36 0,41 0,35
150 0,35 0,34 0,30 0,42 0,45 0,37 0,40 0,30 0,34 0,30
185 0,30 0,29 0,25 0,36 0,39 0,32 0,35 0,25 0,29 0,25
240 0,25 0,24 0,21 0,30 0,33 0,27 0,30 0,21 0,24 0,20

10
Parâmetros elétricos
Resistências elétricas e reatâncias indutivas (Xl) em Ohms / km

Resistência Cabos Antichama e Maxvinil (70 0C) e Cabos Maxlink e Maxlink G flex (90 0C)
Seção elétrica (70 °C) Cabos em Cabos unipolares ao ar livre Cabos
mm² Ohms / km dutos Circuitos FN e FF Circuitos trifásicos multipolares
CC CA 01 02 03 04 05 06 07 08 09 10 11 12 13
1,5 12,1 14,48 0,16 0,16 0,21 0,39 0,44 0,16 0,17 0,23 0,40 0,46 0,16 0,12 0,14
2,5 7,41 8,87 0,15 0,15 0,20 0,37 0,42 0,15 0,16 0,22 0,38 0,44 0,15 0,12 0,13
4,0 4,61 5,52 0,14 0,14 0,20 0,35 0,40 0,14 0,16 0,22 0,37 0,42 0,14 0,12 0,13
6,0 3,08 3,69 0,13 0,14 0,19 0,33 0,39 0,14 0,15 0,20 0,35 0,40 0,14 0,11 0,12
10,0 1,83 2,19 0,13 0,13 0,18 0,32 0,37 0,13 0,14 0,20 0,34 0,39 0,13 0,10 0,12
16,0 1,15 1,38 0,12 0,12 0,17 0,30 0,35 0,12 0,14 0,19 0,32 0,37 0,12 0,10 0,11
25,0 0,73 0,87 0,12 0,12 0,17 0,28 0,34 0,12 0,13 0,18 0,30 0,35 0,11 0,10 0,11
35,0 0,52 0,63 0,11 0,11 0,17 0,27 0,32 0,11 0,13 0,18 0,29 0,34 0,11
50,0 0,39 0,46 0,11 0,11 0,16 0,26 0,31 0,11 0,13 0,18 0,28 0,33 0,11
70,0 0,27 0,32 0,10 0,10 0,16 0,25 0,30 0,10 0,12 0,17 0,27 0,32 0,10
95,0 0,19 0,23 0,10 0,10 0,16 0,24 0,29 0,10 0,12 0,17 0,25 0,30 0,10
120,0 0,15 0,19 0,10 0,10 0,15 0,23 0,28 0,10 0,12 0,17 0,24 0,29 0,10
150,0 0,12 0,15 0,10 0,10 0,15 0,22 0,27 0,10 0,12 0,17 0,23 0,29 0,10
185 0,099 0,12 0,099 0,10 0,15 0,21 0,26 0,10 0,12 0,17 0,23 0,28 0,10
240,0 0,075 0,09 0,098 0,10 0,15 0,20 0,25 0,10 0,12 0,17 0,22 0,27 0,10

Observação:
Esta não é uma tabela para uso direto. Ela apresenta os parâmetros utilizados na determinação de V / A x km
Z = R Cos f + X Sen f

Esquemático das instalações 4


1 Agrupados, sem distanciamento entre cabos
2 S=d 7 S=d
3 S = 2d 8 S = 2d
d d
4 S = 10 cm s 9 S = 10 cm s s
5 S = 20 cm 10 S = 20 cm

6 Trifólio 11 Trifólio

12 Bi e Tripolar 13 Tetrapolar
FN / FF / 3F 3F + N

11
DadosTécnicos

Lances máximos em função da máxima queda de tensão


Tabela simplificada

• Tensão 220 V Monofásico


• Cabo Multipolar 70 °C
• FP 0,80

Metros
CV A 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
1 10 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0
1,5 13 1,5 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 3,08
2 15 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0
2,5 17,5 1,5 2,5 2,5 4,0 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0
3 20 2,5 2,5 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
3,5 22 2,5 2,5 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0
4 24 2,5 4,0 4,0 6,00 6,00 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0
4,5 26 2,5 4,0 4,0 6,00 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0
5 28 2,5 4,0 4,0 6,00 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0
5,5 30 2,5 4,0 6,00 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0
6 32 2,5 4,0 6,00 6,00 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0
6,5 34 2,5 4,0 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0
7 36 4,0 4,0 6,00 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0
8 40 4,0 6,00 6,00 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0
8 44 4,0 6,00 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0
10 49 4,0 6,00 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0
11 53 6,00 6,00 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0
12 59 6,00 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0 70,0
13 62 6,00 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 1,29 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0
14 66 6,00 10,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 0,74 70,0 70,0 70,0 70,0
15 70 6,00 10,0 10,0 16,0 16,0 25,0 25,0 25,0 1,3 35,0 35,0 35,0 50,0 50,0 50,0 50,0 0,70 70,0 70,0 70,0 70,0

