Você está na página 1de 1

OLIAR SERVIÇOS E COMERCIO LTDA EPP

Refrigeraçaã o Industrial, Climatizaçaã o e Projetos de Automaçaã o


CÁLCULO DA CARGA TÉRMICA (VERÃO e INVERNO) (47)3025-5070 – adm@oliar.srv.br
CLIENTE: cliente
OBRA: endereço - obra
REF.: 1
DATA: 3/27/2019

CIDADE: Joinville ÁREA: 23.1 m2 OCUP. AR EXT. CARGA TÉRMICA VERÃO


LATITUDE: 26.3 ° SUL PÉ DIR.: 6 m HORA Pessoas m3/h HORA JAN FEV MAR ABR MAI SET OUT NOV DEZ
ALT.: 4 m VOL.: 138.6 m3 8:00 05 0 8:00 1.6 1.6 1.6 1.5 1.5 1.6 1.6 1.6 1.6
9:00 05 0 9:00 1.7 1.7 1.6 1.6 1.5 1.6 1.6 1.6 1.6
CONDIÇÕES INTERNAS CONDIÇÕES EXTERNAS 10:00 05 0 10:00 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.7 1.7
TBS= 23 [°C] 15:00 hs Verão Inverno 11:00 05 0 11:00 1.7 1.7 1.7 1.7 1.6 1.7 1.7 1.7 1.7
TBU= 16.3 [°C] 50%UR TBS= 35 2.4 [°C] 12:00 05 0 12:00 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7
h= 10.864624 [kcal/kg] TBU= 31.8 -1.2 [°C] 13:00 05 0 13:00 1.8 1.8 1.8 1.7 1.7 1.7 1.8 1.8 1.8
Dens.= 1.1754165 [kg/m3] DTdiário= 15 [°C] 14:00 05 0 14:00 1.8 1.8 1.8 1.8 1.7 1.8 1.8 1.8 1.8
DTanual= 25 [°C] 15:00 05 0 15:00 1.8 1.8 1.8 1.8 1.7 1.8 1.8 1.8 1.8
CALOR POR PESSOA TAXA DE RENOVAÇÃO DE AR 16:00 05 0 16:00 1.8 1.8 1.8 1.8 1.7 1.8 1.8 1.8 1.8
SENS= 60.2 [kcal/h/pessoa] REN= 0 [m3/h/pessoa] 17:00 05 0 17:00 1.8 1.8 1.8 1.7 1.7 1.7 1.8 1.8 1.8
LAT= 38.7 [kcal/h/pessoa] Fp L/S* PESSOAS = 0 18:00 05 0 18:00 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.8
Qsensível 70 Qlatente 45 Fa L/S* m² = 0 20:00 00 0 20:00 1.5 1.5 1.5 1.5 1.4 1.5 1.5 1.5 1.5
ILUMINAÇÃO 22:00 00 0 22:00 1.4 1.4 1.4 1.4 1.3 1.4 1.4 1.4 1.4
LÂMPADAS C/ REATORES= 0 [W] 24:00 00 0 24:00 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.4
LÂMPADAS S/ REATORES= 500 [W]

EQUIPAMENTOS ELÉTRICOS COEFICIENTES DE TRANSMISSÃO


2.0
POT. TOTAL= 1500 [W] PAREDES EXT= 3 [kcal/h/m2/°C]
FATOR SIMULTANEIDADE= 0.5 [-] PAREDES INT= 2.7 [kcal/h/m2/°C]
1.8
TETO/TELHADO= 2.1 [kcal/h/m2/°C]
OUTROS EQUIPAMENTOS PISO= 0 [kcal/h/m2/°C] 1.6
SENS= 0 [kcal/h] VIDROS= 4 [kcal/h/m2/°C]
LAT= 0 [kcal/h] FATORES PARA INSOLAÇÃO POR VIDROS 1.4
FATOR DE SOMBRA= 0.55
1.2
ÁREA DE PAREDES, VIDROS, TETOS E PISOS FATORES DE CORREÇÃO = 1.26
1.0
[m2] FATORES DE COR PESO [kg/m2]
PISO + TETO INTERNO 21.3 PAREDES (b)= 0.33 100 (100/300) 0.8
TELHADO (SOL) 0 TETO (b) = 0.33 50 (50/100)
VIDROS HORIZ. (SOL) 0 0.6
PAREDES INTERNAS 104.4
VIDROS INTERNOS 0 0.4
ÁREAS [m2]
0.2 JAN FEV MAR NOV DEZ
ORIENTAÇÃO S SE E NE N NO O SO SOMBRA
PAREDES EXTERNAS 0 0 0 0 0 0 0 0 25.2
0.0
VIDROS EXTERNOS (SOL) 0 0 0 0 0 0 0 0 4.2 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 20:00 22:00 24:00
,
FATORES DE SEGURANÇA (VERÃO) CARGA TÉRMICA MÁXIMA - VERÃO
MOTOR VENTILADOR= 5 [%]
CALOR SENSÍVEL= 0 [%] MÊS: MAR INTERNO SENSÍVEL INTERNO LATENTE INTERNO TOTAL EXTERNO TOTAL C. TÉRMICA TOTAL
CALOR LATENTE= 5 [%] HORA: 15:00 5273 kcal/h 203 kcal/h 5476 kcal/h 0 kcal/h 5476 kcal/h
1.8 TR

FATORES DE MULTIPLICAÇÃO (INVERNO) CARGA TÉRMICA DE INVERNO


EQUIPAMENTOS= 1 [-]
ILUMINAÇÃO= 1 [-] INTERNO SENSÍVEL INTERNO LATENTE INTERNO TOTAL EXTERNO TOTAL C. TÉRMICA TOTAL
PESSOAS= 1 [-] -6335 kcal/h 194 kcal/h -6142 kcal/h 0 kcal/h -6142 kcal/h
OUTROS EQUIPAMENTOS= 1 [-] -2.0 TR

ÍNDICES COMPARATIVOS (VERÃO) 12.8 m2/TR 76.5 m3/TR 0.36 TR/pessoa 0.0 (m3/h)AE / TR

Compartilhado por Rodrigo V. Machado


Oliar Serviços e Comércio Ltda
F:(47) 3025-5070

OLIAR SERVIÇOS E COMÉRCIO LTDA EPP


Rua Bernardo Welter, 65 joinville – SC | CEP: 89.220-230
Fone: (47) 3025-5070 | Email: adm@oliar.srv.br