Aneel Analise DSV
Aneel Analise DSV
Dispositivo de Seccionamento
Visvel (DSV) na microgerao
Elaborado por:
Peter Krenz (Instituto Ideal)
com apoio de:
Prof. Dr. Ingo Stadler (Fachhochschule Kln)
Prof. Eduardo Lorenzo Pigueiras (Universidad Politcnica de Madrid)
Prof. Roberto Zilles, Aim Pinto e Marcelo Almeida (Universidade de So Paulo)
Para:
Deutsche Gesellschaft fr
Internationale Zusammenarbeit (GIZ) GmbH
Elaborado por:
Peter Krenz (Instituto Ideal)
com apoio de:
Prof. Dr. Ingo Stadler (Fachhochschule Kln)
Prof. Eduardo Lorenzo Pigueiras (Universidad Politcnica de Madrid)
Prof. Roberto Zilles, Aim Pinto e Marcelo Almeida (Universidade de So Paulo)
Para:
Informaes Legais
1.
2.
Contedo
Introduo
11
14
19
20
Referncias Bibliogrficas
22
24
Introduo
A Resoluo Normativa 482, publicada pela Agncia Nacional de Energia Eltrica (ANEEL), em 17 de
abril de 2012, abriu novas perspectivas para a gerao distribuda no Brasil. A resoluo reduz as
barreiras para a conexo de pequenos geradores de energia renovvel rede de distribuio [1].
Os avanos provenientes da publicao da resoluo se baseiam, de maneira geral, na definio da
micro e minigerao distribuda a partir de fontes renovveis e na definio do sistema de
compensao de energia. Segundo a resoluo, microgerao distribuda uma central geradora
com potncia igual ou inferior a 100 kW que utilize fontes com base em energia hidrulica, solar,
elica, biomassa ou cogerao qualificada. J a minigerao distribuda uma central geradora com
potncia superior a 100 kW e inferior ou igual 1MW que utilize as fontes energticas citadas [1].
A grande inovao da resoluo, contudo, fica por conta da criao do sistema de compensao de
energia eltrica [1]. Consumidores que instalarem sistemas de micro ou minigerao podero injetar
na rede de distribuio a energia excedente produzida pelo seu sistema e receber crditos em kWh
com validade de 36 meses para ser descontados da conta de energia. Desse modo, a rede eltrica
atua como uma bateria do sistema, j que a eletricidade no precisa ser consumida no mesmo
momento em que foi gerada.
As condies de acesso ao sistema de distribuio so estabelecidas na Seo 3.7 do Mdulo 3 dos
Procedimentos de Distribuio de Energia Eltrica no Sistema Eltrico Nacional PRODIST. As
distribuidoras devem atender s solicitaes de acesso para micro e minigeradores distribudos de
acordo com os termos do PRODIST e definir as condies tcnicas da instalao, assim como os
equipamentos exigidos.
O novo mercado de gerao distribuda (GD) formado por consumidores residenciais, pequenos
comrcios e indstrias, ou seja, em geral por consumidores de menor porte e em baixa tenso. Em
projetos de pequena potncia, os custos de alguns equipamentos exigidos pelo PRODIST acabam
tendo um peso considervel no investimento total da instalao, que podem se tornar um
impedimento para a viabilidade econmica de tais projetos. Ao comparar essas exigncias com
normas tcnicas j aplicadas e consagradas no mercado internacional para sistemas com at
30 kWp, percebe-se que so solicitados equipamentos j em desuso quando o objetivo garantir a
segurana do acesso rede de distribuio.
O principal deles o elemento de desconexo, que deve ser visvel e acessvel pela concessionria
para garantir a desconexo da central geradora durante manuteno no sistema de distribuio, mais
comumente chamado no Brasil de Dispositivo de Seccionamento Visvel (DSV). Esse elemento j
no mais exigido em vrios pases, como Alemanha e Itlia, naes essas que concentram mais de
48 % da capacidade de energia fotovoltaica instalada do mundo (figura 1).
pases, com o exemplo da Alemanha, que possui bastante experincia com sistemas que poderiam
ser classificados como micro e minigerao distribuda.
O anexo deste documento trs comentrios pertinentes de diversos especialistas sobre o tema.
Alm disso, tanto para micro quanto para minigerao distribuda necessrio um elemento de
desconexo. Este elemento uma chave com a funo de dispositivo seccionador que garanta a
desconexo da central geradora durante a manuteno do sistema de distribuio. A chave
seccionadora deve ser visvel e acessvel pela concessionria acessada:
Chave seccionadora visvel e acessvel que a acessada usa para garantir a
desconexo da central geradora durante manuteno em seu sistema [4, pgina 79].
Conforme Figura 3, esta chave seccionadora (DSV) leva a custos adicionais que no caso de
microgeradores de pequeno porte podem chegar a ser proibitivos. Nos captulos 4 a 6 ser explicado
porque os DSV caram em desuso nos maiores mercados de energia fotovoltaica para
microgeradores de pequeno porte.
Alm disso o PRODIST define que:
A acessada pode propor protees adicionais, desde que justificadas tecnicamente,
em funo de caractersticas especficas do sistema de distribuio acessado,
exceto para central geradora classificada como microgerao distribuda [4, pgina
80].
O que se percebe, no entanto, que algumas concessionrias exigem que o quadro seja dotado de
equipamentos que oferecem segurana redundante para a conexo do sistema fotovoltaico. Isso
porque as protees necessrias para a conexo rede eltrica j so realizadas pelos inversores,
quando em conformidade pelas normas nacionais e internacionais sobre segurana para a conexo
[5].
A seguir sero apresentados dois exemplos de exigncias de segurana, que incluem a definio
para a instalao do Dispositivo de Seccionamento Visvel por parte das concessionrias.
CELESC
Segundo as normas da CELESC, quando a rede na qual est conectado o micro ou minigerador
estiver desenergizada pela concessionria, por causas emergenciais ou por manuteno, o gerador
do acessante dever ser automaticamente desconectado [6, pgina 7].
Com base nisso, pode-se concluir que um Dispositivo de Seccionamento Visvel seria redundante, j
que essa desconexo dever ser feita automaticamente. O inversor do sistema j capaz de atender
essa exigncia.
Mas, mesmo assim, a CELESC exige a instalao de uma caixa com Dispositivo para Seccionamento
Visvel (DSV), conforme o item "Adequaes no Padro de Entrada" citado abaixo [6, pgina 11]:
O manual inclui ainda diagramas orientativos tpicos para conexo de micro ou minigeradores que
so exibidos abaixo:
Figura 5: CELESC Diagrama Orientativo de Conexo na baixa tenso BT [6, pgina 19]
O DSV deve ser dimensionado adequadamente carga conectada. Na ordem da conexo segundo a
figura 5, necessrio instalar um DSV de maior capacidade para atender carga da unidade
consumidora alm da carga do sistema fotovoltaico. Os custos do DSV aumentam proporcionalmente
carga conectada.
Segue o diagrama orientativo de conexo para sistemas fotovoltaicos no nvel da media tenso (MT).
Figura 6: CELESC - Diagrama Orientativo de Conexo na media tenso MT at 300 kVA [6, pgina 21]
Figura 7: CELESC - Diagrama Orientativo de Conexo na media tenso MT acima de 300 kVA [6, pgina 23]
LIGHT
A Light SESA publicou os Procedimentos para a Conexo de Acessantes ao Sistema de Distribuio
Conexo em Baixa Tenso Informao Tcnica DTE/DTP 01/12, de 13 de dezembro de 2012. A
conexo rede de eletricidade de geradores que usam inversores como interface deve ser feita na
forma como indicam as definies dos procedimentos [7]:
A Light SESA define o dispositivo de seccionamento visvel (DSV) como
uma chave seccionadora sob carga abrigada por um invlucro que a Light SESA
utilizar para garantir a desconexo da Microgerao durante manuteno em seu
sistema. O DSV dever ser instalado aps a caixa de medio do padro de entrada
conforme os diagramas unifilares em seguida (Figura 9).
A chave seccionadora dever ter capacidade de conduo e abertura compatvel
com a potncia da Microgerao. Sua caracterstica construtiva dever garantir a
velocidade de acionamento independente do operador. A chave tambm dever
possuir indicao da posio (Liga/Desliga) em portugus [7, pgina 19].
Figura 8: Light SESA Padro de Entrada com DSV [7, pgina 22]
Figura 9: Light SESA Forma de conexo (atravs de inversor) rede de BT [7, pgina 16]
Em comparao com a norma da CELESC, a especificao da Light tem a vantagem de manter a
unidade consumidora (Carga) conectada rede de distribuio quando o DSV desconectado. A
figura seguinte mostra como seria uma instalao com as conexes eltricas necessrias para um
sistema fotovoltaico no telhado de um edifcio atendido pela Light. Alm da dificuldade da instalao e
dos custos com o DSV, o sistema precisaria de cabos, levaria a perdas na transmisso da energia e
queda de tenso. O resultado disso uma reduo na viabilidade econmica do projeto. A figura 10
ilustra essas dificuldades.
10
Sistemas at 30 kVA
A conexo de sistemas com potncia mxima aparente da unidade geradora SEmax de at 4,6
kVA pode ser realizada atravs de uma conexo monofsica. Por isso podem ser instalados
at trs inversores monofsicos, sendo cada um com uma potncia mxima aparente de at
4,6 kVA (para clculo da potncia total do grupo de geradores, utiliza-se a frmula
SAmax = SEmax = 3 x 4,6 kVA 13,8 kVA.
11
Para capacidades maiores, a conexo deve ser trifsica com o objetivo de evitar assimetrias
de tenso (Figura 11). Um Sistema de Balano de potncia no necessrio.
O dispositivo de proteo da rede e das instalaes DPRI, conforme VDE 0126 pode ser
integrado nos inversores.
Figura 11: Exemplo de conexo com potncia de at 3x4,6 kVA (13,8 kVA)
(baseado em VDE-AR-N 4105, p. 49) [9]
A conexo de sistemas com potncia entre 13,8 kVA e 30 kVA deve ser feita com inversores trifsicos
ou com uma ligao de comunicao entre os inversores (Figura 12).
12
Tambm no sendo necessrio um DSV de acordo com a reviso da DIN VDE 0100-551 [11],
[9, item 5.5 e 8.2, pginas 21-22 e 36].
13
Above ground level connection point of the house connection cable to the low voltage grid
(cable connection board or transformer station)
House connection box in case it is accessible to grid operator personnel without limitations
Especially for photovoltaic systems a unit for grid supervision with switching element
according to E DIN VDE 0126 can replace the functions of a section switch and decoupling
protection.
This supervision unit has been developed for photovoltaic systems with a nominal power of less than
4.6 kVA that feed power to the grid on a single phase. This supervision unit also can be used for all
generator types and inverter based power generators up to a nominal power of 30 kVA and three
phase connection. The unit can be integrated into an inverter or can be conducted as an independent
protection device.
The protection device according to E DIN VDE 0126 contains voltage and frequency
supervision and evaluates grid impedance leaps as additional criterion. Due to those three
criteria and its redundant construction it fulfills the necessary safety requirements. Therefore, the
normally requested switch with disconnection functionality that needs to be accessible by grid
operator personnel and also the separate voltage and frequency supervision can be omitted.
The supervision unit requires having a test certificate that is issued by an accredited test laboratory.
The supervision unit requires having a voltage reduction protection in all three phases although the
feed-in is only single phase [12].
14
Section switch
The above described supervision unit is connected with a section switch. This section switch can be
one of the following types:
Fuse switch
The section switch must assure an all-phase galvanic separation. The function of the section switch
can be fulfilled with the above described supervision unit and therefore directly coupled with the
section switch.
The section switch either can be
A switch that connects the complete customer side with the grid, or
A switch that connects the generation unit with the rest of the customer installation.
With generation units that are connected to the grid via frequency converters or inverters the section
switch must be installed on the grid side of the power electronic device. It must not be affected in its
functionality by a short-circuit within the converter.
The section switch must be designed for the maximum possible short circuit current and must trigger
without delay.
15
16
Generation units require a protection unit that interrupts power feed-in to the grid and allows
safe maintenance work at grid assets. This protection device should be allowed to be an
integral part of the generation system in order to avoid unnecessary costs, like is usual in these
countries shown before [12].
The component that makes the grid connection in case of a small photovoltaic generator
is the inverter. Inverters are nowadays a mass product and one is equal to the other.
Therefore, it is a much more reasonable procedure that the inverter manufacturer tests
his equipment with an accredited test laboratory and receives therefore a test certificate.
With the conformity declaration he then confirms that all his inverters are in accordance
with the test [12]. Therefore, the installation of a separate device would be redundant.
Figura 14 shows the test certificate and the conformity declaration of an inverter manufacturer
[12].
Figura 14: Test certificate (left) and conformity declaration (right) of inverter manufacturer KACO
[Source: Kaco]
17
18
Alm disso, a Norma NBR 16149:2013, estabelece que os setpoints de tenso so referidos ao
ponto de conexo (PCC) e a queda de tenso entre o inversor e o ponto de conexo deve ser
levada em conta, ou seja, deve-se ajustar os setpoints no inversor de forma a evitar
desligamentos antecipados, permitindo a incorporao do DPRI aos inversores mesmo para
sistemas acima de 30 kVA.
Resumo
Para garantir que o DPRI seja efetivamente confivel, se exige o cumprimento das
normas de segurana atuais (VDE na Alemanha e ABNT NBR no Brasil).
Alm de proteger contra o funcionamento em ilha, o DPRI atua nos casos em que a
tenso no ponto de conexo rede do produtor de energia fotovoltaica estiver fora das
margens estabelecidas para garantir a qualidade do fornecimento eltrico.
Potncia
(kWp)
Custo de DSV
(R$)
0,25
2.200,00*
1.000,00
45,45%
0,5
4.200,00
1.000,00
23,81%
8.089,00
1.000,00
12,36%
26.267,00
1.000,00
3,81%
44.445,00
1.000,00
2,25%
89.890,00
1.000,00
1,11%
10
20
Custo
Adicional
21
Referncias Bibliogrficas
[1]
[2]
[3]
[4]
[5]
Jonas Rafael Gazoli, Marcelo Gradella Villalva e Juarez Guerra: Energia solar
fotovoltaica Sistemas conectados rede eltrica: requisitos para a conexo e
protees.
Disponvel em:
http://www.osetoreletrico.com.br/web/documentos/fasciculos/Ed83_fasc_energia_renovav
el_cap11.pdf
[6]
[7]
[8]
Beatriz Abdalla, Lucas Paulis, LIGHT SESA: Padres e Desafios para a Conexo de
GD ao Sistema de Distribuio.
Disponvel em:
http://www.solarize.com.br/downloads/seminario_setembro_2013/Seminario%20FV%202
013-09%20Light%20-%20Padroes%20e%20desafios%20para%20GD.pdf
[9]
[10]
22
[12]
Prof. Dr. Stadler, Ingo: Study about International Standards for the connection of
Small Distributed Generators to the power grid. Deutsche Gesellschaft fr
Internationale Zusammenarbeit (GIZ) GmbH, Jun. 2011
Disponvel em:
http://www.americadosol.org/wp-content/uploads/2011/07/International-Standards-for-theconnection-of-Small-Distri.-Generators-Cologne-University-GIZ-2011.pdf
[13]
[14]
[15]
23
24
25
26
Explicacin
La norma VDE-AR-N 4105 regula la conexin de generadores en general (no especficamente
fotovoltaicos) a la red de distribucin de baja tensin, y que operan en paralelo con ella.
Una novedad significativa, respecto de ediciones anteriores de la misma norma, es la obligacin impuesta
a los generadores de contribuir a la estabilidad de la tensin.
La norma permite integrar en un nico dispositivo la proteccin de la red y de las instalaciones. Este
dispositivo debe actuar, aislando al generador de la red de distribucin, entre otros eventos, cuando el
voltaje sale fuera de los mrgenes establecidos para garantizar la calidad del servicio ( 10% en la norma
DIN EN 50160).
El comit de expertos que redact la norma acord que cuando la potencia aparente de la instalacin
generadora es superior a 30 kVA (S_Amax > 30 kVA) las cadas de tensin en la red interior del cliente
pueden ser suficientemente importantes como para hacer que la tensin en el punto de conexin de la
instalacin generadora a la red del cliente (PCIG) difiera significativamente de la tensin en el punto de
conexin del cliente a la red de distribucin (PCC). Obviamente, esto afecta a la actuacin de las
protecciones frente a sobretensin. Por ejemplo, puede darse el caso de que la tensin en el PCC sea
inferior a 1,1 veces la tensin nominal (lmite mximo de tensin segn DIN EN 50160) pero que,
simultneamente, la tensin en el PCIG sea superior a ese lmite. Entonces, si la proteccin atendiera a la
tensin en el PCIG, ocurrira que la instalacin generadora dejara de inyectar potencia en la red de
distribucin aun estando sta en debido orden. Por esta razn, y en lo que respecta a sistemas
fotovoltaicos, la norma impone que cuando S_Amax> 30 kVA, la proteccin debe instalarse directamente
en el punto de conexin del cliente a la red de distribucin.
Para potencias inferiores a este valor, los expertos que redactaron la norma entienden que las cadas de
tensin en el interior de la red del cliente son normalmente poco importantes, de forma que no hay gran
diferencie entre instalar la proteccin en el PCC o en el PGIC. Por esta razn, y en lo que respecta a
sistemas fotovoltaicos, la norma permite que cuando S_Amax 30 kVA, la proteccin pueda estar
directamente integrada en el inversor.
27
Exigir el uso de esta tecnologa segura, imponiendo que el sistema fotovoltaico incluya un
interruptor automtico que cumpla con esa normativa especfica. Esta es la va por la que han
optado Alemania, Espaa y otros pases.
Permitir el uso de tecnologa menos segura (interruptor automtico que no se ajuste a esas
normas) y obligar a instalar un interruptor manual accesible a esos operarios.
Permitir las dos posibilidades anteriores simultneamente, dejando que sea la compaa
distribuidora quien decida.