Observações:

1) Até 35 mm², utilizar cabo multicondutor. Acima de 35 mm² recomendamos e adotamos cabos singelos
2) Considerado comprimento do quadro de comando à bomba (queda tensão máxima 4%),
respeitar limite de queda de tensão de 3% do transformador ao quadro de comando

12
Lances máximos em função da máxima queda de tensão
Tabela simplificada

• Tensão 220 V Trifásico


• Cabo Multipolar 70 °C
• FP 0,80
Metros
CV A 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
1 4,2 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0
1,5 5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0
2 7,3 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 6,00 6,00
2,5 8,6 1,5 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0
3 10,5 1,5 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0
3,5 11,7 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
4 12,4 1,5 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
4,5 13,7 1,5 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0
5 13,9 1,5 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0
5,5 15,2 1,5 2,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0
6 16,7 1,5 2,5 2,5 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0
6,5 18 1,5 2,5 4,0 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
7 19,4 1,5 2,5 4,0 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
8 23 2,5 2,5 4,0 6,00 6,00 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0
9 24,5 2,5 4,0 4,0 6,00 6,00 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0
10 28,1 2,5 4,0 6,0 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0
11 30,5 2,5 4,0 6,0 6,00 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0
12 33,9 2,5 4,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0
13 36,1 4,0 4,0 6,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0
14 38,5 4,0 6,00 6,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0
15 40,7 4,0 6,00 6,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0
16 43,1 4,0 6,00 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0
17 45,5 4,0 6,00 10,0 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0
18 48 4,0 6,00 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0
19
20
50,5
53,8
4,0
6,0
6,00
6,00
10,0
10,0
10,0
10,0
16,0
16,0
16,0
16,0
16,0
16,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
1,34
35,0
35,0
35,0
35,0
35,0
35,0
35,0
35,0
50,0
35,0
50,0
50,0
50,0
50,0
50,0
50,0
50,0
50,0
50,0
4
22,5 60,2 6,00 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0
25 66,6 6,00 10,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0
27,5 72,6 6,00 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 70,0
30 79 6,00 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0
32,5 89 10,0 10,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0
35 93 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0
37,5 99 10,0 16,0 16,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0 120
40 112 10,0 16,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 120 120 120 120
45 126 10,0 16,0 25,0 1,40 35,0 35,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 120 120 120 120 185 185
50 140 16,0 16,0 25,0 35,0 35,0 50,0 50,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 120 120 120 185 185 185 185
55 154 16,0 25,0 25,0 35,0 50,0 50,0 70,0 70,0 70,0 95,0 95,0 95,0 120 120 120 185 185 185 185 185 185
60 168 16,0 25,0 25,0 35,0 50,0 50,0 70,0 70,0 95,0 95,0 95,0 120 120 120 185 185 185 185 185 240 240
65 182 16,0 25,0 35,0 35,0 50,0 70,0 70,0 70,0 95,0 95,0 120 120 0,35 185 185 185 185 240 240 240 240
70 196 16,0 25,0 35,0 50,0 50,0 70,0 70,0 95,0 95,0 120 120 120 185 185 185 185 240 240 240
75 210 16,0 25,0 35,0 50,0 70,0 70,0 95,0 95,0 95,0 120 120 185 185 185 185 240 240 240
80 220 25,0 25,0 35,0 50,0 70,0 95,0 95,0 95,0 120 120 185 185 185 185 240 240 240
85 238 25,0 35,0 50,0 50,0 70,0 95,0 95,0 95,0 120 185 185 185 185 240 240 240
90 240 25,0 35,0 50,0 70,0 70,0 95,0 95,0 120 120 185 185 185 185 240 240 240
95 250 25,0 35,0 50,0 70,0 70,0 95,0 95,0 120 120 185 185 185 240 240 240
100 260 25,0 35,0 50,0 70,0 70,0 95,0 95,0 120 185 185 185 185 240 240
110 280 25,0 35,0 50,0 70,0 95,0 95,0 120 120 185 185 185 240 240
120 300 35,0 50,0 70,0 70,0 95,0 95,0 120 185 185 185 240 240
130 320 35,0 50,0 70,0 70,0 95,0 120 185 185 185 240 240
140 340 35,0 50,0 70,0 95,0 95,0 120 185 185 185 240 240
150 360 35,0 50,0 70,0 95,0 120 120 185 185 240 240

Observações:

1) Até 35 mm², utilizar cabos multicondutores. Acima de 35 mm² recomendamos e adotamos cabos singelos
2) Considerado comprimento do quadro de comando à bomba (queda tensão máxima 4%),
respeitar limite adicional de queda de tensão de 3% do transformador ao quadro de comando

13
DadosTécnicos

Lances máximos em função da máxima queda de tensão


Tabela simplificada

• Tensão 380 V Trifásico


• Cabo Multipolar 70 °C
• FP 0,80
Metros
CV A 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
1 2,4 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5
1,5 2,9 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5
2 4,2 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5
2,5 5,0 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0
3 6,1 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0
3,5 6,8 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0
4 7,2 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0
4,5 7,9 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0
5 8,0 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0
5,5 8,8 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 8,2 7,9
6 9,7 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0
6,5 10,4 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0
7 11,2 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0
8 13,3 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0
9 14,2 1,5 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0
10 16,3 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0
11 17,7 1,5 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0
12 19,6 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 3,5
13 20,9 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0
14 22,3 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0
15 23,6 1,5 1,5 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0
16 25,0 1,5 1,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 3,2 16,0 16,0 16,0
17 26,3 1,5 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0
18 27,8 1,5 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 3,2 16,0 16,0 16,0 16,0 16,0
19 29,2 1,5 2,5 2,5 4,0 4,0 6,0 6,0 6,0 5,2 10,0 10,0 10,0 10,0 10,0 10,0 3,1 16,0 16,0 16,0 16,0 16,0
20 31,1 1,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0
23 34,9 1,5 2,5 4,0 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
25 38,6 2,5 2,5 4,0 4,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0
28 42,0 2,5 4,0 4,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0
30 45,7 2,5 4,0 4,0 6,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0
33 51,5 2,5 4,0 6,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0
35 53,8 2,5 4,0 6,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0
38 57,3 2,5 4,0 6,0 6,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0
40 64,8 4,0 4,0 6,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0
45 72,9 4,0 6,0 6,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0
50 81,1 4,0 6,0 10,0 10,0 3,13 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 36,0 50,0 50,0 50,0
55 89,2 4,0 6,0 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0
60 97,3 6,0 6,0 10,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0
65 105 6,0 10,0 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0
70 113 6,0 10,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0
75 122 6,0 10,0 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0
80 127 6,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0
85 138 6,0 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0
90 139 6,0 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0
95 145 10,0 10,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0
100 151 10,0 10,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0
110 162 10,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0
120 174 10,0 16,0 16,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 95,0 120
130 185 10,0 16,0 16,0 25,0 25,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 120 120 120
140 197 10,0 16,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 120 120 120 120
150 208 10,0 16,0 25,0 25,0 35,0 35,0 50,0 50,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,0 120 120 120 120 150

Observações:

1) Até 35 mm², utilizar cabos multicondutores. Acima de 35 mm² recomendamos e adotamos cabos singelos
2) Considerado comprimento do quadro de comando à bomba (queda tensão máxima 4%),
respeitar limite adicional de queda de tensão de 3% do transformador ao quadro de comando

14
Lances máximos em função da máxima queda de tensão
Tabela simplificada

• Tensão 440 V Trifásico


• Cabo Multipolar 70 °C
• FP 0,80
Metros
CV A 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
1 2,1 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5
1,5 2,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5
2 3,7 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5
2,5 4,3 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5
3 5,3 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5
3,5 5,9 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5
4 6,2 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5
4,5 6,9 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0
5 7,0 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0
5,5 7,6 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0
6 8,35 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0
6,5 9 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0
7 9,7 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0
8 11,5 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0
9 12,3 1,5 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0
10 14,1 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0
11 15,3 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0
12 17 1,5 1,5 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0
13 18,1 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0
14 19,3 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0
15 20,4 1,5 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0
16 21,6 1,5 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
17 22,8 1,5 1,5 2,5 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
18 24 1,5 1,5 2,5 2,5 4,0 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0
19
20
25,3
26,9
1,5
1,5
1,5
1,5
2,5
2,5
2,5
2,5
4,0
4,0
4,0
4,0
4,0
4,0
6,0
6,0
6,0
6,0
6,0
6,0
6,0
6,0
6,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
10,0
16,0
4
23 30,1 1,5 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0
25 33,3 1,5 2,5 2,5 4,0 4,0 6,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0
28 36,3 2,5 2,5 4,0 4,0 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
30 39,5 2,5 2,5 4,0 8,9 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 10,0 3,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
33 44,5 2,5 2,5 4,0 7,9 6,0 6,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0
35 46,5 2,5 2,5 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0
38 49,5 2,5 4,0 4,0 6,0 6,0 10,0 10,0 10,0 10,0 10,0 3,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0
40 56 2,5 4,0 6,0 6,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0
45 63 2,5 4,0 6,0 6,0 10,0 10,0 10,0 3,1 16,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0
50 70 2,5 4,0 6,0 10,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0
55 77 4,0 6,0 6,0 10,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 26,0 26,0 26,0 26,0 35,0 35,0 35,0 35,0 35,0 35,0
60 84 4,0 6,0 6,0 10,0 10,0 16,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 35,0
65 91 4,0 6,0 4,84 10,0 10,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0
70 98 4,0 6,0 4,49 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0
75 105 4,0 6,0 4,19 10,0 16,0 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0
80 110 4,0 6,0 4,00 10,0 16,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0
85 115 4,0 5,10 3,83 16,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0
90 120 6,0 4,89 3,67 16,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0
95 125 6,0 4,69 3,52 16,0 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0
100 130 6,0 4,51 3,38 16,0 16,0 25,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0
110 140 6,0 4,19 3,14 16,0 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 50,0 0,70 70,0 70,0 70,0 70,0
120 150 6,0 3,91 2,93 16,0 25,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 70,0 0,53
130 160 6,0 3,67 2,75 16,0 25,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 70,0 95,0 95,00
140 170 10,0 3,45 2,59 16,0 25,0 25,0 35,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0 95,00
150 180 10,0 3,26 16,0 16,0 25,0 25,0 35,0 35,0 35,0 50,0 50,0 50,0 70,0 70,0 70,0 70,0 70,0 95,0 95,0 95,0 95,00

Observações:

1) Até 35 mm², utilizar cabos multicondutores. Acima de 35 mm² recomendamos e consideramos o uso de fases singelas
2) Considerado comprimento do quadro de comando à bomba (queda tensão máxima 4%),
respeitar limite adicional de queda de tensão de 3% do transformador ao quadro de comando

15
DadosTécnicos

Capacidade de curto-circuito
As curvas seguintes fornecem para cada seção condutora a corrente máxima de curto-circuito para tempos entre
0,1 seg (1 ciclo) à 1,4 segundos (100 ciclos)

A corrente de curto circuito foi determinada conforme instruções da IEC 949

I² t = I² (x + X²+ 4 z S / 2 z S)

z = I² / a - Y / S

a = K² S² ln (F f + b / F i + b)

Onde:

I = corrente admissível no condutor em Amperes


t = tempo em segundos
x = tabela
S = seção nominal do condutor em mm²
Y = tabela
K = tabela
b = tabela
Ff = temperatura final do condutor OC
Fi = temperatura inicial do condutor OC

Condutor K b Isolação X Y
Cobre 226 234,5 PVC < 3 Kv 0,29 0,06
Alumínio 148 228 PVC > 3 Kv 0,27 0,05
XLPE 0,41 0,12
EPR < 3 Kv 0,38 0,10
EPR > 3 Kv 0,32 0,07

16
Correntes máximas de curto-circuito (Conexão soldada)
Cabos com isolantes termofixos (90 °C) Maxlink / Maxlink G Flex

10 x 200

100
90
80
70
60
50

40

30

20
o
cl
ci os
1 cl
ci
2
os
cl
ci
4 os
10 cl
ci
9 8 os
cl
ci
Corrente de Curto Circuito (Kiloamperes)

