RELATÓRIO DE ENSAIO NÃO FR-OP-002

DESTRUTIVO POR LÍQUIDO REV: 05


PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-001-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 001-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-001-08/22 - LP - Olhal Helideck - 001-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-002-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 002-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-002-08/22 - LP - Olhal Helideck - 002-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-003-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 003- SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-003-08/22 - LP - Olhal Helideck - 003- SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-004-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 004-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-004-08/22 - LP - Olhal Helideck - 004-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-005-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 005-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-005-08/22 - LP - Olhal Helideck - 005-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-006-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 006-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-006-08/22 - LP - Olhal Helideck - 006-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-007-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 007-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-007-08/22 - LP - Olhal Helideck - 007-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-008-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 008-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-008-08/22 - LP - Olhal Helideck - 008-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-009-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 009-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-009-08/22 - LP - Olhal Helideck - 009-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-010-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 010-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-010-08/22 - LP - Olhal Helideck - 010-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-011-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 011-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-011-08/22 - LP - Olhal Helideck - 011-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-012-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 012-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-012-08/22 - LP - Olhal Helideck - 012-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-013-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 013-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-013-08/22 - LP - Olhal Helideck - 013-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-014-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 014-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-014-08/22 - LP - Olhal Helideck - 014-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-015-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 015-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-015-08/22 - LP - Olhal Helideck - 015-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-016-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 016-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-016-08/22 - LP - Olhal Helideck - 016-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-017-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 017-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-017-08/22 - LP - Olhal Helideck - 017-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date:


Liftingtest.com
comercial@liftingtest.com
+55 (22) 2757-1125 / +55 (22) 99998-9897
Av. Nossa Senhora da Glória, 1109, C/3, Praia Campista
Macaé/RJ – CEP: 27.923-215
RELATÓRIO DE ENSAIO NÃO FR-OP-002
DESTRUTIVO POR LÍQUIDO REV: 05
PENETRANTE
TEST REPORT FOR NON- Data: 18/01/21
DESTRUCTIVE PENETRANT CERTIFICADO Nº:
LIQUID 239-018-08/22
CLIENTE: OCEÂNICA ENGENHARIA OBRA / CONTRATO: 239/22
Client: Work / Contract
LOCAL DO ENSAIO: OCEÂNICA SUB VI EQUIPAMENTO: Olhal Helideck
Site of the test Equipment NS 018-SUB VI
NORMA E CRITÉRIO DE REFERÊNCIA: N-1596-H PROCEDIMENTO: PR-OP-004 REV.: 3
Reference Standards and Criteria AWS D1.1 Procedure REV.
MATERIAL: Aço Carbono CONDIÇÃO DA SUPERFÍCIE: Escovada ESPESSURA: N/A
Material Condition Surface Thickness
LUMINOSIDADE: 2100 LUX TEMPERATURA DA SUPERFÍCIE: 32º C
Luminosity: Surface Temperature:
SOLVENTE / SOLVENT PENETRANTE / PENETRATING REMOVEDOR / REMOVER REVELADOR / DEVELOPER
Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer: Fabricante Manufacturer:
METAL CHECK METAL CHECK N/A METAL CHECK
Ref. Comercial: E-59 Ref. Comercial: VP-30 Ref. Comercial: ÁGUA Ref. Comercial: D-70
Trade Reference Trade Reference Trade Reference: Water Trade Reference

Nº Lote Nº Lot: 20-0160 Nº Lote Nº Lot: 21-0273 Nº Lote Nº Lot: N/A Nº Lote Nº Lot: 21-0255
Validade: 10/2022 Validade: 05/2023 Validade: N/A Validade: 04/2023
Expire Date: Expire Date: Expire Date: Expire Date:
SOLDA / PEÇA DESCONTINUIDADES DISCONTINUITY OBSERVAÇÕES
WELDING / PART Nº Tipo / Type Cota / Quote Compr / Length LAUDO / Report NOTES
Soldas do olhal N/A N/A N/A N/A Aprovado
Inspeção em 100% LT 239-018-08/22 - LP - Olhal Helideck - 018-SUB VI
LEGENDA SUBTITLE: TR – Trinca ramificada PO – Poro ou porosidade
REC – Recomendação de Exame Complementar Branched crack Pore ou porosity
Recommendations for further Review FF – Falta de fusão / Lack of fusion MO – Mordedura / Bite
TL – Trinca longitudinal / Longitudinal crack FP – Falta de penetração SP – Sobreposição
TT – Trinca transversal / Transverse crack Lack of penetration Superposition
Instrumentos Calibráveis / Calibrable Instruments:
Luxímetro MLM-1011-NS:727622-141595/22-06/2023 -

INSPETOR / INSPECTOR CONTROLE DA QUALIDADE / Q C CLIENTE / CLIENT

Data / Date: 03/08/2022 Data / Date: 03/08/2022 Data / Date: