Você está na página 1de 16

Stepping Up to the Avançando para o futuro com

Future with Power transformadores de potência

Transformers Estratégias de gerenciamento de ativos de


transformadores de potência: estado da arte e
recomendações para o futuro
Power Transformer Asset
Os transformadores têm sido usados na
Management Strategies: State of the indústria de energia por mais de um século, desde
Art and Recommendations for the que o uso generalizado de geração, transmissão e
Future distribuição CA tornou-se o padrão. Mesmo agora,
eles continuam sendo um dos ativos de subestação
Transformers have been used in the power
mais importantes que as concessionárias de todo o
industry for more than a century since the
mundo planejam e operam. A Figura 1 mostra um
widespread use of ac generation, transmission, and
transformador de 200 MVA em serviço em uma
distribution became the standard. Even now, they
subestação da concessionária. Nas últimas
remain one of the most important substation
décadas, com um rápido impulso em direção à
assets that utilities around the world plan and
digitalização da rede devido à proliferação de
operate. Figure 1 shows a 200-MVA transformer in
recursos de energia distribuídos (DER), a antiga
service at a utility substation. In the past few
estratégia de gerenciamento de ativos de
decades, with a rapid push toward grid
transformadores também evoluiu para melhor.
digitalization due to the proliferation of distributed
energy resources (DER), the age-old transformer Os transformadores de potência modernos
asset management strategy has also evolved for geralmente são projetados para densidades de
the better. fluxo mais altas para reduzir o tamanho do
transformador. No entanto, com densidades de
Modern power transformers are often
fluxo mais altas, a perda do núcleo e o
designed for higher flux densities to reduce the
consequente aumento da temperatura do
transformer size. However, with higher flux
transformador podem se tornar um problema. Com
densities, the core loss and resulting increased
o aumento da penetração dos DERs, o fluxo reverso
transformer temperature can become a problem.
de potência também se torna difícil de lidar, a
With the increased penetration of DERs, reverse
menos que as concessionárias prestem atenção e
power flow also becomes challenging to handle
especifiquem novos transformadores
unless utilities pay attention and specify new
adequadamente. As concessionárias em todo o
transformers accordingly. Utilities around the globe
mundo devem planejar estratégias eficazes de
should plan for effective predictive maintenance
manutenção preditiva, pois recorrer ao
strategies, as falling back on "overdesign" might
"overdesign" pode não ser mais relevante.
not be relevant anymore.
As concessionárias devem buscar uma
Utilities must strive for a holistic transformer
estratégia holística de gerenciamento de ativos de
asset management strategy that clearly defines the
transformadores que defina claramente a estrutura
structure being followed based on periodic
a ser seguida com base na coleta periódica de
standard data collection, monitoring packages, and
dados padrão, pacotes de monitoramento e testes.
tests. The following sections will be a quick tour of
As seções a seguir serão um tour rápido pelos
transformer loading capability calculations, impacts
cálculos de capacidade de carga do transformador,
of reverse power flow on transformers due to DER
impactos do fluxo de potência reverso em
growth, economic analysis of transformers,
transformadores devido ao crescimento de DER,
possible spare transformer strategies in light of
análise econômica de transformadores, possíveis
enhanced data and supply chain challenges and
estratégias de transformadores sobressalentes à luz
reliability implications of transformer failures.
de dados aprimorados e desafios da cadeia de
suprimentos e implicações de confiabilidade de
falhas de transformadores .
Transformer Operational issues and
Insights
Transformer Loading Capability Problemas operacionais e insights do
Calculations transformador
The transformer loading capability
Cálculos de Capacidade de Carga do
calculation is a significant element in determining a
Transformador
transformer's normal short-term emergency (STE)
and long-term emergency (LTE) mega volt-ampere O cálculo da capacidade de carga do
(MVA) ratings. A normal rating is generally the 24-h transformador é um elemento significativo na
continuous rating. However, rating practices vary determinação das classificações normais de
among different countries and among organizations emergência de curto prazo (STE) e emergência de
within the same country. Sometimes, ambient longo prazo (LTE) de megavolt-ampere (MVA) de
temperatures are considered for calculating ratings. um transformador. Uma classificação normal é
An STE is something shorter than 24 h and can be geralmente a classificação contínua de 24 horas. No
anything from 15 min to even 4 h, depending on entanto, as práticas de classificação variam entre
which region of the world we are talking about. diferentes países e entre organizações dentro do
The same argument goes for an LTE, which is longer mesmo país. Às vezes, as temperaturas ambientes
than an STE but shorter than 24 h. There are são consideradas para calcular as classificações.
entities in the United States that consider the same Um STE é algo menor do que 24 horas e pode
MVA rating for both STEs and LTEs. Such ratings are variar de 15 minutos a até 4 horas, dependendo de
typical inputs into transformer models used in qual região do mundo estamos falando. O mesmo
planning studies and help determine loading argumento vale para um LTE, que é mais longo que
capabilities in real-time operations. um STE, mas menor que 24 horas. Existem
entidades nos Estados Unidos que consideram o
There are several ways a utility can define
mesmo rating MVA tanto para STEs quanto para
how to rate its transformers, which range in
LTEs. Essas classificações são entradas típicas em
degrees of complexity. However, it is critical that
modelos de transformadores usados em estudos
the methodology be defined and follow, maintain
de planejamento e ajudam a determinar as
compliance with certain mandatory “North
capacidades de carregamento em operações em
American Electric Reliability Corporation”
tempo real.
standards, such as FAC-008, which mandates that
each utility develop and mains a rating Existem várias maneiras pelas quais uma
methodology for bulk electric system transform. concessionária pode definir como classificar seus
Before delving more into transformer ratings that transformadores, que variam em graus de
are followed by utilities, it is pertinent to have a complexidade. No entanto, é fundamental que a
brief discussion of the transformer core flux metodologia seja definida e seguida, mantendo a
densities at this point to set the ground for the conformidade com certos padrões obrigatórios da
reverse power flow that will be discussed later. “North American Electric Reliability Corporation”,
como FAC-008, que exige que cada concessionária
desenvolva e mantenha uma metodologia de
classificação para a transformação do sistema
elétrico em massa. Antes de aprofundar mais nas
classificações do transformador que são seguidas
pelas concessionárias, é pertinente ter uma breve
discussão sobre as densidades de fluxo do núcleo
do transformador neste ponto para definir o
terreno para o fluxo de potência reverso que será
discutido posteriormente.
Figure 1. A representative 200 MVA power
transformer at a utility substation
International Electrotechnical Commission
(IEC) 60076-1-2011, which is followed by many
A Comissão Eletrotécnica Internacional (IEC)
nations worldwide, specifies a voltage/frequency
60076-1-2011, seguida por muitas nações em todo
(V/f) of 110% of the rated V/f for the continuous
o mundo, especifica uma tensão/frequência (V/f)
no-load operation of power transformers. The flux
de 110% da V/f nominal para a operação contínua
density in the core is directly proportional to V/f if
sem carga de transformadores de potência.
the number of turns and the core area are kept
A densidade de fluxo no núcleo é diretamente
constant for a transformer in service. As per the
proporcional a V/f se o número de espiras e a área
IEC, along with the no-load requirement, power
do núcleo forem mantidos constantes para um
transformers should not be operated at a flux
transformador em serviço. De acordo com o IEC,
density over 5% more than they were designed for.
juntamente com o requisito sem carga, os
Generally, for cold-rolled grain-oriented silicon
transformadores de potência não devem ser
steel, which is one of the most popular core
operados com uma densidade de fluxo acima de
materials, 1.9 T is the absolute maximum flux
5% a mais do que foram projetados. Geralmente,
density that a transformer might operate at to have
para aço silício de grão orientado laminado a frio,
the additional 5% headroom for core saturation.
que é um dos materiais de núcleo mais populares,
Generally, and though it might differ slightly around
1,9 T é a densidade de fluxo máxima absoluta em
the world, flux densities of 1.7 T for generator step-
que um transformador pode operar para ter 5% de
up transformers and 1.6-1.65 T for others are often
margem adicional para saturação do núcleo.
used. A flux density lower than these values might
Geralmente, e embora possa diferir ligeiramente
also be used for specific reasons, such as low-noise
em todo o mundo, as densidades de fluxo de 1,7 T
requirements for transformers used in urban areas
para transformadores elevadores de geradores e
and mitigating reverse power flow impacts for
1,6-1,65 T para outros são frequentemente usadas.
areas that are predicted to witness DER growth.
Uma densidade de fluxo inferior a esses valores
Now, coming back to transformer ratings, também pode ser usada por motivos específicos,
multiple ways exist to define a rating methodology como requisitos de baixo ruído para
for bulk electric system transformers and other transformadores usados em áreas urbanas e
lower-voltage transformers. For instance, a utility mitigação de impactos de fluxo de energia reversa
may simply use a transformer's nameplate rating as para áreas que estão previstas para testemunhar o
its normal operating rating and 110% of its crescimento de DER.
nameplate rating as its STE rating, based on good
Agora, voltando às classificações do
utility practice and engineering judgment. Design
transformador, existem várias maneiras de definir
and manufacturing margins cause the temperature
uma metodologia de classificação para
rise test results at the transformer nameplate
transformadores de sistema elétrico em massa e
rating to be less than the defined temperature limit
outros transformadores de baixa tensão. Por
values. This way is simple to justify, document, and
exemplo, uma concessionária pode simplesmente
review but lacks technical details and possibly
usar a classificação nominal de um transformador
underestimates a transformer's loading capability,
como sua classificação operacional normal e 110%
which may negatively impact grid capacity.
de sua classificação nominal como sua classificação
STE, com base nas boas práticas da concessionária
e no julgamento de engenharia. As margens de
projeto e fabricação fazem com que os resultados
do teste de aumento de temperatura na
classificação da placa de identificação do
transformador sejam menores que os valores
limites de temperatura definidos. Esta forma é
simples de justificar, documentar e revisar, mas
carece de detalhes técnicos e possivelmente
subestima a capacidade de carregamento de um
transformador, o que pode impactar
negativamente a capacidade da rede.
A more rigorous way of determining a Uma maneira mais rigorosa de determinar a
transformer's loading capability is using IEEE capacidade de carga de um transformador é usar as
C57.91 clause 7 equations, which are used to equações IEEE C57.91 cláusula 7, que são usadas
calculate the operating temperatures (oil and para calcular as temperaturas operacionais (ponto
winding hottest spot) of a transformer, based on mais quente do óleo e do enrolamento) de um
the load cycle and ambient temperature. The transformador, com base no ciclo de carga e na
equations can also be used to determine the temperatura ambiente. As equações também
reduction of a transformer's insulation life podem ser usadas para determinar a redução da
referenced to a benchmark value. The allowable vida útil do isolamento de um transformador com
loading capability for any defined load cycle and referência a um valor de referência. A capacidade
ambient temperature profile is determined by de carga permitida para qualquer ciclo de carga
iterating the calculations until any one of the definido e perfil de temperatura ambiente é
temperature, loss of life, or maximum per-centage determinada pela iteração dos cálculos até que
of nameplate rating limits is reached. qualquer um dos limites de temperatura, perda de
vida ou porcentagem máxima dos limites de
A simplified calculation process for clause 7
classificação da placa de identificação seja atingido.
is described in Figure 2. Measured temperature
(i.e., ambient, winding hottest spot, winding Um processo de cálculo simplificado para a
average, top oil, and so on) and kilowatt loss data cláusula 7 é descrito na Figura 2. A temperatura
(i.e., load and no-load losses) are obtained from medida (ou seja, ambiente, ponto mais quente do
factory tests based on rated loads. As a result of enrolamento, média do enrolamento, óleo superior
considering the site-specific ambient temperature e assim por diante) e dados de perda de quilowatts
profile and the iterative process to identify the (ou seja, perdas de carga e sem carga) são obtidos
maximum allowable load (mega volt-ampere) de testes de fábrica com base em cargas nominais.
rating, the ultimate load is likely greater than the Como resultado de considerar o perfil de
rated one, which can be used as a new loading temperatura ambiente específico do local e o
capability rating and provide more capacity processo iterativo para identificar a classificação de
headroom for a dispatcher. In summary, clause 7 carga máxima permitida (mega volt-ampère), a
equations are needed to derive the ultimate carga final é provavelmente maior do que a
transformer operating temperatures with ultimate nominal, que pode ser usada como uma nova
loads and ambient temperatures. The calculations capacidade de carga classificação e fornecer mais
are included in an iterative process, which espaço livre de capacidade para um despachante.
gradually increases a transformer's ultimate load Em resumo, as equações da cláusula 7 são
until one of the criteria is reached (typically the necessárias para derivar as temperaturas máximas
winding hottest-spot temperature threshold). Such de operação do transformador com cargas
an ultimate load will be documented as the máximas e temperaturas ambientes. Os cálculos
transformer's loading capability or MVA rating são incluídos em um processo iterativo, que
associated with the input load and ambient aumenta gradualmente a carga final de um
temperature profiles. transformador até que um dos critérios seja
alcançado (normalmente o limite de temperatura
do ponto mais quente do enrolamento). Essa carga
final será documentada como a capacidade de
carga do transformador ou classificação MVA
associada à carga de entrada e aos perfis de
temperatura ambiente.
To the best of our knowledge, some utilities Até onde sabemos, algumas concessionárias
adopt the clause 7 methodology by assuming a adotam a metodologia da cláusula 7, assumindo
constant load (e.g., one per unit) and average daily uma carga constante (por exemplo, uma por
ambient temperature (e.g., 30 °C). This unidade) e temperatura ambiente diária média
methodology does not consider load and ambient (por exemplo, 30 °C). Essa metodologia não
temperature variation in the calculations, which considera a variação de carga e temperatura
simplifies the process but leads to a potentially ambiente nos cálculos, o que simplifica o processo,
more conservative loading capability result. As mas leva a um resultado de capacidade de
detailed in Figure 3(a), the ambient temperature carregamento potencialmente mais conservador.
(yellow bars) and the transformer loading (black Conforme detalhado na Figura 3(a), a temperatura
line) are assumed constant. When the transformer ambiente (barras amarelas) e a carga do
is loaded to 1.15 per unit (the black line), the transformador (linha preta) são consideradas
calculated winding hottest-spot temperature constantes. Quando o transformador é carregado a
reaches its limit (120 °C), as shown by the red 1,15 por unidade (a linha preta), a temperatura
dashed line. In other words, the transformer's calculada do ponto mais quente do enrolamento
loading capability is 1.15 per unit, with a binding atinge seu limite (120 °C), conforme mostrado pela
constraint at the winding hottest-spot temperature. linha tracejada vermelha. Em outras palavras, a
capacidade de carga do transformador é de 1,15
As shown in Figure 3(b), if a variable ambient
por unidade, com uma restrição obrigatória na
temperature (yellow bars) and transformer load
temperatura do ponto mais quente do
cycle curve (black line) are considered, the
enrolamento.
resulting winding hottest-spot temperature (red
dashed line) and top oil temperature (blue dashed Conforme mostrado na Figura 3(b), se uma
line) curves are obtained. In this example, the temperatura ambiente variável (barras amarelas) e
winding hottest-spot temperature reaches its limit uma curva de ciclo de carga do transformador
(120 °C) at 9 p.m., which is the binding constraint (linha preta) forem consideradas, a temperatura do
limiting the transformer loading capability at 1.23 ponto mais quente do enrolamento resultante
per unit when the peak load occurs at 7 p.m. Note (linha tracejada vermelha) e a temperatura do óleo
that the load cycle curve such as the black line in superior (linha tracejada azul curvas são obtidas.
Figure 3(b)1 is defined with its constant shape but Neste exemplo, a temperatura do ponto mais
can be shifted up or down until a constraint (the quente do enrolamento atinge seu limite (120 °C)
winding hottest-spot temperature or top oil às 21h, que é a restrição obrigatória que limita a
temperature) is binding. This comparison shows capacidade de carregamento do transformador em
that considering variable ambient temperature and 1,23 por unidade quando o pico de carga ocorre às
load cycle curves likely increases a transformer's 19h. Observe que a curva do ciclo de carga, [como
loading capability because a transformer is loaded a linha preta na Figura 3(b)], é definida com sua
with variable loads that help dissipate heat. forma constante, mas pode ser deslocada para
cima ou para baixo até que uma restrição (a
temperatura do ponto mais quente do
enrolamento ou a temperatura do óleo no topo)
seja obrigatória. Essa comparação mostra que
considerar a temperatura ambiente variável e as
curvas de ciclo de carga provavelmente aumenta a
capacidade de carga de um transformador porque
um transformador é carregado com cargas variáveis
que ajudam a dissipar o calor.
We also benchmarked how variable load
cycle curves impact a transformer's operating
temperatures. In Figure 4, a load curve with a solid
green line represents a typical "duck" load shape,
which involves a lower demand when sufficient
solar radiation is available around 2 p.m., followed
by a rapidly increasing demand ramp from 3 to 6
p.m. To the contrary, the other load curve with a
dashed green line pertains to a traditional load
shape for a region with an insignificant amount of
DERs. Note that the DERs considered in this article
are mainly solar rooftop systems. However, other
forms of DERs, including battery energy storage
systems, should be evaluated for transformer
loading capability calculations and their potential
impacts. The red solid- and dashed-line curves
represent the calculated winding hottest-spot
temperature results pertaining to the "duck" and
traditional load shapes. respectively, which are
both limited at 120 °C as desired. The peak loading
capability of the transformer for the "duck" load
shape is higher than that for the traditional load
shape. A transformer energized under a "duck"
curve can bear a higher peak load, as the heat
inside the transformer is accumulated starting from
a lower temperature (at 2 p.m.). Also note that the
trend of a transformer’s operating temperature
(i.e., the winding hottest-spot temperature) always
lags that of the load curve. For example, the peak
of the "duck" load curve (solid green line) occurs at
6 p.m., while the peak of its corresponding winding
hottest-spot temperature (solid red line) occurs
two hours later, at 8 p.m. This delay between the
transformer peak load and peak winding hottest-
spot temperature is due to the time constant for a
transformer's oil temperature change. In other
words, a transformer's operating temperatures
cannot change immediately with the load change,
as the transformer oil has a high heat capacity.
Based on IEEE-057.91, during transformer
overload, STE and LTE operations, the temperature
of the oil in tike winding cooling ducts rises rapidly
at a time constant much shorter than the bulk oil
inside the tank. Therefore, during this transient
condition, the duct oil temperature adjacent to the
winding hottest-spot location is higher than the top
oil temper¬ature in the tank. Figure 4 illustrates
this occurrence, where the orange curve
representing the winding duct oil temperature
sur¬passes the blue curve representing the tank
top oil temperature right after 3 p.m. Note that, at
3 p.m., the load ramps up due to the decrease of
photovoltaic generation. This situation occurs
because the wind¬ing duct oil reacts to the ramp of
the load more quickly than the reaction of the tank
oil, due to a shorter time constant. This phenom-
enon needs to be noted because it can result in
winding hottest-spot temperatures greater than
calcu¬lated by the equations of clause 7, which do
not consider the winding duct oil temperatures as a
medium to calculate the winding hottest-spot
temperatures (as shown in Figure 5). Therefore, the
IEEE-C57.91 working group provides an alternate
methodology to better reflect the thermal
transforma¬tion among windings, duct oil, and
tank oil while considering various cooling methods.

Reverse Power Flow Impacts to Transformers


Another emerging trend surfacing in the utility
space is the impact of reverse power from DERs
back to the grid through transformers. Due to the
large-scale penetration of DERs, there has been a
growing concern about reverse power flow
and its impact on interface transformers. Reverse ers both active and reactive power
power flow happens when power starts to flow
to the grid (—P, —Q), an example of
from the distribution to the transmission system
through interface transformers, due to large-scale a third quadrant operation. In this
renewable penetration producing more power than
a local load requires and due to the absence of case, the active power P flows from
adequate energy storage capabilities in the the load (DER) to the grid, while
distribution DER nodes to which the DERs are
connected. the phase angle between vl and v2

The question is, Does reverse power flow affect is less than zero, or v, leading v1, figure 5. The
transformer health, and how can utilities prepare winding duct oil temperatures versus the top oil
for this phenomenon in the coming years as more
DERs get interconnected to the power system?
Let's consider a two-winding transformer with its
high side connected to the grid and its low side
connected to a load or DER. The high-side voltage
is v1, and the low-side terminal voltage is v2, with
v, being the reference for comparison. Now, if the
low side is connected to an inductive load, such as
a motor. that draws a lag¬ging reactive power. both
active

power P and reactive power Q flow

from the grid side to the load side.

The phase angle between v, and v2

is greater than zero, or v, leads v2,

and the magnitude of the excitation

voltage E, in this case, is greater

than the magnitude of the load ter-

minal voltage v,. This is the case

where the transformer is operat-

ing in the first quadrant (+P, +Q),

and the magnetizing current I. is drawn from the


grid.

In the second scenario, we con¬sider a second


quadrant opera¬tion where the load side delivers
active power (—P) but absorbs reac¬tive power
(+Q). In this case, active power flows from the load
side to the grid, with the phase angle between v1
and v, now less than zero, or v, leading v1, and the
mag¬nitude of the excitation voltage E is greater
than the magnitude of the load side terminal
voltage v2. The magnetizing current Im is again
drawn from the grid in this case. In the third
scenario, let's consider the situation when the load
side deliv-
side. Since the active power flows from the grid experience, are aware of this problem and
side to the load side, the phase angle between v, currently working diligently to solve this issue in
and v2 is positive, or v, leading v2. The magnitude multiple ways. Increased taps for on-load tap
of the excitation voltage E is less than the changers and core designs with reduced flux
magnitude of the load side terminal voltage v2, and densities are some of the possible resolutions of
hence, the magnetizing current. In, is supplied by this problem. However, there are several legacy
the DER in this scenario. In a transformer core, the transformers in the system today that face the
magnetizing flux is set up by the exci¬tation voltage challenges outlined in this section.
E through the magnetizing current I,,,. When the
For new transformers, it is important to understand
transformer is operating in the first and the second
these design considerations if a transformer will be
quadrants, the core flux is established by the grid
installed at a place where there is high DER growth
voltage. When the trans¬former is operating in the
or DER growth is pre¬dicted to rise in the future.
third and the fourth quadrants, the excitation
For existing transformers in places with high DER
voltage and, i.n turn, the core magnetizing flux are
penetration, monitoring transformer harmon¬ics at
initiated by the DER instead. Transformers are
close time intervals throughout the year,
designed such that the flux in the core is
depending on the geography and DER penetration,
established by the grid voltage, which is tightly
should be prioritized. Moreover, transformer
regulated in a certain hand and for all practical
primary and secondary voltage checks should
pur¬poses can he taken as constant.. When the
provide a way to understand whether there is an
core flux is instead set up by the DER, it is seen
issue in case reverse power flow is happening at
through practical utility experience that the flux
the interface. When ordering new interface
will increase in the core during reverse power flow.
transformers in areas of the grid that are predicted
The point to understand here is that transformers to witness high DER penetration, aohtl
are optimally designed to operate close to the knee
point of their magnetizing characteristics.
Therefore, any increase in the core flux density will
increase the transformer core losses significantly.
Increased core loss might affect the thermal life of
a transformer. Moreover, grid voltage being
constant, if the excitation current increases due to
the DER, there is a good chance of core saturation.
Core saturation in a trans-former creates additional
losses and harmonics. A typical three-limb core-
type transformer does not provide a path

for zero sequence flux, and hence, increased


harmonics and

core saturation can be greatly aggravated in these


scenarios.

Therefore, a good possibility exists that the life of a


trans¬former might be shortened due to reverse
power flow, and hence, some utilities in the United
States already have specific reverse power flow
requirements limiting the amount of reverse power
flow through interface transformers. Also, utilities
might be able to get ahead of this problem by
initiating a conversation with transformer
manufacturers, most of which, by the authors'
low flux ratio can be chosen (1.5 or 1.6 T) instead transformer asset strategies to reflect longer lead
of the more standard 1.7 T. Distribution planning in times for replacement planning. Histori¬cally,
a high-DER penetra-tion scenario becomes quite utilities typically run transformers to failure and
different and more challenging than traditional carry
utility distribution planning, and a minimum
loading criterion might need to be developed with
thorough studies and expertise to prevent reverse
power flow if operat-ing with legacy transformer
designs.
Challenges Due to Long Transformer Lead Time In
addition to the challenges of planning for increased
lev¬els of DERs on circuits, the availability of
transformers is another issue facing the utility
industry today. Due to COVID-19 and supply chain larger spare inventory levels to account for
disruptions, the power indus¬try is now witnessing unplanned failures, or they elect to do planned
a challenge in procuring some key assets. and replacements and carry leaner inventories. Utilities
transformers have become particularly running transformers to failure and those that use
challeng¬ing to procure in a normal time frame. In planned replacements must update their strategies
the United States, approximately 90% of the and models to account for longer lead times. Not
consumed power flows through adjusting the spare transformer strategy based on
current lead times can be a problematic long-term
large power transformer (LPT). Due to the shortage approach, due to long lead times of 18-24 months
of domestic manufacturers, most of the LPTs are for purchasing and receiving a new transformer.
imported, and this creates a potential supply The average life expectancy of a transformer is
bottleneck. Utilities are now challenged with typically 40-50 years. If a certain percentage of
evolving their spare equipment strategies to transformers operating in the utility footprint are
incorporate the longer lead times for LPTs to nearing typical life expec¬tancy, additional
maintain grid resilience. Moreover, LPT trans- monitoring and asset replacement planning should
portation and overall logistics are also challenging be prioritized. This will ensure that the inventory
and should be planned efficiently. Figure 6 shows strat¬egy is still appropriate, given the health of the
an LPT being transported to be put in service in the transformer fleet in this long-lead-time
AES Ohio service territory. environment.

In June 2022, the United States mandated the use Transformer Asset Health Monitoring Strategies
of the Defense Production Act to increase the The goal of this section is to recommend
output of transformers for domes¬tic transformer asset health monitoring strategies to
manufacturers. Figure 7 pres¬ents a representative transition the industry to a future state where
process to acquire an LPT by a utility. This process, predictive maintenance takes over pre-emptive
as of writing this article, can take anywhere from maintenance due to failure. To facilitate this,
12 to 24 months, and hence, pro¬active planning utilities
becomes key. Figure 8 gives the global transformer
trade average export value by power rating
capability, and we can see that LPTs are globally the
most sought-after component in the transformer
manufacturing industry. Due to challenges in the
supply chain owing to COVID-19 and other factors,
it is essential that utilities take a proactive role in
identifying transformers that are essen¬tial to
manage the bulk power system reliability. It is also
important for utilities to develop their own scoring
model based on tests and
monitoring/instrumentation data and create a
sound spare transformer strategy.
Spare Transformer Strategy: Past and Present As a
result of the supply chain challenges facing the
industry, utilities must evolve their spare
should develop a transformer instrumentation
standard (such as the information listed in Table 1)
that will ensure that data are brought back from
operations and into asset management platforms of critical electrical equipment, and hence,
used for continuous monitoring in operations and experience and expert engineering judgment
long-range strategic asset planning. This developed should always be consulted and are recommended.
standard will serve as the basis for future A good utility practice is to perform TM DGA,
purchasing specifications outlining the maintaining a good bookkeeping practice of the
instrumentation needs for the concerned util¬ity results and comparing earlier DGA reports with
high-voltage power transformers. This will also later ones. However, most indicators in these tests
serve to strategically recommend targeted advance rapidly, and hence, periodic testing in
instrumentation projects that address any major close intervals and comparing the results with
gaps with legacy transformers cur-rently in service. previous test reports are some of the key aspects
This developed instrumentation standard to be considered for DGA. Also, new engineers
document should set forth a minimum entering the testing field should note that if a
requirement of moni¬toring equipment to monitor transformer is cooled and de-energized or is a new
asset condition. transformer that has not yet com¬pleted at least
two to four weeks of continuous service, DGA
Prediction Based on Transformer Testing
results might be quite unreliable.
Many utilities perform annual oil testing, dissolved
Table 2 condenses some of the key
gas analysis (DGA), and a power factor test every
recommendations and action items from a DGA
three to five years. These tests are used to monitor
analysis. If the gas concen¬tration, in parts per
the health of a trans¬former and help predict when
million, exceeds the normal limits but is less than
the transformer will need to be replaced. DGA is
the action limits, the frequency of DGA test¬ing
often the first indication that problems exist with a
should be increased with some consideration given
transformer. DGA consists of sending oil sam¬ples
to planned outages in the future for further
to a laboratory for testing, as transformer oil health
evaluation. As the gas concentration exceeds the
is a good indicator of the overall transformer itself.
"action" column, removal of the transformer might
DGA reports individual and total combustible gas
be considered. It should be noted that these gas
generation rates based on IEC 60599 and/or IEEE
concentrations should be tested periodically, and
C57-104 standards.
any sharp increase in the concentrations might
There are some recommended industry rules to indicate a potential problem. In summary, just the
interpret a DGA report. However, transformers are concentration levels of these key gases should not
complex pieces be taken as an indication of a possible problem, but
the trend of these dissolved gas levels should be
evaluated to better understand DGA results.
table 1. An example of a standardized
One of the common causes of a transformer failure
instrumentation package for is the breakdown of the dielectric. Generally,
substation transformers. dielectric breakdown happens due to repeated
thermal cycles with high temperatures combined
with moisture, oxygen, and other air particulates. It
has been observed that dielectric breakdown in a
transformer is aggravated if the transformer is
overloaded frequently. A power factor test of a
transformer is done to test the ac char¬acteristics
of the transformer dielectric. Dielectric losses of a
based on predictive health measures from their
asset management department. Some companies
transforrnef),-: a p_ w31°factor
replace a set number of transformers every year,
test. When the transformer insulation is excii:ed by and others replace based on the health of a
-a known ac voltage, it draws charging current. The transformer. The latter would require a formal
charging current can be split into two components: process to assess the condition of a transformer.
capacitive and resistive current. As the name Predictive transformer replacements can be driven
suggests, capacitive current leads the applied by models derived from a utility's historical
volt¬age by 90°, whereas the resistive current datasets, analyzing past failures, historic test
component is in phase with the applied voltage. results, and maintenance records to train an
Capacitive current is directly pro¬portional to the advanced model capable of predicting future
dielectric constant of the insulation, area, and failures. Further, advanced analytical techniques
voltage and inversely proportional to the thickness could build
of the insu¬lation under test. Changes in capacitive
off this predictive model and pair it with a basic
current indicate insula¬tion degradation. As the
optimization model to establish optimal inventory
insulation deteriorates, more current will leak
levels based on predicted failures and dynamic
through the insulation, and the power factor
transformer lead times updated regularly based on
therefore becomes increasingly greater. The results
updated lead times from utility supply chain
of a power factor test will confirm the condition of
experts.
the insulation in the windings, bushings, tap
changers, and oil. For modern oil-filled power Spare Strategy: Future Recommendations
transformers, power factors of 0.5% or less, at 20
A long-term spare transformer strategy should he
°C (68 °F), for individual windings to ground and
transitioned to a risk-based methodology including
interwinding insulations are generally considered a
additional asset moni¬toring data. This strategy will
passing criterion.
help ensure that inventory levels directly align with
Spare Transformer: Present Strategies the probability of failures to ensure an opti¬mal
spare transformer strategy. As more data become
Companies employ different strategies with respect
avail¬able through asset monitoring, additional
to trans-former replacement. These range from run
performance metrics should be built into the risk
to failure to tar-geted replacement.
formula. It is recommended that transformer
Strategy 1: Run Transformers Until Failure and Have inventory levels be evaluated on an annual basis to
Large Spare Inventory to Account for Failures ensure that the inventory strategy is refreshed
Some companies choose to run their transformers based on the risk profile.
until there is a failure. This strategy ensures that Once a utility reaches a future state in online
the company has used the equipment to its fullest transformer monitoring, it may be possible to shift
extent but could come at the poten¬tial expense of to planned transformer replacements, versus the
operational risk posed by an unplanned fail¬ure. current methodology of running to failure, if
This philosophy would typically require a company sufficient leading indicators are developed that can
to maintain more spares so that it would be positively identify a failing transformer. This
prepared to replace a transformer after it fails and strategy would require fewer spare transformers
be able to have sufficient spares available for since the methodology determines which
multiple individual failures in a short time frame. A transformers to replace and when to replace them.
failure could happen at any moment and could As a part of the change to this strategy, utilities
create other issues in the system, so this justifies would need to create a transformer health index,
the need for a larger inventory of spares. It is criticality index, or risk index or some combination
recommended that utilities have at least a basic of the three that considers everything from
prediction model, if detailed predictive models are transformer test results, condition, and utili¬zation
not technically feasible, combined with inventory to location and criticality. As noted in this article,
lead time models to recommend the appropriate tar¬geted replacement is the strategy employed by
transformer strategy strategically and dynamically. most utilities, and a combination of these three
Strategy 2: Replacement Based on Asset metrics would help to better plan and prepare for
the future. This three-pronged scoring model might
Management Practices and Optimized Inventory be used to rank the worst-performing
Most companies employ a programmatic or transform¬ers in a utility footprint.
targeted replace-ment strategy for transformers, Health Index
Some of the recommended parameters that might
be used to create the health index are DGA, load
history, global loss factor, infrared thermography,
oil quality analysis, Omicron testing data, Furan's
content, leakage reactance, winding resis¬tance,
core to ground connection, conditions of bushings,
tank corrosion, and so on. Each of these
parameters can be assigned a weight, and an
overall quantitative health index can be
formu¬lated. These metrics were determined by
looking at the failure modes of a transformer and
understanding the maintenance and tests taken to
help understand how that transformer is
per¬forming. The biggest challenge that some
utilities might run into is the lack of data and the
lack of consistency in the data. With the data that
might be available, utilities might be able to rank all
these metrics from zero to 10, with 10 being
perfect health. For example, if a transformer has
high gas levels, then that can be assigned a certain
score threshold, depending on the severity and
internal utility practice.
A lesson that might help the industry, from the
authors' collective experience, is the fact that age
has a lower effect on transformer health than most
people think. Transformers
are created to withstand a lot of capacity. Unless power system. This article delineated some past
there are outside forces causing a unit to fail, the and state-of-the-art transformer failure prediction
age of a transformer is almost irrelevant to the methodologies that are used in the industry:
overall health. That is why age can have a small transformer asset health monitoring concepts,
weighting factor in the metrics developed. There instrumentation packages that are currently avail-
are quite a few 80-year-old transformers in some able, loading calculations, and the effect of reverse
util-ity territories that are still performing quite power
well. With all these data, metrics, and weighting
flow in transformers.
factors, a model should be built to monitor the
health of transformers. Transformer Proactive transformer health monitoring using
monitoring/instrumentation packages should be standard tests and bringing data from the field in
used and are recommended to augment the regular intervals to feed into a health model will be
developed models. In the future, using these key in moving to the future. Also, while planning
developed models, utilities should be able to for transformers in an area with high renewable
develop a structure feeding data into health score growth, care must be taken regarding the choice of
models to do predictive and preventative transformers and, if required, through adequate
maintenance and reduce outages. This will help system studies. Specifications regarding low-core-
utilities to shift from the strategy of running a flux designs might be incorporated at an early stage
transformer to failure. Understanding the in these areas. The authors' hope is that this article
difference between time-based maintenance and will inspire utilities to set up proactive standards
pre¬ventative/proactive maintenance is the key and requirements as we transition to a smarter
here. Obtaining data from the installed future with more active loads, renewables, and
transformers through using instru¬mentation and two-way power flow. As a final note, the authors
automation would help the models make bet¬ter would like to point out that the article is devoted
decisions. primarily to substation transformers and might not
be applicable for other transmis-sion and
The authors recommend that the developed health
distribution assets.
index should be reflective of the overall
transformer health and should provide an objective For Further Reading
evaluation instead of being a subjective IEEE Guide for Loading Mineral-Oil-Immersed
observation. The index should be understandable Transform-
and be interpreted easily for it to be widely useful.
ers and Step-Voltage Regulators, IEEE Standard
Criticality Index C57.91, 2011.
Since the health index depends on testing data, a IEEE Guide for the Interpretation of Gases
criticality index might also be defined for the Generated in Mineral Oil-Immersed Transformers,
benefit of the overall asset management plan. The IEEE Standard C57.104, 2019.
criticality index will assign a score to each
transformer, based on network location, load IEEE Standard for Interconnection and
serving crit¬icality, impact on system stability, Interoperability of Distributed Energy Resources
consequence of failure, and social and with Associated Electric Power Systems Interfaces,
environmental impacts, if any. Similar to the health IEEE Standard 1547-2018.
index, ft.- criticality index parameters might be Mineral Oil-filled Electrical Equipment in Service—
weighted depending on their relative importance. Guidance on the Interpretation of Dissolved and
For example, more weight might be given to system Free Gas¬es Analysis, IEC Standard 60599, 2022.
instability and load serving capability than some
other parameters, though this should depend on Office of Technology Evaluation, "The effect of
engineering judgment and is best left to utilities to imports of transformers and transformer
find out what works best for their footprint. components on the national security," Bureau of
Industry and Security, U.S. Department of
Risk Index Commerce, Washington, DC, USA, 2020. Accessed:
A risk index might be formulated, which is a Dec. 21, 2022. [Online.] Available:
combination of the health index and criticality https://www.bis.doc.gov/index.
index, with equal weight given to both. Since the php/documents/section-232-investigations/2790-
risk index takes into consideration redacted -goes-report-20210723-ab-redacted/fi le
Biographies
Rajarshi Roychowdhury

Você também pode gostar