8
16 os
cl
7
ci
30 os
6 cl
ci os
60 cl
5 ci
0
10
4

Máxima temperatura em regime contínuo 90 °C


Máxima temperatura do curto circuito 160 °C

1
0.9
0.8
0.7
0.6

0.5

0.4
5
0.3

0.2
4

16
10

25

35

240
150

500

630

800

1000
2,5

185

300
50

95

400
1,5

70

120

0.1
1

5
3
2

9
7
8

60

100

250
30

80
40

900
600
200

700
20

Seção nominal do condutor (mm2)

17
DadosTécnicos

Correntes máximas de curto-circuito


Cabos com isolante termoplástico (70 °C) Maxvinil / Antichama

10 x 200

100
90
80
70
60
50

40

30

20
o
cl
ci
1 os
cl
ci
2 os
cl
ci
4 os
cl
10 ci
8 os
9 cl
ci os
Corrente de Curto Circuito (Kiloamperes)

8
16 cl
7 ci os
3 0 cl
6 ci os
6 0 cl
5 ci
0
10
4

Máxima temperatura em regime contínuo 70 °C


Máxima temperatura do curto circuito 160 °C

1
0.9
0.8
0.7
0.6

0.5

0.4

0.3

0.2
4

16
10

25

35

240
150

500

630

800

1000
2,5

185

300
50

95

400
1,5

70

120

0.1
1

5
3
2

9
7
8

60

100

250
30

80
40

900
600
200

700
20

Seção nominal do condutor (mm2)

18
Novo conceito de dimensionamento de cabos com seção econômica

A NBR 5410 dimensiona os condutores pelo critério da menor seção permissível (seção de segurança e com menor
custo de aquisição) e não pelo menor custo operacional em um determinado período.

O IEC - International Electrical Commite - sugere a adoção de uma nova forma de dimensionamento para definir não
só a menor seção permissível (seção de segurança), mas também a seção com o menor custo operacional (seção
econômica).

O procedimento é bastante simples e consiste em dimensionar a seção mínima permissível (segurança) e, a partir
desta seção mínima, buscar a seção de cabo imediatamente superior e efetuar cálculos de pay back
sucessivamente.

Demonstramos abaixo o método simplificado da IEC 60287-3

Se=(Ib/ Ch x Cn) e/G


onde:

Ch = 2,66 / H Se = seção econômica em mm²


n Ib = Corrente do circuito em Amperes
Cn = 0,69 / 1- 0,937 e = Custo da energia elétrica ativa R$ / KWh
G = Custo do cabo em R$ / mm² x km
G = P2 – P1 / S2 – S1 H = Número de horas/ano de funcionamento do circuito
n = Número de anos considerados no cálculo
P2 e P1 = Preço dos cabos
S2 e S1 = Seções dos cabos

Exemplo comparativo entre método da Seção Econômica com Seção Mínima

Cabos com isolação termofixa (90 OC)


Comprimento de 100 metros

Seção Econômica (IEC 60287-3) Seção Mínima (NBR 5410)


Relação de custos R$ / mm² x km 117 Corrente de projeto em Amperes 320
Horas de funcionamento anual 4.000 Instalação em trifólio 95 mm²
Corrente de projeto em Amperes 320 Queda de tensão 3,7 %
Número de anos para amortização 10 Fator de potência 0,95
Fator C h 0,0421 Tabela V / A km 0,44
Fator C n 0,998 Seção mínima obtida 95 mm² 5
Seção econômica calculada 134 150 mm²

19
DadosTécnicos

Exemplo prático

50 m
E - Cabine Primária Método G
Quadro de Distribuição Geral
QDG
70 m 50 m B - Escritório
A - Iluminação Externa Quadro de Distribuição
Método C Método B1

30 m 70 m
C - Área Fabril D - Bombeamento
Método D Método G

• Sistema: Trifásico 220 V


• Fator de potência: 0,92
• Temperatura ambiente: 35 OC Corrente corrigida
Subterrânea Aérea
Distância Método Potência Corrente de Projeto 20 c 30 c
A Iluminacão Externa 70 m C 6 kW I a = 6.000 / 3 x 220 x 0,92 17,1 A 18,1 A
B Escritório 50 m B1 12 kW I b = 12.000 / 3 x 220 x 0,92 34,2 A 36,4 A
C Área Fabril 30 m D 100 kW I c = 100.000 / 3 x 220 x 0,92 285,3 A 297,1 A
D Bombeamento 70 m G 20 CV 1200 rpm, 60 Hz, 6 pólos 56,0 A 59,6 A
Total da corrente conforme a instalação 392,5 A

