Você está na página 1de 12

Aula 2 - Exercícios

01) Script de programação:

# -*- coding: utf-8 -*-

from __future__ import print_function


from CoolProp import AbstractState
from CoolProp.CoolProp import PhaseSI, PropsSI, get_global_param_string
import CoolProp.CoolProp as CoolProp
from CoolProp.HumidAirProp import HAPropsSI
from math import sin
import math

#Dados de entrada
#Alterar
T_evap=273.15+(-5) #K
T_cond=273.15+40 #K

#constantes

T1=T_evap+7 #k
RendV=70/100
RendG=45/100
n=3500/60
V_des=25/(10**6)

#Obtenção das propriedades


P_evap=PropsSI('P','T',T_evap,'Q', 1,'R410A') #Pa, pressao de evaporacao

P_cond=PropsSI('P','T',T_cond,'Q', 1,'R410A')

s1=PropsSI('S','T',T1,'P', P_evap,'R410A') #J/kgK, entropia succao do compressor

s2=s1 #J/kgK, entropia descarga do compressor

P_cond=PropsSI('P','T',T_cond,'Q', 1,'R410A') #Pa, pressao de condensação

H1=PropsSI('H','T',T1,'P',P_evap,'R410A')

H2=PropsSI('H','S',s2,'P',P_cond,'R410A')

rho1=PropsSI('D','T',T1,'P',P_evap,'R410A')

#Calculo Vazão massica e potencia de acionamento


mr=rho1*n*V_des*RendV

wc=((mr*(H2-H1))/RendG)

#FIM

Variando a Temperatura de evaporação (T_evap) e a temperatura de condensação


(T_cond) obtivemos os dados dispostos abaixo:

T_evap T_cond rho1 mr H1 H2 H2-H1 Wc


Letra (ºc) (ºc) (kg/m^3) (kg/s) (kJ/kg) (kJ/kg) (kJ/kg) (kJ/kg)
a -5 40 24,797 0,0253 427,16 463,98 36,82 2,07
b 5 40 34,1 0,0348 430,75 457,78 27,03 2,09
c -5 50 24,797 0,0253 427,16 471,18 44,02 2,48

Nota-se que com o aumento da temperatura de evaporação, houve um acréscimo na vazão


mássica, tal fenômeno ocorre para que a capacidade de refrigeração se mantenha. Com a
variação na temperatura de condensação, houve um aumento significativo no trabalho gasto
pelo compressor, isso ocorre, devido a pressão de condensação ser maior, gastando assim
maior “trabalho” do compressor para elevar a pressão do fluido.
2) Script de programação:

# -*- coding: utf-8 -*-

from __future__ import print_function


from CoolProp import AbstractState
from CoolProp.CoolProp import PhaseSI, PropsSI, get_global_param_string
import CoolProp.CoolProp as CoolProp
from CoolProp.HumidAirProp import HAPropsSI
from math import sin
import math

#Dados de entrada
#Alterar
T_evap=273.15+(-20) #K

#constantes
T_cond=273.15+35 #K
T1=273.15+20 #k

#Obtenção das propriedades

P_evap=PropsSI('P','T',T_evap,'Q', 1,'n-Propane') #Pa, pressao de evaporacao

s1=PropsSI('S','T',T1,'P', P_evap,'n-Propane') #J/kgK, entropia succao do


compressor

s2=s1 #J/kgK, entropia descarga do compressor

P_cond=PropsSI('P','T',T_cond,'Q', 1,'n-Propane') #Pa, pressao de condensação

h1=PropsSI('H','T', T1 ,'P', P_evap ,'n-Propane') # J/kg, entalpia de aspiração

h2=PropsSI('H','P',P_cond, 'S', s2, 'n-Propane') # J/kg, entalpia de descarga

rho1=PropsSI('D','P',P_evap, 'T',T1, 'n-Propane')


O compressor escolhido, que atende os requisitos foi o Embraco - EMX6165U
Os dados obtidos através do script de programação com os dados fornecidos pela catalogo
do fornecedor foram:

T_evap Q wc mr(k w/ H1 H2 rho1 P2 Rend_V Rend_G


(ºc) (W) (kW) g/s) w (kJ/kg) (kJ/kg) (kg/m^3) P1 (Pa) (Pa) P2/P1 (%) (%)
0,00 1. 244518, 12178
-20 346 0,186 11 86 617,56 707,92 4,62 28 83,29 4,98 0,51 0,52
0,00 2. 291623, 12178
-15 428 0,198 13 16 616,06 694,99 5,56 59 83,29 4,18 0,52 0,53
0,00 2. 345279, 12178
-10 524 0,209 16 51 614,31 682,54 6,65 94 83,29 3,53 0,54 0,53
0,00 2. 406037, 12178
-5 636 0,217 20 93 612,28 670,49 7,92 03 83,29 3,00 0,55 0,53
0,00 3. 474457, 12178
0 762 0,223 24 42 609,93 658,78 9,38 54 83,29 2,57 0,56 0,53
0,00 3. 551116, 12178
5 905 0,227 29 99 607,2 647,31 11,09 61 83,29 2,21 0,57 0,51
106 0,00 4. 636601, 12178
10 4 0,228 34 66 604,03 635,99 13,06 56 83,29 1,91 0,57 0,48

Para obter as equações do rendimento volumétrico e global, dispomos os valores em um


gráfico e fizemos as devidas regressões. As equações apresentadas foram:

Rend_V= -0,0227 * (P2/P1) + 0,618


Rend_G= 0,327 + 0,113 * (P2/P1) - 0,0152 * (P2/P1)^2

Segue gráficos abaixo:


3) Script de programação:

# -*- coding: utf-8 -*-


"""
Created on Wed Jan 27 19:01:37 2021

@author: Flavio
"""

from __future__ import print_function


from CoolProp import AbstractState
from CoolProp.CoolProp import PhaseSI, PropsSI, get_global_param_string
import CoolProp.CoolProp as CoolProp
from CoolProp.HumidAirProp import HAPropsSI
from math import sin
import math

#dados de entrada
#R134a

T_evap=273.15+0 #K
T_cond=273.15+45 #K
Q=650 #W
delta_sub=4 #k
D=1/1000 #m
T3=T_cond-delta_sub

P_evap=PropsSI('P','T',T_evap,'Q',1,'R134a')

P_cond=PropsSI('P','T',T_cond,'Q',1,'R134a')

H3=PropsSI('H','T',T3,'P',P_cond,'R134a')

X3=PropsSI('Q','H',H3,'P',P_evap,'R134a')

P4=P_evap

H4=H3

#TRANSIÇÃO

P_TRANS=P_evap

X_TRANS=X3

DELTA_P=100

while (X_TRANS>=0):
if (X_TRANS<=0.0001):
print(X_TRANS, P_TRANS)
break
else:
P_TRANS=P_TRANS+DELTA_P
X_TRANS=PropsSI('Q','P',P_TRANS,'H',H3,'R134a')

T_TRANS=PropsSI('T','P',P_TRANS,'Q',0,'R134a')

DELTAP_MONO=P_cond-P_TRANS

H1=PropsSI('H','T',T_evap,'Q',1,'R134a')

m=Q/(H1-H4)

A=(3.14*(D**2)/4)

G=m/A

Visc=PropsSI('V', 'P',P_cond,'H',H3,'R134a')

rho3=PropsSI('D','P',P_cond,'H',H3,'R134a')

V3=1/rho3

#REGIAO MONOFASICA

Re_mono=(G*D)/Visc

if (Re_mono>2*(10**4)):
f_mono=0.184*((Re_mono)**(-1/5))
else:
f_mono=0.316*((Re_mono)**(-1/4))

L_mono=((DELTAP_MONO*2*D)/(f_mono*V3*(G**2)))

#regiãoBifasica

P_med=((P_evap+P_TRANS)/2)

X_med=PropsSI('Q','H',H4,'P',P_med,'R134a')

T_med=PropsSI('T','H',H3,'P',P_med,'R134a')

#REGIAO LIQUIDA

rho_L=PropsSI('D','Q',0,'P',P_med,'R134a')
V_L=1/rho_L

Visc_L=PropsSI('V','Q',0,'P',P_med,'R134a')

#REGIAO DE VAPOR

rho_V=PropsSI('D','Q',1,'P',P_med,'R134a')

Visc_V=PropsSI('V','Q',1,'P',P_med,'R134a')

#CALCULO DO PARAMETRO DE MARTINELLI

X_MART=(((1-X_med)/X_med)**0.9) * ((rho_L/rho_V)**0.5) * ((Visc_L/Visc_V)**0.1)

#CALCULO DE REYNOLDS

Re_bi_L=(G*(1-X_med)*D)/Visc_L

Re_bi_V=(G*X_med*D)/Visc_V

#Calculo do fator corretivo

if (Re_bi_L>2300) and (Re_bi_V>2300):


C=20
else:
if (Re_bi_L<2300) and (Re_bi_V>2300):
C=12
else:
if (Re_bi_L>2300) and (Re_bi_V<2300):
C=10
else: C=5

Corr=1+(C/X_MART)+(1/(X_MART**2))

#CALCULO DO FATOR DE ATRITO

if (Re_bi_L>2*(10**4)):
f_bi_L=0.184*((Re_bi_L)**(-1/5))
else:
f_bi_L=0.316*((Re_bi_L)**(-1/4))

#Calculo perda de presão bifase

DeltaP_bi=P_TRANS-P_evap

#calculo do L Bifasico

L_bi=((DeltaP_bi*D*2)/(f_bi_L*V_L*Corr*((G-(1-X_med))**2)))
#Comprimento total

L_total=L_bi+L_mono

#UFAA! eu consegui!

O comprimento total encontrado foi de: L_total= 1,844 m


4) Script de programação:

# -*- coding: utf-8 -*-


"""
Created on Tue Jan 26 18:52:23 2021

@author: Flávio
"""

from __future__ import print_function


from CoolProp import AbstractState
from CoolProp.CoolProp import PhaseSI, PropsSI, get_global_param_string
import CoolProp.CoolProp as CoolProp
from CoolProp.HumidAirProp import HAPropsSI
from math import sin
import math

#variavel
T_cond=273.15+40

#constantes
Q=1000
T_evap=273.15+(-5)
delta_sub=3
delta_sup=7
T1=T_evap+delta_sup
T3=T_cond-delta_sub

P_evap=PropsSI('P','T', T_evap, 'Q', 1, 'R410A')

P_cond=PropsSI('P','T', T_cond, 'Q', 1, 'R410A')

H1=PropsSI('H','T',T1,'P',P_evap,'R410A')

H3=PropsSI('H','T',T3,'P',P_cond,'R410A')

H4=H3

rho3=PropsSI('D','T',T3,'P',P_cond,'R410A')

m=Q/(H1-H4)

CdA=m/((2*rho3*(P_cond-P_evap))**0.5)

#fim

o produto de CdA encontrado para T_cond=40 foi de: 1,0196e-7


Variando a temperatura de condensação (T_cond) de 40ºc para 50ºc, encontramos
os seguintes valores:

Para o segundo caso, a vazão mássica aumenta, devido a capacidade de


refrigeração diminuir com o aumento da pressão de condensação. O produto CdA
diminui, devido ao aumento na diferença de pressão (P3-P4).