Optar por una va u otra es principalmente una cuestin de confianza en la tecnologa, aunque otras
consideraciones relacionadas con la poltica industrial tambin pueden influir. Por ejemplo, hace algunos
aos hubo intentos de imponer en Europa que todos los interruptores automticos para la proteccin
frente al funcionamiento en isla estuvieran basados en medir la impedancia de la red (que aumenta mucho
cuando se produce una isla). El intento estaba apoyado por un grupo de empresas que haban desarrollado
esa tecnologa, pero no fue adelante, porque muchos otros se opusieron y demostraron que otras
posibilidades eran igual de buenas o mejores. De hecho, la tecnologa actualmente ms extendida se basa
en un concepto diferente, conocido como deriva de frecuencia.
Dejando al margen episodios anecdticos como este, lo cierto que es hay un patrn histrico, ms
ajustado a la idea de la confianza, que se ha repetido en varios pases (Alemania y Espaa, por ejemplo):
primero, desde la desconfianza, se opta por exigir la instalacin de un interruptor manual accesible a los
operarios y, despus, desde la confianza que da la experiencia, se opta por prescindir de este interruptor
de actuacin manual y accesible y por exigir, eso s, que el interruptor automtico incorporado en el
sistema cumpla con la normativa especfica.
Importa mucho entender que este asunto de la seguridad de los operarios no est relacionado ni con el
tamao de la instalacin fotovoltaica ni con la ubicacin del interruptor. Es simplemente una
cuestin de confiar o no en la tecnologa de los interruptores automticos.
Para garantizar la calidad del suministro elctrico y tambin para proteger al sistema
fotovoltaico, el interruptor debe desconectarse automticamente no slo en caso de funcionamiento
en isla sino tambin en caso de sobretensin o de subtensin. Ahora bien, ocurre que el perfil de
tensiones es variable (en funcin del consumo y de la generacin fotovoltaica) tanto en el tiempo como a
lo largo de las lneas de distribucin de las compaas distribuidores y de la lnea interna del cliente (en
este caso, el propietario del sistema fotovoltaico). Obviamente, los mrgenes permitidos para la tensin
28
se definen precisamente en el punto de conexin del cliente a la red de distribucin, por lo que como
idea general los interruptores deberan estar situados precisamente en este punto (o bien estar
hechos de tal manera que acten en funcin de la tensin en ese punto).
Ahora bien, cuando se trata de sistemas de pequea potencia, las cadas de tensin en los
cableados internos del cliente son normalmente poco importantes, por lo que no hay mucha diferencia
prctica entre colocar el interruptor en el punto de conexin del cliente a la red o colocarlo en cualquier
otro punto de la instalacin interna del cliente, por ejemplo, en la salida del propio inversor. Por esta
razn, y para facilitar la instalacin de los sistemas fotovoltaicos de pequea potencia, que son los ms
interesantes para las personas de clase media, por debajo de un cierto lmite de potencia se permite que el
interruptor automtico, que de todas formas tiene que cumplir con la normativa especfica, est
incorporado en la salida del inversor.
Obviamente, las cadas de tensin dependen de la potencias de consumo y de generacin
fotovoltaica, y de las longitudes y secciones del cableado, por lo que cabra pensar en hacer un estudio
detallado para determinar lo que es pequea potencia en cada caso. Sin embargo esto sera muy poco
prctico, por lo que se opta por establecer un valor razonable y de uso general. En el caso de Alemania,
este valor ha sido fijado por el comit de expertos que redact la norma en 30 kVA. La costumbre de
establecer valores nicos que se aplican de forma general, en vez de valore especficamente estudiados
para cada caso est muy extendida en el sector elctrico. Por ejemplo, es lo que ocurre con las secciones
de los cableados o con los tamaos de los transformadores de la red de distribucin.
En resumen:
La seguridad de los operarios de las compaas distribuidoras no se ve afectada por la localizacin
del interruptor, sino por la fiabilidad en la deteccin del funcionamiento en isla y en la interrupcin
automtica de la generacin fotovoltaica.
Hoy existe tecnologa y normativa suficiente para garantizar que, si se exige su cumplimiento, el
interruptor automtico sea efectivamente fiable.
El interruptor, adems de proteger frente al funcionamiento en isla, debe actuar en caso de que la
tensin en el punto de conexin del cliente a la red est fuera de los mrgenes establecidos para garantizar
la calidad del suministro elctrico.
Cuando los sistemas son de pequea potencia, la cada de tensin en la red interior del cliente es
normalmente pequea, por lo que puede permitirse la instalacin del interruptor en el interior del propio
inversor.
29
30
31
32