Dimensionamento dos cabos condutores para o sistema geral

1) Máxima capacidade de corrente

Seção Produto
A Tabela folha 5, método C, 3 CC 2,5 mm2 Fio / cabo antichama ou Maxvinil (70 oC)
B Tabela folha 5, método B1, 3 CC 6,0 mm2 Fio / cabo antichama ou Maxvinil (70 oC)
C Tabela folha 5, método D, 3 CC 185,0 mm 2
Cabo Maxlink ou Maxlink G flex (90 oC)
D Tabela folha 5, método G 10,0 mm 2
Fio / cabo antichama ou Maxvinil (70 oC)

2) Máxima queda de tensão (limite máximo de 4%)

Determinação de V/A x KM Seção Condutor unipolar


A (220 x 0,04) / (0,07 x 17,1) = 7,33 6,0 mm2 Conduto não magnético
B (220 x 0,04) / (0,05 x 34,2) = 5,15 10,0 mm2 Conduto não magnético
C (220 x 0,04) / (0,03 x 297,1) = 0,987 50,0 mm2
D (220 x 0,04) / (0,07 x 56,0) = 2,245 16,0 mm2 Ar livre contíguos

Condutores a serem utilizados:


Circuíto A - Fio / Cabo Antichama ou Maxvinil 6,0 mm2
Circuíto B - Fio / Cabo Antichama ou Maxvinil 10,0 mm2
Circuíto C - Cabo Maxlink / Maxlink G Flex 185,0 mm2 ou Cabo Antichama / Maxvinil 240 mm2
Circuíto D - Cabo Antichama ou Maxvinil 16,0 mm2

Dimensionamento do cabo para a cabine primária

1) Máxima capacidade de corrente 2) Máxima queda de tensão


Determinação de
Distância Método Corrente de Projeto Tabela (Folha 5) V/A x km = (220 x 0,03) / (0,05 x 406) = 0,325 V/A x km
e Cabine primária 50 m C 399,4 A Cabo Maxlink 185 mm2
(0,325 na tabela V/A x km define cabo 150 mm2)

Cabo a ser utilizado: Maxlink G Flex 185,0 mm2

20
Dimensionamento de cabos para solda
(Termoplástico 70 °C)

Definições:

Fator de Carga:
Porcentagem do Ciclo de Trabalho no qual o
cabo conduz sua corrente nominal

Ciclo de Trabalho:
por definição 5 minutos

Corrente Nominal

Seções Fator de Carga


nominais
mm2 100% 75% 50% 25% 10%
10,0 71 74 81 102 148
16,0 95 101 114 148 220
25,0 131 142 162 213 322
35,0 162 178 206 275 420
50,0 196 218 256 347 535
70,0 251 280 332 453 700
95,0 304 342 407 559 869
120,0 352 397 475 656 1.021

21

8
Qualidade, confiabilidade e tecnologia
para a produção de cabos elétricos

Cabos de controle Blindados com malha Blindados com fita


0,6 / 1 kV de fios de cobre de cobre helicoidal

Maxvinil Flex Maxlink Maxvinil Flex Multipolar


0,6 / 1 kV 0,6 / 1 kV 0,6 / 1 kV A Condumax ocupa hoje uma
posição de destaque no ranking
dos fabricantes de fios e cabos
elétricos. É reconhecida em todo o
Brasil pela sua competência no setor,
pela qualidade de seus produtos e pelo

Julho/ 2 0 0 2 - Informações t é c n i c as s u j e i t a s a a l t e r a ç ões s e m p r é v i o a v i s o .


profundo respeito às normas técnicas e
aos seus clientes.

Maxlink G Flex Multipolar Maxlink G Flex Cabos de controle blindados com fita
0,6 / 1 kV 0,6 / 1 kV de Poliéster aluminizada

Linha de Produtos: Cabo Maxlink Antifur to 0,6/1,0 kV, Cabo Maxvinil 0,6/1,0 kV, Cabo Maxvinil Flex 0,6/1,0 kV, Os cabos fabricados de
Cabo Maxlink G-Flex 0,6/1,0 kV, Fio Sólido Antichama 750 V, Cabo Antichama 750 V, Cabo Antichama Flex 750 V, acordo com as normas
Cabo PP 750 V, Cordão Torcido 300 V, Cordão paralelo 300 V, Cabo de controle 0,6/1,0 kV, Cabo de solda. NBR 6148, NBR 13249 e
NBR 7288 são cer tificados